OPERATING INSTRUCTIONS 

Universal Thermostat 

with modulating power control

 

 

© Paul Wärmerückgewinnung GmbH • August-Horch-Straße 7 • 08141 Reinsdorf • Deutschland 

Tel: +49(0)375-303505-0 • Fax: +49(0)375-303505-55  • E-Mail: [email protected] • Internet: www.paul-lueftung.de

 

 

2.1.2 ON/OFF Control 
 

In the operation modes mentioned below, the control of the consumer load is realized by switching it 
completely on or off. 

 

2.1.2.1 Brine defroster / GHX flap control 

 

The temperature sensor is installed 

upstream

 of the components brine defroster or GHX regulating flap. 

The control of the brine defroster / GHX regulating flap depends on the configured temperature thresholds 
X1 /X2 (see appendix 1 and appendix 2): 

  

 

ON:     T 

 X2   

or 

 X1  

OFF:   T 

 X2+H 

and 

 X1-H 

 
DIP- 1 

ON   

DIP-2,-3,-4 OFF 
 
 
 
 
 
 
 
 

- Actual value of 

intake air temperature upstream of brine defroster / GHX flap

 

     H 

- Hysteresis 

X1 - 

Setpoint 

upper switching threshold

 

X2 - 

Setpoint 

lower switching threshold

 

 
2.1.2.2 2-level control for defroster heater 

 

The temperature sensor is installed 

downstream

 of the component defroster heater. The control of the 

defroster heater depends on the configured temperature threshold X2 (see appendix 1 and appendix 3): 
 
ON: T 

 X2

 

OFF: T 

 X2+H 

 
DIP-2 ON 

 

DIP-1, -3, -4 

OFF 

 
 
 
 
 
 
 
 

- Actual value of 

intake air temperature downstream of the component

 

H - 

Hysteresis 

X2 - 

Setpoint 

lower switching threshold

 

 

 
 
 
 
 
 
 
 
 
 
 

Summary of Contents for Universal Thermostat

Page 1: ...er heater Back up duct heater fffff Paul W rmer ckgewinnung GmbH August Horch Stra e 7 08141 Reinsdorf Tel 49 0 375 303505 0 Fax 49 0 375 303505 55 Deutschland Operating Instructions Operating Instruc...

Page 2: ......

Page 3: ...ature switching threshold and switching times ON OFF Control Brine defroster GHX flap control 2 level control for defroster heater 2 level control for backup duct heater Settings of operating mode ON...

Page 4: ...d by an electronic relay for electric duct heaters with modulating power control Pparallel to this a potential free changeover is available Enabling and locking of the control can be performed by an e...

Page 5: ...nd switching times After setting the operation mode using the DIP switches the temperature thresholds have to be set via the control buttons The relevant thresholds can be changed according to the mod...

Page 6: ...GHX regulating flap The control of the brine defroster GHX regulating flap depends on the configured temperature thresholds X1 X2 see appendix 1 and appendix 2 ON T X2 or T X1 OFF T X2 H and T X1 H D...

Page 7: ...value of supply air temperature H Hysteresis X1 setpoint upper switching value 2 1 2 4 Settings of operating mode ON OFF control Button Temp 1 upper temperature threshold X1 keypress 3 s current switc...

Page 8: ...contact is closed This input in combination with a backup duct heater can be used for a room thermostat and or a flow sensor 2 2 2 Status message Consumer load ON Terminal X7 Potential free output for...

Page 9: ...rent lid of the existing plastic humidor suitable housing Operating data Housing dimensions W x D x H 160 x 120 x 90 mm Electrical connection 230 Vac 10 50 Hz Fuse T 160 mA Degree of protection IP 44...

Page 10: ...n Terminal diagram Potential free output for notification consumer ON 230VAC and distribution Grounding External enabling contact contact open inhibiting contact closed releasing Consumer load Heating...

Page 11: ...With intended use of brine defroster only connect at N und L pump 230VAC and distribution Grounding Potential free output for notification consumer load ON Balance leveling Middle position neutral pus...

Page 12: ...lower threshold 3 C H Hysteresis 0 5 C Grounding 230VAC and distribution Filter time Balance leveling Middle position neutral push button days days days Keyboard Status relay e g release for defroster...

Page 13: ...1 2 4 OFF X1 Setpoint upper threshold 50 C H Hysteresis 1 C 230VAC and distribution Potential free output for notification consumer load ON Room thermostat Status relay e g release for defroster Vent...

Reviews: