Modu-Fire
®
Gas-Fired Boiler
Installation
For example, assume the following settings:
ITEM
DISPLAY
VALUE
SETPOINT 1
SP1
160
LOW TEMP DIFFERENTIAL
HyS1
-5
HIGH TEMP DIFFERENTIAL
HyS3
12
LOW TEMP SETPOINT
SPL
150
HIGH TEMP SETPOINT
SPH
195
The boiler will modulate to try to maintain 160
o
F.
If the temperature increases to 172
o
F which is
Setpoint 1 (SP1)
160
+ High Temp Differential
(HyS3)
12
, it will shut off. Once it shuts off, it will
not restart until the temperature drops to 155
o
F
which is Setpoint 1 (SP1)
160
+ Low Temp
Differential (Hys1)
-5
. The Low Temp Setpoint
(SPL) prevents the operator from setting Setpoint 1
(SP1) lower than Low Temp Setpoint (SPL)
150
.
The High Temp Setpoint (SPH) prevents the
operator from setting Setpoint 1 (SP1) higher than
the High Temp Setpoint (SPH)
195
.
Alternate Setpoint
The control must be configured for night setback.
(See the configuration menu.) When the Alternate
Setpoint contact is closed the boiler switches to its
alternate setpoint.
The alternate setpoint can be determined by several
different values. It can be a fixed alternate setpoint
SP2. It can be a fixed differential from SP1 called
dsP. dsP will “offset” the main setpoint SP1 by the
value of dsP. dsP can be positive or negative.
The Alternate Setpoint can also be determined by an
external analog source such as a 4-20 mA signal.
Outdoor Air Reset
The control must be configured for outdoor air reset.
(See the configuration menu.)
The setpoint of the boiler is controlled by an
outdoor temperature sensor. As the outdoor
temperature falls the setpoint of the boiler is
increased.
The boiler modulates to maintain this setpoint. The
boiler functions as indicated in internal setpoint;
however SP1 is determined by the outdoor air
temperature.
The setpoint SP1 is reset using a linear relationship
with outdoor air temperature. As the outdoor air
temperature drops the setpoint SP1 is increased a
proportional amount. This increase is determined
by the Heating Slope H. (See Table 1 at the end of
this section.) For example if H is set at 1 then for
every degree the outdoor air temp drops, the
setpoint SP1 will increase 1 degree.
This heating curve has a reference temperature of
68°. This reference can be offset using the Parallel
shift parameter P. (See Table 1 at the end of this
section.) If P is set to 0 the setpoint SP1 will be 68°
when the outdoor temp is 68°. If P is set to 10, the
setpoint SP1 will be 78° when the outdoor temp is
68°. The minimum setpoint of the boiler is limited
by the control. In the above example the actual
setpoint SP1 of the boiler will not go below 150°.
Analog Input Setpoint
The control must be configured for external
setpoint. (See the configuration menu.)
The setpoint of the boiler is controlled by an
external signal. The boiler functions as described
with the internal setpoint, using the value
determined by the external analog signal.
Analog Input Direct Drive
The firing rate of the boiler is controlled by an
external analog signal, usually from a multiple
5
Summary of Contents for THERMIFIC MODU-FIRE
Page 11: ...Modu Fire Gas Fired Boiler Installation 8 Table 1 Table of Parameters ...
Page 20: ...Modu Fire Gas Fired Boiler Parts Technical Support Standard Unit w Siemens Control 17 ...
Page 21: ...Modu Fire Gas Fired Boiler Parts Technical Support Standard Unit w Remote Control 18 ...
Page 22: ...Modu Fire Gas Fired Boiler Parts Technical Support IRI with Siemens Control 19 ...
Page 23: ...Modu Fire Gas Fired Boiler Parts Technical Support IRI with Remote Control 20 ...