background image

Digital Power Amplifier

Series VRD350 and VRD355

Installation Manual

29

IA VRD UK.INDD RH 02.06

Parker Hannifin GmbH & Co. KG

Hydraulic Controls Division

The internal command signal used for 
this  purpose  serves  as  a  final  value 
(position value). The drive is run to this 
value according to the pre-set ramp.

Status Chart of Safety Function

External Control, Pressure Control

Pressure  sensors  can  be  designed  in  two  or 
three-wire technology. The sensor signal is either 
a voltage from 0...10V or a current from 0...20mA 
or  4...20mA. The  parameter  E11  should  be  set 
between 7 and 9. Apart from an adjustment to the 
sensor signal, this also prevents controller param-
eters U13 < 0 (see page 22). Wire break monitoring 
is only possible with 4...20mA sensor signals.
When  connecting  pressure  sensors  we  recom-
mend that great care be taken. The zero volt wiring, 
screening  and  PE  connection  are  critical.  Faults 
in the signal can lead to a triggering of the wire 
break monitor. Instabilities in the control loop are 
also possible.
The scaling of the sensor signal is very important 
for a high quality pressure control. This also guar-
antees a maximum exploitation of the resolution. 
The maximum pressure to be controlled is decisive. 
The closer the sensor signal is to 10V or 20mA, 
the  more  favourable  this  is.  In  other  words,  the 
measuring range of the sensor must be adapted to 
the pressure range of the application. Furthermore, 
the setting of the actual value adjustment must also 
be given special attention. At the maximum pres-
sure to be controlled, almost 9.90V should appear 
in display U11.
Example:

When setting the zero point, care must 
be  taken  because  pressure  valves  do 
not permit a drop in pressure to 0 bar 
on account of their design.

Summary of Contents for VRD355 Series

Page 1: ...ision Gutenbergstr 38 41564 Kaarst Germany Tel 49 181 99 44 43 0 Fax 49 2131 513 230 E mail infohcd parker com Copyright 2003 Parker Hanni n GmbH Co KG Bulletin HY11 AL287 M1 UK Installation Manual Se...

Page 2: ...lectoruseanyproductorsystem it is important that you analyse all aspects of your application and review the information concerning the product or system in the current product catalogue Due to the var...

Page 3: ...n Generators 24 3 3 Offset 25 3 4 Valve Curve Linearisation 25 3 5 Adjustment of Current Gain 25 3 6 Dither 25 3 7 Current Controller 25 3 8 Output Stages 25 3 9 Step Functions 26 3 10 Control Circuit...

Page 4: ...Simple operation by 4 entry keys and 3 digit LED display Fault indication by numeric code Variable dither amplitude and frequency Gain for solenoids A and B can be set indepen dantly Different valve c...

Page 5: ...0 10 150kOhm Digital 0 V 0 1 1 V 3 30 Outputs Ext supply voltage V 24 10 ripple 5 Reference V 10 10 10mA Analogue V 0 10 5mA Digital mA 50 Solenoids A 0 8 2 7 3 5 Interfaces Serial RS 232C Adjustment...

Page 6: ...enoids or position indicator with 7 5V null voltage Code Ext closed loop 0 without 0 0 10V 1 4 20mA 2 0 20mA Code Sensor assignment 01 controlled 12 Flow valves NG6 22 Directional valves NG6 32 Direct...

Page 7: ...ence The following devices are to be regarded as strong sources of interference Switching power supply units Frequency converters Drive modules Mains lters with wiring even if screened AC DC commutato...

Page 8: ...ke a potential equalisation Use only cables with a Cu screening grid and a covering of 85 whenever possible Avoid screening lms The screen may not be interrupted along the entire length of the cable I...

Page 9: ...Digital Power Ampli er Series VRD350 and VRD355 Installation Manual 9 IA VRD UK INDD RH 02 06 Parker Hanni n GmbH Co KG Hydraulic Controls Division 1 4 Block Diagram Entire System...

Page 10: ...RD UK INDD RH 02 06 Digital Power Ampli er Series VRD350 and VRD355 Installation Manual Parker Hanni n GmbH Co KG Hydraulic Controls Division Feedback Option hardware only with boards for closed loop...

Page 11: ...7 5V Voltage input without terminating resistance Used for potentiometric transmitter systems in which the loop current is limited to smal values Linearity of the transmitter signal is maintained Cur...

Page 12: ...le emergency stop measures must be taken Application Construction and Operation of ABG35S The ABG35S plug in control unit is used in con junction with the VRD355 proportional ampli er It can easily be...

Page 13: ...anni n GmbH Co KG Hydraulic Controls Division 2 2 Programming Programming Instructions for U S P and E Values Select mode U1 S1 P1 or E1 can be selected Select address Display contents e g S2 has the...

Page 14: ...he ampli er This setting depends on the type of ampli er see also type code This basic setting can be recovered from memory by pressing the 4 keys at the same time up to 10 seconds after the supply vo...

Page 15: ...Hydraulic Controls Division 2 3 Block Diagram Open Loop Control Software functions Open loop Parameter functions U parameter display of internal measured values S parameter internal command signals an...

Page 16: ...Hydraulic Controls Division Closed Loop only with boards for closed loop systems Closed loop Parameter functions U parameter display of internal measured values S parameter internal command signals an...

Page 17: ...systems External closed loop Parameter functions U parameter display of internal measured values S parameter internal command signals and ramps H parameter auxiliary parameters P parameter operating...

Page 18: ...vision Remote Loop Control only with boards for closed loop systems Remote loop control external closed loop E2 2 Parameter functions U parameter display of internal measured values S parameter intern...

Page 19: ...lic Controls Division Bypass Controller only with boards for closed loop systems Bypass controller Parameter functions U parameter display of internal measured values S parameter internal command sign...

Page 20: ...cting variable Note Parameter setting and diagnostics only possible for VRD355 using ABG35S Only trained staff should make pa rameter changes The drive should be switched off whilst adjusting para met...

Page 21: ...3 03 V of 0 30 a setpoint of 3 V corresponds to 30 see also page 25 section 3 6 P6 Dither frequency variable in steps from 0 to 647 Hz steps 0 16 40 60 80 110 130 160 220 327 647 in Hz See also page...

Page 22: ...trol only with boards for closed loop systems not active 0 active 1 remote loop control 2 bypass control 3 safety function active only with E14 1 4 E3 Solenoid type 3 5A 9V solenoid coil 1 8 1 reserve...

Page 23: ...data in ABG35S S Load data to ampli er L E16 Activates action selected with E15 Proceeding Press button E The display shows the function selec tedpreviously with parameter E15 S or L Activate the data...

Page 24: ...al Command Signal 5 and Command Signal 6 SW5 and SW6 The command signal inputs 5 and 6 are de signed for signals 0 10 V These setpoints are also passed through the ramp function generator ramp if E8 1...

Page 25: ...dither signal reduces the hysteresis of spool movement Generally low frequency signals are more effective however they may result in noticeable disturbances noise oscil lations Values between 80Hz for...

Page 26: ...or selections 1 to 6 U13 can be positive or negative depending on the difference between feedback and set value Then either solenoid A or B is energized 3 11 To set Zero Point General Case Place the f...

Page 27: ...KP P share of the PID controller P15 has no function E14 0 set Parameter P14 can be used to program a T portion delayingtimefunctionelement Effect on P16 The integral portion is determined by P17 whi...

Page 28: ...E g in position control loops the ramps determine the speed of the drive Using the equations given on page 22 enables the computation of parameters from the loop gain factor In cases where these calc...

Page 29: ...pressure sensors we recom mend that great care be taken The zero volt wiring screening and PE connection are critical Faults in the signal can lead to a triggering of the wire break monitor Instabili...

Page 30: ...s preferably used If the actual value now exceeds this comparative value the control switches on Even if the actual value is under the switching threshold the control remains active The signal at the...

Page 31: ...P21 and P22 Setting E2 3 activates the bypass P13 deter mines the gain of the bypass loop P15 is without any function and P16 sets the P portion P17 the I Portion and P18 the D Portion of the PID con...

Page 32: ...s via a so called null mo dem cable The program PROVRD350 355 Order No HR 59 500 010 is available to carry out programming and remote control This permits simple remote control and programming of the...

Page 33: ...e gure page 9 4 3 Malfunction and Error Messages The current in the output stages is monitored in the ampli er If the total current exceeds a speci c limit an electronic cut out responds and switches...

Page 34: ...10V output PE decoupled 10V output 22 Solenoid A Solenoid A Solenoid A 24 Solenoid B Solenoid B Solenoid B 26 Supply 0V Supply 0V Analogue 0 28 Solenoid A Solenoid A Solenoid A 30 Solenoid B Solenoid...

Page 35: ...eshold P15 0 255 P17 I portion 0 255 P18 D portion 0 255 P19 T portion of DT1 element 0 255 P20 Gain for feedback signal 0 00 2 00 P21 Window Set feedback 0 V 0 00 9 99 P22 Window Set feedback 0 V 0 0...

Page 36: ...Setting Basic Version VRD35X 031 00 old new S1 S4 0 S5 S8 0 H1 H2 Set to 0 after commissioning P1 0 00 P2 0 P3 1 00 P4 1 00 P5 0 80 P6 110Hz P7 0 00 P8 0 00 P9 P10 0 00 P11 1 P12 1 P13 0 P14 0 P15 9...

Page 37: ...open loop version Note All screens are to be earthed over a large areal Earth ampli er with short lines Bridge unused analogue inputs to analogue 0V In the case of terminal names with a number of lett...

Page 38: ...areal Earth ampli er with short lines Bridge unused analogue inputs to analogue 0V In the case of terminal names with a number of letters the terminals are bridged on the ampli er If no electrical iso...

Page 39: ...real Earth ampli er with short lines Bridge unused analogue inputs to analogue 0V In the case of terminal names with a number of letters the terminals are bridged on the ampli er If no electrical isol...

Page 40: ...eal Earth ampli er with short lines Bridge unused analogue inputs to analogue 0V In the case of terminal names with a number of letters the terminals are bridged on the ampli er If no electrical isola...

Page 41: ...e areal Earth ampli er with short lines Bridge unused analogue inputs to analogue 0V In the case of terminal names with a number of letters the terminals are bridged on the ampli er If no electrical i...

Page 42: ...areal Earth ampli er with short lines Bridge unused analogue inputs to analogue 0V In the case of terminal names with a number of letters the terminals are bridged on the ampli er If no electrical is...

Page 43: ...rge areal Earth ampli er with short lines Bridge unused analogue inputs to analogue 0V In the case of terminal names with a number of letters the terminals are bridged on the ampli er If no electrical...

Page 44: ...44 IA VRD UK INDD RH 02 06 Digital Power Ampli er Series VRD350 and VRD355 Installation Manual Parker Hanni n GmbH Co KG Hydraulic Controls Division...

Reviews: