7
ELECTRICAL DATA
PA13NAZ
UNIT
SIZE
V---PH---Hz
VOLTAGE RANGE*
COMPRESSOR
OUTDOOR FAN MOTOR
MIN
CKT
AMPS
FUSE/CKT
BKR AMPS
Min
Max
RLA
LRA
FLA
NEC
Hp
kW
Out
018---A
208/230---1---60
187
253
9.0
48.0
0.8
0.125
0.09
12.1
20
024---B
208/230---1---60
187
253
13.5
58.3
0.8
0.125
0.09
17.7
25
030---A
208/230---1---60
187
253
14.1
73.0
1.5
0.250
0.19
19.1
30
036---A
208/230---1---60
187
253
14.1
77.0
1.5
0.250
0.19
19.1
30
208/230---3---60
187
253
9.2
71.0
1.5
0.250
0.19
13.0
20
460---3---60
414
506
5.6
38.0
0.8
0.250
0.19
7.9
10
048---B
208/230---1---60
187
253
19.9
109.0
1.5
0.250
0.19
26.4
40
208/230---3---60
187
253
13.1
83.1
1.5
0.250
0.19
17.9
25
460---3---60
414
506
6.1
41.0
0.8
0.250
0.19
8.4
15
060---B
208/230---1---60
187
253
26.4
134.0
1.5
0.250
0.19
34.5
60
208/230---3---60
187
253
15.0
110.0
1.5
0.250
0.19
21.5
30
460---3---60
414
506
7.8
52.0
0.8
0.250
0.19
10.6
15
* Permissible limits of the voltage range at which the unit will operate satisfactorily
FLA
--- Full Load Amps
HACR
--- Heating, Air Conditioning, Refrigeration
LRA
--- Locked Rotor Amps
NEC
--- National Electrical Code
RLA
--- Rated Load Amps (compressor)
NOTE
: Control circuit is 24---V on all units and requires external power source. Copper wire must be used from service disconnect to unit.
All motors/compressors contain internal overload protection.
Complies with 2007 requirements of ASHRAE Standards 90.1
A--WEIGHTED SOUND POWER LEVEL
Unit Size
Standard
Rating
(dBA)
Standard
Rating
(dBA)
With Sound
Blanket
Typical Octave Band Spectrum (dBA, without tone adjustment)
125
250
500
1000
2000
4000
8000
018
70
51.5
56.5
63.5
62.5
60.5
57.0
45.5
69
50.0
57.0
60.5
62.0
60.0
56.0
44.5
024
73
59.5
64.0
65.5
68.5
61.0
57.0
46.0
72
56.0
64.0
66.0
69.0
62.5
58.0
47.5
030
74
58.5
62.0
65.5
66.5
66.5
65.0
58.0
73
59.0
62.5
65.5
66.5
67.0
65.0
58.0
036
74
59.0
64.5
70.5
70.5
67.0
65.0
56.5
73
59.0
63.0
64.5
69.5
66.5
64.5
56.0
048
74
63.0
64.5
67.5
67.5
65.5
63.0
55.0
73
63.0
64.5
67.5
67.5
65.5
63.0
55.0
060
74
60.5
62.5
65.5
64.5
64.0
62.5
53.5
73
60.5
62.0
65.0
64.0
63.5
62.0
53.5
NOTE
: Tested in accordance with ARI Standard 270---08 (not listed in ARI).
CHARGING SUBCOOLING (TXV--TYPE EXPANSION DEVICE)
UNIT SIZE---VOLTAGE, SERIES
REQUIRED SUBCOOLING
_
F (
_
C)
018---A
12 (6.7)
024---B
12 (6.7)
030---A
12 (6.7)
036---A
12 (6.7)
048---B
12 (6.7)
060---B
12 (6.7)
PA
13N
AZ