Conversion to LP gas orifice
1. Take out the screws on the top cover, then take off the top cover. You can see the orifice is on the
left side of the
Salamander
as below
Fig.7
shows.
Fig.7
Fig.8
2. As Fig. 8 shows, unscrew and remove the Nat. gas orifice [#31(φ3.2mm)] turning counter-clockwise,
then screw in the LP gas orifice *#52(φ1.68mm)+ clockwise.
3. Change the pressure regulator spring kit to LP gas model, set at 10" W .C. (Water Column).
Fig.9,
Fig.10
4. Turn pilot adjustment screw clockwise, then light standing pilot and adjust flame to be 1/4" high.
A product with the
Patriot
name incorporates the best in durability and low maintenance. We all recognize,
however, that replacement parts and occasional professional service may be necessary to extend the
useful life of this unit. When service is needed, contact a
n
Authorized Service Agency, or your dealer. To
avoid confusion, always refer to the model number, serial number, and type of your unit.