background image

Part No. 1101-7119-01     © 2014 PAX Water Technologies, Inc.

PAX Water Mixer (PWM100)

Installation/Operation Manual

8

1.  Bring power (120 VAC, 60 Hz, GFCI-protected, 20 amp circuit) onsite to tank.
2.  Install a safety disconnect switch and connect power.

NOTE: 

Make sure that the safety disconnect switch is in the off position; follow proper lockout/

tagout procedures.

3.  Penetrate the side of the tank hatch (1.025” or 26 mm hole).
4.  Run conduit (3/4” or 20mm) from the safety disconnect switch to a junction box at the tank 

hatch, and then from the junction box to the penetration of the hatch lip. Pull wire from safety 
disconnect switch to the junction box (copper wires min. 12 AWG (3.31 mm

2

), type THHN, 

rated 90 °C).

5.  Bring the PAX Water Mixer to the roof of the tank.

NOTE: 

Keep PAX Water Mixer inside its packaging for protection. The holes on the sides of the 

packaging can be used to secure a rope.

6.  Remove mixer from its packaging and tie off the power cord (halfway between mixer and end 

of cord) to ensure that mixer cannot fall off the top of the tank. Then thread the end of the 
power cord through a strain relief, the tank penetration and the conduit that connects to the 
junction box.

7.  Hold the mixer over the open hatch by gripping its power cord and slowly lower into the water.

a)  Continue to lower the mixer, a few feet at a time, until it makes contact with the floor of  

the tank. 

b)  After the mixer makes contact with the floor of the tank, allow 3-4 feet (1-1.5 m) of slack in 

the cable. 

c)  If there is excess power cord, coil it up and secure it to the ladder above the water.

NOTE: 

The PAX Water Mixer is designed to come to rest on the floor of the tank and point upwards. 

On a sloped floor, the mixer will come to rest at a low point on the tank floor.

7. PAX Water Mixer Start-Up and Shut-Down Procedure 

NOTE: 

After the initial installation or any tank maintenance, always perform the PAX electrical 

checks before placing the PAX Water Mixer in service.

Checks include:

•  Measuring Motor Resistance and Ground
•  Measuring AC Current 
•  Measuring AC Voltage

1. To turn the PAX Water Mixer ON, energize the GFCI breaker and turn ON the safety disconnect 

switch.

2. To turn the PAX Water Mixer OFF, turn off the safety disconnect switch and de-energize the 

GFCI breaker.

Summary of Contents for PWM100

Page 1: ...PAX Water Mixer PWM100 Installation Operation Manual ...

Page 2: ......

Page 3: ...pril 2014 Printed in USA PAX Water Technologies Inc 860 Harbour Way South Suite C Richmond CA 94804 866 729 6493 Warranty The material contained in this Installation Operation Manual is provided AS IS and WITH ALL FAULTS and the user understands and agrees that all express and implied warranties including those warranties implied by the Uniform Commercial Code as enacted in the state of California...

Page 4: ...pment Operation Safety Warnings 2 Overview 4 PAX Water Mixer Description Quality Control Statement 3 PAX Water Mixer Specifications 5 4 Installation Tools and Test Equipment 5 5 Facilities Requirements 6 6 Installation Procedure 7 Figure 1 PWM100 7 7 PAX Water Mixer Start Up and Shut Down Procedure 8 8 PAX Water Mixer Electrical Checks 9 9 Recommended Maintenance Checks 10 10 Replacement Parts Lis...

Page 5: ...his is the safety alert symbol and is used to alert potential personal injury hazards Please obey all safety messages that follow this symbol to avoid personal injury or death WARNING indicates an imminently hazardous situation which if not avoided can result in death serious injury or equipment damage A confined space entry plan and operational procedures must be used for every reservoir entry Re...

Page 6: ...Technologies is dedicated to supplying high quality products that meet or exceed the needs of water customers PAX Water Technologies strict quality control and continuous improvement programs ensure the best value to customers PAX Water Technologies manages its business to the highest environmental and ethical standards NSF International provides testing and certification of water systems and comp...

Page 7: ...ied Power Switch 3R fused safety disconnect switch Motor Type 115 VAC 60 Hz water filled water lubricated single phase motor NSF 61 RPM 3450 Nominal Power Draw 1 15 kVA 670 watts Footprint Diameter 10 25 4 cm Height 30 76 2 cm Weight 40 lbs 18 1 kg Material Motor Housing 316 stainless steel Material Motor Seals Chlorine chloramine resistant NBR rubber Material Foot Chlorine chloramine resistant EP...

Page 8: ...ected circuit Safety Disconnect Switch The safety disconnect switch must be a 3R certified type properly marked and installed in accordance with all electrical codes state local and OSHA requirments Junction Box 3R located in accordance with local codes Electrical Conduit The PAX Water Mixer cable is a 3 wire cable set 0 5 12 7 mm in diameter Use electrical conduit 3 4 or 20 mm from the tank penet...

Page 9: ...ter Mixer PWM100 Installation Operation Manual 7 6 Installation Procedure WARNING The PAX Water Mixer should always run underwater NEVER RUN DRY NOTE All electrical and conduit connections should be secure and routed in accordance with electrical code FIGURE 1 ...

Page 10: ...top of the tank Then thread the end of the power cord through a strain relief the tank penetration and the conduit that connects to the junction box 7 Hold the mixer over the open hatch by gripping its power cord and slowly lower into the water a Continue to lower the mixer a few feet at a time until it makes contact with the floor of the tank b After the mixer makes contact with the floor of the ...

Page 11: ... by a licensed electrical contractor Electrical Test Equipment The following equipment is to be used to perform the electrical check Multimeter Current Clamp NOTE Perform the measurements at a location in the circuit where you are able to place a clamp on amperage meter and where you can take a voltage reading NOTE Reference Table 1 for the next steps Table 1 Quick Reference Chart WHAT TO MEASURE ...

Page 12: ...easuring AC Input Current 1 Power up the PAX Water Mixer 2 Set the multimeter to AC amp 3 Clamp the current meter to each of the input power wires Verify that the current is between 9 5 and 11 5 AC amps 9 Recommended Maintenance Checks NOTE There is no preventative maintenance required for the PAX Water Mixer 1 Perform the PAX Electrical Checks Section 8 annually to ensure that the PAX Water Mixer...

Page 13: ......

Page 14: ...PAX Water Technologies Inc 860 Harbour Way South Suite C Richmond CA 94804 For sales and service contact Phone 866 729 6493 Email service paxwater com www paxwater com ...