Technical Help

1 - Readers/Keypads not working.

• 

Software settings - Confirm that the settings of the reader or 
keypad are correct. 

• 

Connections - Check the wiring and integrity of the connectors. If 
possible, test this reader on the other port.

• 

Extended cable - Belden 9540/5306FE or General Cable C0745A 
/E2038S should be used up to a maximum of 328 feet. Twisted 
pair alarm cable should not be used. To confirm that an extended 
reader cable is not at fault, wire the reader directly to the port.

• 

Supply voltage - Confirm that the voltage is within specification. 
(see table) 

• 

User token - Confirm that the user token used for testing is OK by 
presenting it to a known working reader.

• 

Interference - Confirm whether the reader works when tested ‘in 
hand’ and not mounted on the wall. 

• 

PROXIMITY readers should not be mounted back to back or close 
to other RF devices.

2 - Readers / Keypads - Extending cable.

• 

Only Belden 9540/5306FE or General Cable C0745A /E2038S can 
be used for cable extensions. The maximum run is 328 feet.

3 - Net2 - Using a door reader as a desktop reader. 

• 

It is possible to configure a door reader to operate as a desktop 
reader: 

1 - Select the doors menu in the left hand Net2 pane.
2 - Click on the door you wish to change the reader to act as a desktop 
reader.
3 - Under the relevant reader tab, change the reader operating mode to 
‘Desktop Reader’.
4 - The PC displays ‘Would you like to accept desktop reader events from 
this reader at the PC?’ ; click ‘Yes’
Now when you present a blank or existing token to that reader it will 
allow you to add this new token or edit the existing one. 

NOTE: Remember to return the operating mode to the original setting 
once the cards have been read or users will not be able to gain access 
through the reader. 

 

KP Reader - Ensure that Keypad type is set to ‘None’, 

otherwise the Desktop reader option will not be available.

Summary of Contents for ins-20801

Page 1: ...ins 20801 Paxton Proximity metal readers ...

Page 2: ...1 1 2 1 Mounting ...

Page 3: ... plate to the surface with four screws as per fitting diagram on page 1 Suitable screws and fixings are provided for fitting the plate to a wall Mount the reader on its backplate and secure with the security screws using the Allen key supplied Ensure the data cable has free access at the rear Wiring ...

Page 4: ...ck or close to other RF devices 2 Readers Keypads Extending cable Only Belden 9540 5306FE or General Cable C0745A E2038S can be used for cable extensions The maximum run is 328 feet 3 Net2 Using a door reader as a desktop reader It is possible to configure a door reader to operate as a desktop reader 1 Select the doors menu in the left hand Net2 pane 2 Click on the door you wish to change the read...

Page 5: ...rd on a known working reader If there is still no response replace the card Green LED flashing when a card is presented check relay 1 LED to check for activity and also the lock wiring Red LED is flashing when a card is presented check the validity of the user at the PC Check user s access level and ensure they should have access by clicking on Current Validity Check the Expires end date and confi...

Page 6: ...upport paxton benelux com 49 0 251 2080 6900 paxton gmbh support verkauf paxton gmbh de 33 0 1 57 32 93 56 support paxtonaccess fr paxton support 27 0 21 4276691 support paxtonaccess co za paxton support 8000 3570 3783 paxton support support paxtonaccess ae 52 55 5351 3667 paxton soporte soporte paxton access com 57 1508 8198 paxton soporte soporte paxton access com 44 0 1273 811011 paxton support...

Page 7: ...e of any add on expansion memory or other module manufactured or supplied by the manufacturer s representative will invalidate the CAN ULC S319 certification Wiring methods shall be in accordance with the National Electrical Code ANSI NFPA70 local codes and the authorities having jurisdiction Pour que l installation répond aux normes UL les conditions suivantes sont applicables Les fonctions serve...

Page 8: ... Paxton Ltd 1 0 4 Made in the UK 19 02 2018 ...

Reviews: