background image

Page 4 of 12 

 

Commissioning 

Filling, Flushing and Commissioning of the Solar Station

 

1.

 

Connect the pressure hose to the fill valve (2) below the pressure gauge (1) and open the valve. 

2.

 

Connect the flush hose to the flush valve (4) on the flow meter (on the ball valve below the 

pump) and open the valve. 

3.

 

The slot of the screw at the flow meter (3) has to be in a horizontal position. This way, the 

integrated ball valve is closed (see user’s guide for the flow meter). Open both check valves 

(over the pump and inside the supply valve); in order to do this, bring the ball valve into a 45° 

position (half open, half closed)  using 14 mm or 9/16 wrench. 

4.

 

Fill up solar fluid into the clean container and charge the solar loop using external service pump. 

5.

 

Flush the solar circuit for at least 15 min. In order to remove all of the air from the system, it is 
necessary time to time to open the balancing screw on the flow meter. 

6.

 

Never flush or make a hydrostatic pressure test of the whole solar installation only 

with water. It is impossible to completely empty the installation; there is a danger of 

icing damages! 

7.

 

Close the flush valve (4) while the pump is still working and increase the pressure of the system 

to approx. 5 bar/ 72 PSI. You can read the pressure from the pressure gauge (1). 

8.

 

Close the fill valve (2) and switch off the service pump. Open completely the balancing valve at 

the flow meter (slot vertical). 

9.

 

Bleed the installation from above the collectors until the heat transfer fluid comes out free from 

bubbles. If necessary, increase the pressure to approx. 5 bar/72 PSI and check for the leaks on 

all the joints. If there is a considerable pressure drop on the pressure gauge (1), you can assume 
that there is a leak in the system. 

10.

 

Adjust the operating pressure in accordance with the installation requirements (approx. 1,8 

bar/28 PSI for a static height between the collectors and the pressure gauge of 5 m/16 ft; and  

to 2,3 bar/33 PSI for a static height 10 m/32 ft). 

11.

 

Set the circulation pump on the highest speed level (see user’s guide of the pump and the 

controller) and keep it circulating for at least 15 min. Adjust the circulation pump to the desired 

RPM level. 

12.

 

Adjust the flow rate on the flow meter in accordance to collector manufacturer’s instructions. 

13.

 

Disconnect the hoses of the fill pump and cap the flush and fill valves with supplied cups. 

14.

 

Double check the possible leaks of the installation. Open both shut-off ball valves completely. 

15.

 

Fix the front shell of the solar station. Insert the red handle with thermometer in the supply line 
(on the left side) and the blue handle with thermometer in the return line (on the right side).

 

Summary of Contents for FlowCon FA

Page 1: ...In North America for technical Assistance Contact Solarnetix Inc 416 699 6746 www solarnetix com info solarnetix com Page 1 of 12 User Guide For FlowCon FA Solar Stations ...

Page 2: ...alve 6 bar 87 PSI Pressure gauge 0 6 bar 0 87 PSI Connection for expansion tank NPT female Shut off Indication Devices Ball valve Full port Dial thermometer 0 160 C 32 320 F Flow check Valves Pressure Drop 2 x 200 mm 7 9 W C 400 mm 15 8 W C type PPS Temperature max 180 C 356 F Flow Meter Range of indication adjustment 1 13 l min connections BSP female 1 nut flat sealing Additional connections 1 x ...

Page 3: ...e the solar station assembled with the back insulation shell 5 Mark the drill holes distance 70 mm 2 and drill them with an 8 mm 5 16 bit 6 Insert the attached plugs S 8 into the holes 7 Attach the complete solar station to the wall by using the enclosed screws 8 Connect the piping between the solar station storage and collectors All connections were tightened in the factory so that in general it ...

Page 4: ...can read the pressure from the pressure gauge 1 8 Close the fill valve 2 and switch off the service pump Open completely the balancing valve at the flow meter slot vertical 9 Bleed the installation from above the collectors until the heat transfer fluid comes out free from bubbles If necessary increase the pressure to approx 5 bar 72 PSI and check for the leaks on all the joints If there is a cons...

Page 5: ...lves see the following instructions 2 Open the venting valves at the highest point above the collectors 3 Open the valve at the lowest point of the installation if possible near the connection of the storage not included in the delivery or at the flush valve outlet valve below the pump 1 2 3 4 ...

Page 6: ...ctly behind the collectors For an assembly in the attic it has to be ensured that the air vents can not overheat e g by means of a steam scoop The expansion tank has to be checked regularly in accordance with local Plumbing Code Solar installations have to be grounded for reasons of lightning protection Only skilled and trained electrical personnel are authorized to carry out wiring operations All...

Page 7: ...e cross section of the valve inlet You must also ensure that the blow line is laid at a slope the outlet of the pipe work must be open and visible and routed such that the blowing process does not endanger persons Placing a canister under the blow line has proven itself as a practical solution If the safety valve is actuated the liquid is collected and can be pumped back into the system if the pre...

Page 8: ...to be followed The values of the attached table determined by the Institute for solar energy research in Hameln Germany can be used fort he calibration of the flow meter The calibration is necessary as 1 the viscosity changes against the temperature 2 the density changes against the temperature 3 the precise volume flow is needed for the calculation of the energy transfer The floater of the flow m...

Page 9: ...s Please note After the air purge it is important to double check the pressure and if necessary to increase it to normal operation pressure Optional Compression fittings Assembly instructions 1 Push the union nut 2 onto the copper tube 1 then push the brass O ring 3 onto the copper tube 1 In order to guarantee a secure transmission of force and seal the tube has to stick out out at least 1 8 of th...

Page 10: ...mometer handle red 12 Dial thermometer Ø40 mm 1 57in blue 0 160 C 32 320 F 13 Dial thermometer Ø40 mm 1 57in red 0 160 C 32 320 F 14 gasket 30 0 x 21 0 x 2 0 For flat union connections 1 15 Flow meter DN 20 1 x female 16 Air Stop 17 Extension 3 8 x 40 mm 1 9 16 18 Manual air vent 3 8 19 plug S 8 20 Wood screws S 6 60 mm 2 36in Per piece zinc coated 21 Mounting plate for solar station DN 20 A 125 m...

Page 11: ... Page 11 of 12 Attention Please always mention the item number of the solar station while ordering spare parts ...

Page 12: ...as not installed in accordance with WILO s published installation and operation instructions Please visit www WILO NA com for a copy of our installation and operation instructions All claims under this warranty must be returned to an authorized WILO distributor for processing along with proof of purchase installation date and replacement date A WILO authorized distributor will then contact WILO fo...

Reviews: