Payne PA13NAZ Product Data Download Page 7

7

ELECTRICAL DATA

PA13NAZ

UNIT

SIZE

V---PH---Hz

VOLTAGE RANGE*

COMPRESSOR

OUTDOOR FAN MOTOR

MIN

CKT

AMPS

FUSE/CKT

BKR AMPS

Min

Max

RLA

LRA

FLA

NEC

Hp

kW

Out

018---A

208/230---1---60

187

253

9.0

48.0

0.8

0.125

0.09

12.1

20

024---B

208/230---1---60

187

253

13.5

58.3

0.8

0.125

0.09

17.7

25

030---A

208/230---1---60

187

253

14.1

73.0

1.5

0.250

0.19

19.1

30

036---A

208/230---1---60

187

253

14.1

77.0

1.5

0.250

0.19

19.1

30

208/230---3---60

187

253

9.2

71.0

1.5

0.250

0.19

13.0

20

460---3---60

414

506

5.6

38.0

0.8

0.250

0.19

7.9

10

048---B

208/230---1---60

187

253

19.9

109.0

1.5

0.250

0.19

26.4

40

208/230---3---60

187

253

13.1

83.1

1.5

0.250

0.19

17.9

25

460---3---60

414

506

6.1

41.0

0.8

0.250

0.19

8.4

15

060---B

208/230---1---60

187

253

26.4

134.0

1.5

0.250

0.19

34.5

60

208/230---3---60

187

253

15.0

110.0

1.5

0.250

0.19

21.5

30

460---3---60

414

506

7.8

52.0

0.8

0.250

0.19

10.6

15

* Permissible limits of the voltage range at which the unit will operate satisfactorily

FLA

--- Full Load Amps

HACR

--- Heating, Air Conditioning, Refrigeration

LRA

--- Locked Rotor Amps

NEC

--- National Electrical Code

RLA

--- Rated Load Amps (compressor)

NOTE

: Control circuit is 24---V on all units and requires external power source. Copper wire must be used from service disconnect to unit.

All motors/compressors contain internal overload protection.

Complies with 2007 requirements of ASHRAE Standards 90.1

A--WEIGHTED SOUND POWER LEVEL

Unit Size

Standard

Rating

(dBA)

Standard

Rating

(dBA)

With Sound

Blanket

Typical Octave Band Spectrum (dBA, without tone adjustment)

125

250

500

1000

2000

4000

8000

018

70

51.5

56.5

63.5

62.5

60.5

57.0

45.5

69

50.0

57.0

60.5

62.0

60.0

56.0

44.5

024

73

59.5

64.0

65.5

68.5

61.0

57.0

46.0

72

56.0

64.0

66.0

69.0

62.5

58.0

47.5

030

74

58.5

62.0

65.5

66.5

66.5

65.0

58.0

73

59.0

62.5

65.5

66.5

67.0

65.0

58.0

036

74

59.0

64.5

70.5

70.5

67.0

65.0

56.5

73

59.0

63.0

64.5

69.5

66.5

64.5

56.0

048

74

63.0

64.5

67.5

67.5

65.5

63.0

55.0

73

63.0

64.5

67.5

67.5

65.5

63.0

55.0

060

74

60.5

62.5

65.5

64.5

64.0

62.5

53.5

73

60.5

62.0

65.0

64.0

63.5

62.0

53.5

NOTE

: Tested in accordance with ARI Standard 270---08 (not listed in ARI).

CHARGING SUBCOOLING (TXV--TYPE EXPANSION DEVICE)

UNIT SIZE---VOLTAGE, SERIES

REQUIRED SUBCOOLING

_

F (

_

C)

018---A

12 (6.7)

024---B

12 (6.7)

030---A

12 (6.7)

036---A

12 (6.7)

048---B

12 (6.7)

060---B

12 (6.7)

PA

13N

AZ

Summary of Contents for PA13NAZ

Page 1: ...evels as low as 70 dBA Design Features S Small footprint same as old model and stackable S All steel cabinet construction S Baked on powder paint S Mesh coil guard Reliability Quality and Toughness S...

Page 2: ...er in mm 18 457 18 457 24 610 24 610 24 610 24 610 No Blades 3 3 3 3 3 3 Motor hp w 1 8 93 1 8 93 1 4 187 1 4 187 1 4 187 1 4 187 OUTDOOR COIL Face Area sq ft 5 8 7 3 12 1 12 1 14 1 14 1 No Rows 2 2 2...

Page 3: ...50 250 250 250 250 250 230 160 060 AC with R 410A 3 8 3 8 250 250 250 225 190 150 110 Maximum actual length not to exceed 200 ft 61 m Total equivalent length accounts for losses due to elbows or fitti...

Page 4: ...Level Outdoor Below Indoor Outdoor Above Indoor 1 4 No accessories needed within allowed lengths No accessories needed within allowed lengths 175 53 3 5 16 120 36 6 50 15 2 vertical or 120 36 6 total...

Page 5: ...inter Start Kit for low ambient X X X X X X KSACY0101AAA Cycle Protector X X X X X X KSAHS1501AAA Hard Start Kit X X X X X X KSASH1801COP Sound Blanket X X X X KSASH0601COP Sound Blanket X X KSALA0401...

Page 6: ...intains condensing temperature at 100_F 10_F 37 8_C 5 5_C Usage Guideline A Low Ambient Controller must be used when cooling operation is used at outdoor temperatures below 55_F 12 8_C Suggested for a...

Page 7: ...ical Code RLA Rated Load Amps compressor NOTE Control circuit is 24 V on all units and requires external power source Copper wire must be used from service disconnect to unit All motors compressors co...

Page 8: ...7 16 6 1 2 200 223 A X O X X 37 3 16 44 9 16 17 1 16 18 7 16 30 1 2 19 5 8 29 3 16 34 1 16 13 11 16 8 1 8 15 7 8 3 4 3 7 16 6 1 2 218 240 A B X O X X 43 3 16 44 9 16 17 1 16 18 7 16 30 1 2 19 5 8 35...

Page 9: ...7 206 4 403 2 19 0 87 3 165 1 90 9 101 4 PA13AZ36 A X O X X 944 6 1131 9 433 4 468 3 774 7 498 5 741 4 865 2 347 7 206 4 403 2 19 0 87 3 165 1 99 0 109 0 PA13AZ48 A B X O X X 1097 0 1131 9 433 4 468...

Page 10: ...0 3466416 PA13NAZ24 B CNPH 2417A PG9MTAV36050 A 23 400 11 5 14 0 3466417 PA13NAZ24 B CNPH 2417A PG9MTAV36075 A 23 400 11 5 14 0 3466418 PA13NAZ24 B CNPH 2417A PG9MTAV60100 A 23 400 11 5 14 0 3466419 P...

Page 11: ...AZ30 A CNPH 3017A PG9MXA036080 28 800 11 5 14 0 3095439 PA13NAZ30 A CNPH 3017A PG9MXA048080 28 800 11 5 14 0 3092111 PA13NAZ30 A CNPH 3017A TDR 28 800 11 0 13 0 3092119 PA13NAZ30 A CNPH 3617A PG8 EA04...

Page 12: ...13 5 3092175 PA13NAZ36 A CNPH 3617A PG9MTAV36075 A 33 200 11 5 14 0 3092176 PA13NAZ36 A CNPH 3617A PG9MTAV60100 A 33 400 11 5 14 0 3092177 PA13NAZ36 A CNPH 3617A PG9MTAV60125 A 33 400 11 5 14 0 30954...

Page 13: ...PA13PAZ36 A CAP 3619A PG9MTAV36075 A 33 400 11 5 14 0 3092223 PA13PAZ36 A CAP 3619A TDR 33 400 11 0 13 0 3092216 PA13PAZ36 A CAP 3621A PG8 EA048090 33 400 11 5 14 0 3092217 PA13PAZ36 A CAP 3621A PG8 E...

Page 14: ...36060 34 000 12 0 14 5 3095738 PA13PAZ36 A CSPH 4212A PG9MXA036080 34 000 12 0 14 5 3095739 PA13PAZ36 A CSPH 4212A PG9MXA048080 34 000 12 0 14 5 3095740 PA13PAZ36 A CSPH 4212A PG9MXA060100 34 000 11 5...

Page 15: ...2321 PA13EAZ36 A CSPH 3612A PG9MTAV36075 A 33 400 11 5 14 0 3092322 PA13EAZ36 A CSPH 3612A PG9MTAV60100 A 33 400 11 5 14 0 3092323 PA13EAZ36 A CSPH 3612A PG9MTAV60125 A 33 400 11 5 14 0 3095670 PA13EA...

Page 16: ...A PG8 EA060135 47 000 12 0 14 5 3466526 PA13NAZ48 B CNPH 6124A PG9MTAV60100 A 47 000 11 5 14 0 3466527 PA13NAZ48 B CNPH 6124A PG9MTAV60125 A 47 000 11 5 14 0 3466523 PA13NAZ48 B CNPH 6124A PG9MXA04808...

Page 17: ...0 11 5 14 0 3466605 PA13PAZ48 B CNPH 4821A PG9MTAV60100 A 46 500 11 5 14 0 3466606 PA13PAZ48 B CNPH 4821A PG9MTAV60125 A 46 500 11 5 14 0 3466602 PA13PAZ48 B CNPH 4821A PG9MXA048080 46 500 11 5 14 0 3...

Page 18: ...66672 PA13EAZ48 B CAP 4823A TDR 47 000 11 0 13 0 3466661 PA13EAZ48 B CAP 4824A PG8 EA060135 46 500 11 5 14 0 3466663 PA13EAZ48 B CAP 4824A PG9MTAV60125 A 46 500 11 5 14 0 3466662 PA13EAZ48 B CAP 4824A...

Page 19: ...14 0 3466745 PA13EAZ48 B CSPH 6012A PG9MTAV60100 A 47 000 11 5 14 0 3466746 PA13EAZ48 B CSPH 6012A PG9MTAV60125 A 47 000 12 0 14 5 3466742 PA13EAZ48 B CSPH 6012A PG9MXA048080 47 000 12 0 14 5 3466743...

Page 20: ...3 PA13PAZ60 B CNPV 6124A TDR 56 000 11 0 13 0 3466821 PA13PAZ60 B CSPH 6012A PG8 EA048090 56 000 11 0 13 2 3466822 PA13PAZ60 B CSPH 6012A PG8 EA060110 56 000 11 0 13 5 3466823 PA13PAZ60 B CSPH 6012A P...

Page 21: ...Seasonal Energy Efficiency Ratio TDR Time Delay Relay In most cases only 1 method should be used to achieve TDR function Using more than 1 method in a system may cause degradation in performance Use...

Page 22: ...6 00 12 11 1 74 14 93 11 70 1 96 13 78 11 25 2 20 72 22 2 20 74 10 71 1 19 19 68 10 32 1 35 18 59 9 93 1 53 17 49 9 54 1 73 16 32 9 13 1 95 15 05 8 69 2 18 675 57 13 9 17 71 17 71 1 24 16 96 16 96 1 4...

Page 23: ...Y POWER FURNACE MODEL CNPV 2414A 1 00 1 00 CAP 2414A 1 00 1 00 CAP 2417A 1 00 1 00 CAP 3014A 1 01 1 01 CAP 3017A 1 01 1 01 CNPF 2418A 1 00 1 00 CNPH 2417A 1 00 1 00 CNPH 3017A 1 01 1 01 CNPV 2417A 1 0...

Page 24: ...1 00 CNPV 3617A 1 01 1 01 CNPV 3621A 1 01 1 01 CSPH 3012A 1 00 1 00 CSPH 3612A 0 99 0 99 FF1ENP030 0 99 0 99 FF1ENP036 1 01 1 01 PF4MNA030 0 99 0 99 PF4MNA031 1 00 0 92 PF4MNA036 1 01 1 01 PF4MNA037...

Page 25: ...4217A 1 00 0 92 PG9MXA036080 CSPH 3612A 0 98 0 94 PG9MXA036080 CSPH 4212A 1 00 0 92 PG9MXA036080 CAP 3614A 0 98 0 98 PG8 EA024045 CNPH 3617A 0 98 0 98 PG8 EA024045 CNPH 4221A 0 99 0 95 PG8 EA024045 C...

Page 26: ...8 EA048070 CSPH 6012A 1 00 1 00 PG8 EA048070 CAP 4821A 0 99 0 95 PG8 EA048090 CAP 4823A 0 99 0 95 PG8 EA048090 CAP 6021A 1 00 0 92 PG8 EA048090 CNPH 4821A 0 99 0 95 PG8 EA048090 CNPH 6024A 1 00 0 92 P...

Page 27: ...0 CNPH 6124A 1 00 1 00 CNPV 6124A 0 98 0 98 CSPH 6012A 1 00 1 00 PF4MNA060 1 00 1 05 PF4MNA061 1 01 1 01 CAP 6021A 0 98 0 98 PG8 EA048090 CNPH 6024A 0 98 0 98 PG8 EA048090 CNPH 6124A 0 98 0 98 PG8 EA0...

Page 28: ...phase type with class B insulation and permanently lubricated bearings Shafts will be corrosion resistant Fan blades will be statically and dynamically balanced Condenser fan openings will be equippe...

Page 29: ...3 4 m and or 35 ft 10 7 m vertical differential consult Residential Piping and Longline Guideline and Service Manual available from equipment distributor 6 If any refrigerant tubing is buried provide...

Page 30: ...rris St S Indianapolis IN 46231 Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations Catalog No SS PA13NAZ 03 Replaces SS PA13NAZ 02...