After the DC power supply leads are properly connected and

power is applied, the green "12V" LED on the 1001RPSM-R48V front
panel will be illuminated and the fan will operate. There is no on/off
switch.

5.9  SERVICE PROCEDURE - REPLACING A 1001RPSM-RUI          

FRONT CARD

This section describes the procedure for replacing an already-

installed 1001RPSM-RUI AC power supply front card. A flat blade
screwdriver is required to remove and install the card.

To replace an already-installed 1001RPSM-RUI AC power supply

front card, follow the detailed instructions below:

1.

Loosen the two front-panel captive securing screws. Do not
remove the screws from the card.

2.

Using two hands, grasp the captive screws and slowly separate
the card from the rack until the front panel is approximately ONE
INCH from the edge of the rack chassis. This disconnects the
front card from the AC voltage source.

DO NOT COMPLETELY

REMOVE THE CARD FROM THE RACK CHASSIS!

3.

After a minimum of three minutes have elapsed after disconnect-
ing the AC voltage source, the front card may be safely removed
from the rack chassis.

4.

Install a new 1001RPSM-RUI front module by carefully aligning it
with the chassis guides. Gently slide the card into the chassis
along the metal rails provided. The card connectors will meet the
mid-plane bus when the card is almost all the way into the chassis.

5.

After the connectors meet, gently apply even pressure to the top
and bottom of the panel to seat the card. Do not force the card
into the chassis. This may damage the connector pins.

6.

Tighten the captive screws. The green "12V" LED should be illu-
minated and the fan should operate.

5.10  SERVICE PROCEDURE - REPLACING A 1001RPSM-R48V  

FRONT CARD

Follow the same procedure as outlined in the section "REPLAC-

ING A 1001RPSM-RUI FRONT CARD". Since the  1001RPSM-R48V
uses only non-hazardous, low DC voltage, it may be safely removed
from the rack chassis immediately after loosening the captive screws.

WARNING!  

Hazardous voltages exist in the primary cir-

cuits. Beware of internal lethal voltages due to charged capaci-
tors even after the AC input is disconnected. A minimum of 3
minutes should be allowed after AC input power is disconnect-
ed before removing or handling the front power supply module.

WARNING!

Hazardous voltages present. To avoid electric

shock or personal injury, adhere to the module replacement
instructions exactly as stated.

Summary of Contents for 1001RP Series

Page 1: ...odel 1001RP Series Rack Power Supply System SALES OFFICE 301 975 1000 TECHNICAL SUPPORT 301 975 1007 http www patton com Part 07M1001RPSVC C Doc 078452UC Revised 09 14 99 C E R T I F I E D An ISO 9001 Certified Company ...

Page 2: ...lectronics be liable for any damages incurred by the use of these products These damages include but are not lim ited to the following lost profits lost savings and incidental or conse quential damages arising from the use of or inability to use this prod uct Patton Electronics specifically disclaims all other warranties expressed or implied and the installation or use of this product shall be dee...

Page 3: ...re 1000CC 1000RC 222NRC 1010ARC 1018ARC 1045RC 1060RC 1070RC 1080ARC 1110RC 1110ARC and 1140RC Plugs into Patton Electronics Redundant Rack Chassis Model 1001RP Redundant supply serves up to 14 function cards Single supply serves up to 16 function cards Easily replaceable front and rear modules LED Indicators 12V Fail and Temperature 2 2 DESCRIPTION There are two 1001 series power supplies 1 Model...

Page 4: ...ad from 50 C to 70 C C All chassis ventilation holes and fan intake openings must remain open and unobstructed D The power supply modules are components of the 1001RP series rack system When installing the modules and making input con nections the relevant safety standards e g IEC950 VDE 0805 UL 1950 and EN 60950 must be complied with E For continued safe operation the power supplies must be opera...

Page 5: ...y card These two cards togeth er comprise a 48 VDC input supply module henceforth referred to as the DC power supply A single 1001R16P rack system may be fitted with any combina tion of the above listed power supplies For redundant applications two supplies are required 5 2 INSTALLING THE POWER SUPPLY MODULES This section describes how to install rear and front power supply cards into the chassis ...

Page 6: ...rear spacer to slot 16 using the two screws provided 5 Install the second power entry card into slot 15 Secure the card using the two screws provided 5 5 INSTALLING THE FRONT POWER SUPPLY CARDS INITIAL INSTALLATION To install a new front power supply card into the chassis follow the instructions below 1 Make sure that the associated rear power entry card is securely installed into the rack chassis...

Page 7: ...tor This con nector contains an integral fuse and accepts a domestic US power cord or any of several international AC power cords Only three wire power cords containing an earth ground lead may be used After the power cord is properly connected and power is applied the green 12V LED on the 1001RPSM RUI front panel will be illuminated and the fan will operate Voltage selection is automatic There is...

Page 8: ...nstall a new 1001RPSM RUI front module by carefully aligning it with the chassis guides Gently slide the card into the chassis along the metal rails provided The card connectors will meet the mid plane bus when the card is almost all the way into the chassis 5 After the connectors meet gently apply even pressure to the top and bottom of the panel to seat the card Do not force the card into the cha...

Page 9: ...ECTRONICS MODELS 1001RPSM R48V plus 1001RPEM RVDC 48VDC SPECIFICATIONS 12V FAIL TEMP Figure 4 Models 1001RPSM R48V 1001RPSM RUI Front Panel Showing LED s Input Specifications PARAMETER CONDITIONS DESCRIPTION MIN NOM MAX UNITS Input Voltage DC Reverse polarity protected 42 48 60 VDC Brown out Protection Lowest DC input voltage that 36 VDC regulation is maintained with full rated load Input Current ...

Page 10: ...o loss of input power Alarm Contacts Normally open and normally closed contacts via 3 position terminal block 1A 30V Contacts operate upon power failure detection Overtemperature RED indicator Shifts power fail Indication signal to a logic LOW state Output voltage during 4 4 5 5 VDC overtemperture condition User Controls Single jumper to select maintenance mode No alarm if PS is removed Safety Reg...

Page 11: ...within 1 of 250 us initial set point due to a 30 100 load change Load Sharing Two Supplies 72W load 1 5 Accuracy Efficiency Full load 115VAC in 78 88 Safety Regulatory and EMI Specifications PARAMETER CONDITIONS DESCRIPTION MIN NOM MAX UNITS Agency Approvals NRTL US UL 1950 CAN CSA 950 EN60950 Recognized CE Listing FCC Part 15 Class A Dielectric Withstand Input to output 1 second 3000 VRMS Voltage...

Page 12: ...ant Universal AC Input Power Entry Module 1001R14P 2U 14 Slot Redundant Rack Chassis 05R16FP440W Front Spacer 05R16BP440W Rear Spacer 08246 3A fuse Bussman GMD 3A Wickman 198 1300 0 00 08246 2 5A fuse Littelfuse 215 005 Wickman 19181 063 FS 10 00003 Terminal Plug For Alarm Connection 07M1001RPR User Manual 07M1001RPSVC Service Manual 05R16PL Plenum Safety Regulatory and EMI Specifications PARAMETE...

Page 13: ... performance of the 1001R rack system a fully loaded rack chassis may generate a considerable amount of heat To ensure long equipment life it is important the thermal management guidelines are adhered to in all 1001R installations In high density stacked configurations additional plenums may be required between each chassis to improve sys tem thermal performance Ambient air temperature total rack ...

Reviews: