11
JINCHI05 REV E. 11/11/2014
F
LUE OUTLET
P
OSITIONS
(D
OCUMENT
J):
Position on Roof
Clearances to flue exit
A
At or within
600mm of the ridge
At least 600mm
above the ridge
B
Elsewhere on a roof
(Pitched or Flat)
At least 2.3 M
horizontally from the
nearest point on the
weather surface and:
a) At least 1.0 M above
the highest point of
intersection between the
chimney and weather
surface; or
b)at least as high as the
ridge
C
Below (on a pitched
roof) or within 2.3 M
horizontally to an
opening window or
dormer
At least 1.0 M above the
top of the opening
D
Within 2.3 M of an
adjoining or
adjacent building,
whether or not
beyond the
boundary
At least 600mm above
any part of the adjacent
building within 2.3 M
A full copy of Document J can be found here:
http://www.planningportal.gov.uk/uploads/br/BR
_PDF_ADJ_2010.pdf
INSTALLATION INSTRUCTIONS
L
EGAL
R
EQUIREMENTS
Parkray Stoves requests that before installation
and/or use of this appliance that you read these
instructions carefully to ensure that all the relevant
requirements are fully understood.
These instructions cover the basic principles to
ensure satisfactory installation of the stove,
although detail may need slight modification to
suit particular local site conditions. In all cases the
installation must comply with current Building
Regulations, Local Authority Byelaws, European
and National Standards and other specifications or
regulations as they affect the installation of the
stove.
It should be noted that the Building Regulations
requirements may be met by adopting the relevant
recommendations given in British Standards BS
8303, BS 6461 and BS 7566 as an alternative means
to achieve an equivalent level of performance to
that obtained following the guidance given in
Approved Document J.
Your local Building Control Officer can advise you
regarding the interpretation of the Regulations
should there be any questions.
This appliance must be installed by a Registered
Installer (see Competent Persons Scheme) or
approved by your local Building Control Officer.
All works undertaken must be carried out with due
care and attention to meet the requirements of the
Health & Safety code of practice and any other
legislation that may have been introduced since
the publication of these instructions.
W
ARNING
!
A faulty installation can cause danger, ill health and
even death to the inhabitants and possibly
compromise the structure of the building.