Troubleshooting Flow Charts
38
PROBLEM: Interference from crane
electric. Error Code “E93/E94"
intermittent. Frozen console displays.
Interference Problem
START
Refer to Section 8 - Bad Data
Transfer Between Console & Central Unit.
Correct?
No
Replace or repair part which is defective.
Yes
Check if additional ground link between main
board terminal X1:3 and central unit box mounting bracket is in place.
Correct?
No
Install ground line - single cable minimum of AWG14 (2.0mm ) between
terminal X1:3 and central unit box mounting bracket.
Refer to system wiring diagram.
Yes
Ensure that cable shields are connected correctly. Refer to connection and
wiring diagrams, Refer to system wiring diagram.
Correct?
No
Make correct shield connection.
Refer to system wiring diagram.
Yes
Find out which component of the crane electric is spiking out (e.g. dump valve, outrigger relay). Install
a diode or resistor across terminals of spiking component. Diode type such as 1N4001 can be used,
END
Summary of Contents for DS 150
Page 2: ......
Page 3: ......
Page 5: ...Service Manual DS150...
Page 7: ...Service Manual DS150...
Page 10: ...Mechanical Description Of The System 3 Basic System Component Layout...
Page 13: ...Drawings 6 4 DRAWINGS SYSTEM Electrical Diagram...
Page 14: ...Drawings 7 Central Unit 024 150 060 002 Spare Parts List...
Page 20: ...Drawings 13 4 5 Cable Reel 068 208 060 013 LWG208 Spare Parts List...
Page 24: ...Procedures 17 Length Angle Adjustments...
Page 26: ...Theory 19 6 THEORY Anti Two Block Shutoff Circuit Length Measuring Channel...
Page 27: ...Theory 20 Piston Side Pressure Measuring Channel Rod Side Pressure Measuring Channel...
Page 28: ...Theory 21 Main Boom Angle Measuring Channel Second Angle Measuring Channel...
Page 53: ...Error Codes 46 America Inc service department...