INSTRUCTION REF: IN176
ISSUE No. 1
DATE 2.01.08
Page 24 of 59
TELEPHONE:
SERVICE (44) 01332 875665
FAX:
SERVICE (44) 01332 875536
Parry Group Limited,
Town End Road, Draycott, Derby, England DE72 3PT
www.parry.co.uk
Internal Direct Drive Centrifugal Fans
Parry offer a new range of canopies with
internal fans. The internal fans used are
centrifugal type fans.
Unless otherwise stated on an order, all
canopies sold with internally mounted fans
will have the fan extracting through the top
panel. If the canopy contains one fan it will
be fixed to the centre of the top panel if it
has two or more fans they will be evenly
spread along the length of the top panel.
If another position is required for the
mounting of the fan this is possible at an additional charge. Please state the
exact dimension at time of order.
Fan Code
Width
of
Blades
(inch)
Diameter
of Blades
(inch)
Motor
Rating
(W)
Speed
(rev/min)
Max
Current
(A)
Sound
Pressure
(dB (A) )
Minimum
Air
Volume
(m3/h)
FANDD7-7
7
7
92
1400
1.5
57
500
FANDD9-9
9
9
368
1400
3.8
61
750
Fan Code
Minimum
Air
Volume
(m3/s)
Maximum
Air flow
(m3/h)
Maximum
Air flow
(m3/s)
Minimum
External
resistance
(Pa)
Weight (Kg)
Electrical
connection
(V/ph/Hz)
FANDD7-7
0.14
1150
0.32
75
6.9 230/50/1
FANDD9-9
0.21
2300
0.64
260
14.2 230.50/1