MAIN OVEN
Natural Gas
L.P. Gas
Heat Input
2.4kW (8189Btu/h)
2.4kW (172.4 g/h)
Injector Marking
108
78
Flame Supervision Device
Diamond'H' GSD 100/28
Diamond 'H' GSD-100-30
Thermostat
Diamond'H' 1100 93/B2
Diamond'H' 1100-98/B2
Thermostat By-Pass Marking
69
78
SECOND OVEN
Natural Gas
L. P. Gas
Heat Input
2.4kW (8189 Btu/h)
2.4kW (172.4g/h)
Injector Marking
108
78
Flame Supervision Device
Diamond 'H' GSD 100/31
Diamond 'H' Ref GSD-100/34
Dual Control
Sourdillon 60112/982
Sourdillon 60525/982
Dual Control By-pass
Fixed Internal
Fixed Internal
GENERAL
Ignition
H. T. Spark
Spark Gap
3-4mm
IMPORTANT - SAFETY REQUIREMENTS
This appliance must be installed in accordance with the Gas Safety (Installation and Use) Regulations
Current Editions. Detailed recommendations are contained in the following British Standard Codes of Practice
- BS. 6172, BS.5440: Part 2 and B.S.6891. All British Standards must be 'Current Editions'.
PROVISION FOR VENTILATION
The room containing the appliance should have an air supply in accordance with BS.5440: Part 2 Current
Edition. All rooms require an openable window or equivalent and some rooms will require a permanent vent
as well. For room volumes up to 5m³ an air vent of 100 cm² is required; for room volumes between 5m³ and
10m³ an air vent of 50cm² is required. If the room has a door that opens directly to the outside, no air vent is
required. For room volumes that exceed 11m³ no air vent is required. If there are other fuel burning
appliances in the same room, BS.5440: Part 2 Current Edition should be consulted to determine the requisite
air vent requirements
.
The use of a gas cooking appliance results in the production of heat and moisture in
the room in which it is installed. Ensure that the kitchen is well ventilated: keep natural ventilation holes open
or install a mechanical ventilation device (mechanical extractor hood).
Prolonged intensive use of the appliance may call for additional ventilation, for example opening of a window,
or more effective ventilation, for example increasing the level of mechanical ventilation where present.
37
S O N A T A 5 5 G L X