background image

Restart Procedure

The restart procedure is in place to allow the

and Time Outs

units to re-establish a connection after the
framer begins seeing unframed packets. The
Test Model Timing Chart below shows the
amount of time the framer must see consecutive
unframed packets before the unit will restart and
try to establish a new line connection. The rea-
son that there are different Restart Times will
become apparent after reading the rest of the
document. The 511/511E Time Out shown refers
to the amount of time the 511/511E pattern will
be valid. At the end of this time the pattern will
automatically turn itself off and the normal data
path will be re-established. The ER led will flash
indicating to the user that the test has timed out.
The ER led will stop flashing once the 511/511E
switch is placed into the normal position.

Symbol Indicators

This symbol designates the origination or the
termination of a data path. The direction of the
arrow connected distinguish the two data paths.

This symbol designates an invalid data path. If
there is data  present it should be ignored.

21

5.3.2  Loops and Patterns

The following section describes the Test Modes used in the Model

1088. At the bottom of each Test Mode, a figure is included to show
the data path.

Local Loop

There are two different modes of operation for a
Local Loop depending on the status of the units
at the time that the Local Loop is initiated. If the
units are not in linked (NS LED on) and the
Local Loop is initiated, either by the front panel
switch or the DTE interface, the unit will enter
mode 1. If the units are linked, NS LED off, then
the unit will enter a mode 2 Local Loop. 

A Mode 1 Local Loop is shown in Figure 12.
When the Local Loop is initiated, either by the
front panel switch or the DTE interface, the loop
will be activated within the local Processor. The
data present at the local DTE interface will be
looped back to the local DTE by the Loop
Control block within the Processor. Any data
present on the line or at the far end DTE inter-
face is invalid. The remote unit will remain in the
StartUP mode, NS LED on, DSL Link LED stays
off, until the local unit is taken out of the Local
Loop mode. After the Local Loop is deselected,
the units will both be in StartUP mode and the
link will be established.

A mode 2 Local Loop is shown in Figure 13.
When the Local Loop is initiated, either by the
front panel switch or the DTE interface, two sep-
arate loop paths will be started. In the first path,
data presented to the local DTE interface will be
looped back to the local DTE within the framer.
In the second path,  data presented at the far
end DTE will be transmitted to the local DTE
and then looped back within the local DTE Loop
Control block with the Processor. After the Local
Loop is deselected, the units will be placed back
into DataMode and the normal data paths will be
re-established. 

22

                          Test Mode Timing

Item

Elapsed Time (seconds)

Start Up

50

Data Mode

4

511/511E Generator Enabled 60 (The generator will stop after 45 seconds.)

Remote End of an RDL

60

511/511E Time Out

45 (The pattern generator will automatically turn

off after 45 seconds. The ER LED will flash until

the user turns off the 511/511E switch.)

Summary of Contents for 1088

Page 1: ...MODEL 1088 K mDSL Modem with fixed G 703 G 704 Interface Part 07M1088 K B Doc 033141UB Revised 02 22 00 SALES OFFICE 301 975 1000 TECHNICAL SUPPORT 301 975 1007 http www patton com An ISO 9001 Certif...

Page 2: ...oduct These damages include but are not limited to the following lost profits lost savings and incidental or consequen tial damages arising from the use of or inability to use this product Patton Elec...

Page 3: ...mDSL Rocket offers the ability to extend G 703 G 704 service over Multi rate Symmetric Digital Subscriber Line technology Multi rate DSL offers the ability to deliver the maximum bit rate that a twis...

Page 4: ...n in the table below Switch S1 1 CO CP Use Switch S1 1 configure the CO located at the Central Office or or G 703 G 704 demarcation point or CP located at the Customer Premises mode of the 1088 K S1 1...

Page 5: ...e special violations and decodes them as zeros This method enables the network to meet minimum pulse density requirements Use HDB3 unless AMI is required in your application Alternate Mark Inversion A...

Page 6: ...n 1664 On Off Off Off Off On 1728 Off Off Off Off Off On 1792 On On On On On Off 1856 Off On On On On Off 1920 On Off On On On Off 1984 Off Off On On On Off 2048 Switch S2 7 Reset Software Defaults Sw...

Page 7: ...g S1 and S2 DIP switches in the ON position as described in Figure 3 below When the CO and CP units connect over DSL the CP will enter a pre defined default configuration Receive Recovered Clocking Du...

Page 8: ...r a 75 Ohm connection coax insert JP1 JP4 JP5 and JP6 default 2 For a 120 Ohm connection RJ45 remove JP1 and JP4 JP5 and JP6 4 2 1 Connect Twisted Pair 120 ohm to G 703 Network The Model 1088 K is equ...

Page 9: ...wire interface The signal pin relationships are shown in Figure 8 15 4 4 POWER CONNECTION Universal AC Power 100 240VAC The Model 1088 uses a 5VDC 2A universal input 100 240VAC power supply center pin...

Page 10: ...cross the DSL span is active The DSL Link LED is Off when the link is down E1 FE1 Link Active Green Solid green On indicates a valid E1 connection LOS Active Red The Loss of Sync indicates that the un...

Page 11: ...eives framed packets from the far end the DSL Link LED will be active If framed packets are not received the DSL Link LED will be inactive The restart procedure uses this information to determine if a...

Page 12: ...the front panel switch or the DTE interface the unit will enter mode 1 If the units are linked NS LED off then the unit will enter a mode 2 Local Loop A Mode 1 Local Loop is shown in Figure 12 When t...

Page 13: ...the box 23 Local Loop After the 511 511E pattern times out the ER led with 511 511E will begin flashing It will remain this way until continued the pattern generator switch is turned off Note that the...

Page 14: ...again before the completion of the termination phase the switch will be ignored until it is placed back into the normal position 25 26 Remote Digital The Remote Digital Loop with 511 511E is Loop wit...

Page 15: ...Using the V 52 BER Test Pattern Generator To use the V 52 BER tests in conjunction with the Remote Digital Loopback tests or with Local Line Loopback tests follow these instructions 1 Locate the 511 5...

Page 16: ...de and Phase Modulation Line Rates DSL line 144 272 400 528 784 1040 1552 2064 Line Interface Transformer coupled 1500 VAC isolation mDSL Physical Connection RJ 45 2 wire polarity insensitive pins 4 a...

Page 17: ...000 1 9 3 1 2064 1600 2048 5920 1 1 1 8 8000 1 5 2 5 Cross Talk 49 adjacent CAP pairs 26 AWG 0 4mm 24 AWG 0 5mm Transmission Distance Patton NetLink mDSL Model 1088 No Cross Talk 26 AWG 0 4mm 24 AWG 0...

Reviews: