Payne PA13NAZ Product Data Download Page 6

6

ACCESSORY USAGE GUIDELINE

ACCESSORY

REQUIRED FOR LOW---AMBIENT

COOLING APPLICATIONS

(Below 55

°

F/12.8

_

C)

REQUIRED FOR

LONG LINE

APPLICATIONS*

(Over 80 ft. / 24.4 m)

REQUIRED FOR

SEA COAST APPLICATIONS

(Within 2 miles / 3.2 km)

Compressor Start Assist Capacitor and Relay

Yes

Yes

No

Crankcase Heater

Yes

Yes

No

Evaporator Freeze Thermostat

Yes

No

No

Hard Shutoff TXV

Yes

Yes

Yes

Liquid Line Solenoid Valve

No

See Longline

Application Guideline

No

Low---ambient Control

Yes

No

No

Winter Start Control

Yes

No

No

* For tubing line sets between 80 and 200 ft. (24.38 and 60.96 m) and/or 35 ft. (10.7 m) vertical differential, refer to Residential Piping and Longline Guideline.

Accessory Description and Usage (Listed Alphabetically)

1. Crankcase Heater

An electric resistance heater which mounts to the base of the

compressor to keep the lubricant warm during off cycles.
Improves compressor lubrication on restart and minimizes the

chance of liquid slugging.

Usage Guideline:

Required in low ambient cooling applications.
Required in long line applications.
Suggested in all commercial applications.

2. Evaporator Freeze Thermostat

An SPST temperature--actuated switch that stops unit operation
when evaporator reaches freeze--up conditions.

Usage Guideline:

Required when low ambient kit has been added.

3. Low--Ambient Control

A fan--speed control device activated by a temperature sensor,
designed to control condenser fan motor speed in response to the

saturated, condensing temperature during operation in cooling
mode only. For outdoor temperatures down to --20

_

F (--28.9

_

C),

it maintains condensing temperature at 100

_

F

±

10

_

F (37.8

_

C

±

5.5

_

C).

Usage Guideline:

A Low Ambient Controller must be used when
cooling operation is used at outdoor temperatures

below 55

_

F (12.8

_

C).

Suggested for all commercial applications.

4. Outdoor Air Temperature Sensor

Designed for use with Payne Thermostats listed in this
publication. This device enables the thermostat to display the

outdoor temperature. This device also
is required to enable special thermostat features such as auxiliary

heat lock out.

Usage Guideline:

Suggested for all Payne thermostats listed in this

publication.

5. Thermostatic Expansion Valve (TXV)

A modulating flow--control valve which meters refrigerant liquid

flow rate into the evaporator in response to the superheat of the
refrigerant gas leaving the evaporator.
Kit includes valve, adapter tubes, and external equalizer tube.

Hard shut off types are available.

NOTE

: When using a hard shut off TXV with single phase

reciprocating compressors, a Compressor Start Assist Capacitor
and Relay is required.

Usage Guideline:

Accessory required to meet ARI rating and system
reliability, where indoor not equipped.
Hard shut off TXV or LLS required in air conditioner

long line applications.
Required for use on all zoning systems.

6. Time--Delay Relay

An SPST delay relay which briefly continues operation of indoor

blower motor to provide additional cooling after the compressor

cycles off.

NOTE

: Most indoor unit controls include this feature. For those

that do not, use the guideline below.

Usage Guideline:

Accessory required to meet ARI rating, where indoor

not equipped.

7. Winter Start Control

This control is designed to alleviate nuisance opening of the

low--pressure switch by bypassing it for the first 3 minutes of
operation.

PA

13N

AZ

Summary of Contents for PA13NAZ

Page 1: ...evels as low as 70 dBA Design Features S Small footprint same as old model and stackable S All steel cabinet construction S Baked on powder paint S Mesh coil guard Reliability Quality and Toughness S...

Page 2: ...er in mm 18 457 18 457 24 610 24 610 24 610 24 610 No Blades 3 3 3 3 3 3 Motor hp w 1 8 93 1 8 93 1 4 187 1 4 187 1 4 187 1 4 187 OUTDOOR COIL Face Area sq ft 5 8 7 3 12 1 12 1 14 1 14 1 No Rows 2 2 2...

Page 3: ...50 250 250 250 250 250 230 160 060 AC with R 410A 3 8 3 8 250 250 250 225 190 150 110 Maximum actual length not to exceed 200 ft 61 m Total equivalent length accounts for losses due to elbows or fitti...

Page 4: ...Level Outdoor Below Indoor Outdoor Above Indoor 1 4 No accessories needed within allowed lengths No accessories needed within allowed lengths 175 53 3 5 16 120 36 6 50 15 2 vertical or 120 36 6 total...

Page 5: ...inter Start Kit for low ambient X X X X X X KSACY0101AAA Cycle Protector X X X X X X KSAHS1501AAA Hard Start Kit X X X X X X KSASH1801COP Sound Blanket X X X X KSASH0601COP Sound Blanket X X KSALA0401...

Page 6: ...intains condensing temperature at 100_F 10_F 37 8_C 5 5_C Usage Guideline A Low Ambient Controller must be used when cooling operation is used at outdoor temperatures below 55_F 12 8_C Suggested for a...

Page 7: ...ical Code RLA Rated Load Amps compressor NOTE Control circuit is 24 V on all units and requires external power source Copper wire must be used from service disconnect to unit All motors compressors co...

Page 8: ...7 16 6 1 2 200 223 A X O X X 37 3 16 44 9 16 17 1 16 18 7 16 30 1 2 19 5 8 29 3 16 34 1 16 13 11 16 8 1 8 15 7 8 3 4 3 7 16 6 1 2 218 240 A B X O X X 43 3 16 44 9 16 17 1 16 18 7 16 30 1 2 19 5 8 35...

Page 9: ...7 206 4 403 2 19 0 87 3 165 1 90 9 101 4 PA13AZ36 A X O X X 944 6 1131 9 433 4 468 3 774 7 498 5 741 4 865 2 347 7 206 4 403 2 19 0 87 3 165 1 99 0 109 0 PA13AZ48 A B X O X X 1097 0 1131 9 433 4 468...

Page 10: ...0 3466416 PA13NAZ24 B CNPH 2417A PG9MTAV36050 A 23 400 11 5 14 0 3466417 PA13NAZ24 B CNPH 2417A PG9MTAV36075 A 23 400 11 5 14 0 3466418 PA13NAZ24 B CNPH 2417A PG9MTAV60100 A 23 400 11 5 14 0 3466419 P...

Page 11: ...AZ30 A CNPH 3017A PG9MXA036080 28 800 11 5 14 0 3095439 PA13NAZ30 A CNPH 3017A PG9MXA048080 28 800 11 5 14 0 3092111 PA13NAZ30 A CNPH 3017A TDR 28 800 11 0 13 0 3092119 PA13NAZ30 A CNPH 3617A PG8 EA04...

Page 12: ...13 5 3092175 PA13NAZ36 A CNPH 3617A PG9MTAV36075 A 33 200 11 5 14 0 3092176 PA13NAZ36 A CNPH 3617A PG9MTAV60100 A 33 400 11 5 14 0 3092177 PA13NAZ36 A CNPH 3617A PG9MTAV60125 A 33 400 11 5 14 0 30954...

Page 13: ...PA13PAZ36 A CAP 3619A PG9MTAV36075 A 33 400 11 5 14 0 3092223 PA13PAZ36 A CAP 3619A TDR 33 400 11 0 13 0 3092216 PA13PAZ36 A CAP 3621A PG8 EA048090 33 400 11 5 14 0 3092217 PA13PAZ36 A CAP 3621A PG8 E...

Page 14: ...36060 34 000 12 0 14 5 3095738 PA13PAZ36 A CSPH 4212A PG9MXA036080 34 000 12 0 14 5 3095739 PA13PAZ36 A CSPH 4212A PG9MXA048080 34 000 12 0 14 5 3095740 PA13PAZ36 A CSPH 4212A PG9MXA060100 34 000 11 5...

Page 15: ...2321 PA13EAZ36 A CSPH 3612A PG9MTAV36075 A 33 400 11 5 14 0 3092322 PA13EAZ36 A CSPH 3612A PG9MTAV60100 A 33 400 11 5 14 0 3092323 PA13EAZ36 A CSPH 3612A PG9MTAV60125 A 33 400 11 5 14 0 3095670 PA13EA...

Page 16: ...A PG8 EA060135 47 000 12 0 14 5 3466526 PA13NAZ48 B CNPH 6124A PG9MTAV60100 A 47 000 11 5 14 0 3466527 PA13NAZ48 B CNPH 6124A PG9MTAV60125 A 47 000 11 5 14 0 3466523 PA13NAZ48 B CNPH 6124A PG9MXA04808...

Page 17: ...0 11 5 14 0 3466605 PA13PAZ48 B CNPH 4821A PG9MTAV60100 A 46 500 11 5 14 0 3466606 PA13PAZ48 B CNPH 4821A PG9MTAV60125 A 46 500 11 5 14 0 3466602 PA13PAZ48 B CNPH 4821A PG9MXA048080 46 500 11 5 14 0 3...

Page 18: ...66672 PA13EAZ48 B CAP 4823A TDR 47 000 11 0 13 0 3466661 PA13EAZ48 B CAP 4824A PG8 EA060135 46 500 11 5 14 0 3466663 PA13EAZ48 B CAP 4824A PG9MTAV60125 A 46 500 11 5 14 0 3466662 PA13EAZ48 B CAP 4824A...

Page 19: ...14 0 3466745 PA13EAZ48 B CSPH 6012A PG9MTAV60100 A 47 000 11 5 14 0 3466746 PA13EAZ48 B CSPH 6012A PG9MTAV60125 A 47 000 12 0 14 5 3466742 PA13EAZ48 B CSPH 6012A PG9MXA048080 47 000 12 0 14 5 3466743...

Page 20: ...3 PA13PAZ60 B CNPV 6124A TDR 56 000 11 0 13 0 3466821 PA13PAZ60 B CSPH 6012A PG8 EA048090 56 000 11 0 13 2 3466822 PA13PAZ60 B CSPH 6012A PG8 EA060110 56 000 11 0 13 5 3466823 PA13PAZ60 B CSPH 6012A P...

Page 21: ...Seasonal Energy Efficiency Ratio TDR Time Delay Relay In most cases only 1 method should be used to achieve TDR function Using more than 1 method in a system may cause degradation in performance Use...

Page 22: ...6 00 12 11 1 74 14 93 11 70 1 96 13 78 11 25 2 20 72 22 2 20 74 10 71 1 19 19 68 10 32 1 35 18 59 9 93 1 53 17 49 9 54 1 73 16 32 9 13 1 95 15 05 8 69 2 18 675 57 13 9 17 71 17 71 1 24 16 96 16 96 1 4...

Page 23: ...Y POWER FURNACE MODEL CNPV 2414A 1 00 1 00 CAP 2414A 1 00 1 00 CAP 2417A 1 00 1 00 CAP 3014A 1 01 1 01 CAP 3017A 1 01 1 01 CNPF 2418A 1 00 1 00 CNPH 2417A 1 00 1 00 CNPH 3017A 1 01 1 01 CNPV 2417A 1 0...

Page 24: ...1 00 CNPV 3617A 1 01 1 01 CNPV 3621A 1 01 1 01 CSPH 3012A 1 00 1 00 CSPH 3612A 0 99 0 99 FF1ENP030 0 99 0 99 FF1ENP036 1 01 1 01 PF4MNA030 0 99 0 99 PF4MNA031 1 00 0 92 PF4MNA036 1 01 1 01 PF4MNA037...

Page 25: ...4217A 1 00 0 92 PG9MXA036080 CSPH 3612A 0 98 0 94 PG9MXA036080 CSPH 4212A 1 00 0 92 PG9MXA036080 CAP 3614A 0 98 0 98 PG8 EA024045 CNPH 3617A 0 98 0 98 PG8 EA024045 CNPH 4221A 0 99 0 95 PG8 EA024045 C...

Page 26: ...8 EA048070 CSPH 6012A 1 00 1 00 PG8 EA048070 CAP 4821A 0 99 0 95 PG8 EA048090 CAP 4823A 0 99 0 95 PG8 EA048090 CAP 6021A 1 00 0 92 PG8 EA048090 CNPH 4821A 0 99 0 95 PG8 EA048090 CNPH 6024A 1 00 0 92 P...

Page 27: ...0 CNPH 6124A 1 00 1 00 CNPV 6124A 0 98 0 98 CSPH 6012A 1 00 1 00 PF4MNA060 1 00 1 05 PF4MNA061 1 01 1 01 CAP 6021A 0 98 0 98 PG8 EA048090 CNPH 6024A 0 98 0 98 PG8 EA048090 CNPH 6124A 0 98 0 98 PG8 EA0...

Page 28: ...phase type with class B insulation and permanently lubricated bearings Shafts will be corrosion resistant Fan blades will be statically and dynamically balanced Condenser fan openings will be equippe...

Page 29: ...3 4 m and or 35 ft 10 7 m vertical differential consult Residential Piping and Longline Guideline and Service Manual available from equipment distributor 6 If any refrigerant tubing is buried provide...

Page 30: ...rris St S Indianapolis IN 46231 Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations Catalog No SS PA13NAZ 03 Replaces SS PA13NAZ 02...

Reviews: