PB iMPB Installation Manual Download Page 5

Powerbar 

iMPB

Step 5.

 

Tighten the joint pack center bolt to 25Nm using a calibrated torque 

wrench. If installed correctly the joint will appear level.

*The joint pack center bolt should be torqued to 25Nm

  (221 in/lbs)

Step 4. 

Attach the Bottom Joint pack cover using the M6 socket cap screws 

provided. Tighten to 10Nm. 

Bottom Joint pack cover

Page 04

Cable End Box

  This is generally the fi rst component to be mounted on a run.  

 

The entire route should initially be inspected for any obstructions before installation. 

  The box should be installed at the correct height in accordance with the approved drawings.

  A plumb line should be applied at this point from the start of the run to the end of the run, as a guide for the installation of the Busbar Run.

Joint Pack

Gland/Conduit plate

*A Joint Pack is pre-fi tted to each cable 

end box which determines the neutral 

side of the busbar run. The approved 

drawings will show this detail.  

Joint pack Center Bolt

Summary of Contents for iMPB

Page 1: ...iMPB Installation Manual...

Page 2: ...must be safely secured to the lifting apparatus before lifting Always check that the load does not exceed the safe working load of the lifting apparatus Ensure that equipment is used as per manufactur...

Page 3: ...ts Care is to be taken not to damage ends of the busbar during installation Powerbar recommends the hanging brackets be mounted no more than 1 5 metres 5 apart Ensure that each section of busbar has a...

Page 4: ...ar orientation and site conditions may restrict installers from adhering to this methodology In these cases installers must be cautious and ensure the joint pack is installed correctly Ensure all part...

Page 5: ...ally the first component to be mounted on a run The entire route should initially be inspected for any obstructions before installation The box should be installed at the correct height in accordance...

Page 6: ...omprise an arrangement of enclosure circuit breaker monitoring device on load isolator and safety interlocks which provide a unique set of safety features for installation and allow the tap off module...

Page 7: ...ll connected load to the Busbar Trunking via tap offs for example should be isolated prior to energizing the bar The Main Supply switch to the Busbar is to be energized first The Protection Settings s...

Page 8: ...66536 E I Engineering Corporation USA Manufacturing Location 400 Supreme Industrial Drive Anderson South Carolina 29621 Tel 1 864 375 1757 E I Engineering LTD European Manufacturing Location Ballydero...

Reviews: