background image

Bulletin 100-50-1 /

 Page 3

SET POINT POTENTIOMETER

 

The  potentiometer  is  only  used  when  the 
TCB  acts  as  a  standalone  controller.  When 
using an external signal source the potenti-
ometer is not required and may be removed. 
When  used  with  the  optional  sensors,  tem-
perature range is -40°F to 210°F.

CAUTION: The TCB with potentiometer 

cannot  be  used  to  directly  control  an 

Electric  Expansion  Valve  (EEV).  EEVs 

must be controlled by superheat sensing 

and  the  TCB  can  only  supply  a  single 

temperature signal.

PIN JUMPERS

Pin  jumpers  are  used  in  electronics  as 
switches  for  parameters  that  need  not  be 
changed after initial configuration. Always 
remove power from the board before mak-
ing pin jumper changes.  

The jumper itself is a small plastic housing 
containing  metal  contacts.  These  contacts 
will  fit  snugly  over  two  adjoining  pins  to 
create an electrical “closure”. In the tables 
and instructions below, the Letters indicate 
the  pins  that  are  to  be  connected  with  the 
pin jumpers. Care should be taken to make 
sure  both  pins  are  covered  by  the  jumper 
and the pins themselves are not damaged. 

SETUP INSTRUCTIONS

CONFIGURE THE BOARD

1.

 

Choose the valve - See 

Table 1

2.

 

Choose the signal - See 

Table 2

3.

  Set the logic - Refer to instructions 

  on right

MOUNT THE BOARD

Use the four corner mounting holes with plas-
tic  or  metal  standoffs. 

Care must be exer-

cised  to  ensure  that  mounting  screws  or 

metallic standoffs do not contact any track 

or conductor path on the board. 

Location 

chosen should be dry, protected and close to 
24 VAC supply and PID controller. If used, 
Set  Point  Potentiometer  may  be  remotely 
mounted,  e.g.  through  the  control  panel. 
Refer to “SET POINT POTENTIOMETER” 
section for instructions.

WIRE THE BOARD

1. 

If  using  an  external  PID  or  PLC  con-

troller,  connect  the  positive  lead  to  the 
first  screw  terminal  on  the  board  and  the 
negative lead to the second screw terminal. 

CAUTION:  The  PLC  or  PID  controller 

must  be  able  to  supply  20  milliamps  at 

12  volts  DC  into  a  600  ohm  impedance. 

Other  signals  may  not  control  the  TCB 

properly. 

If the internal temperature control 

is used, these terminals will not be used.

2. 

Connect the valve leads to the next four 

screw terminals, matching indicated colors.

3. 

If  TTL  logic  is  being  used  to  control 

the  valve,  connect  the  step  signal  to  the 
Square  wave  terminal  and  the  direction 
signal to the DIRECTION terminal. If TTL 
logic  is  not  used  these  terminals  will  not 
be  connected.  Contact  Sporlan  for  more 
information.

4. 

Connect  a  24  VAC,  40  VA  transformer 

to these terminals.  

CAUTION: The trans-

former  may  not  be  used  for  any  other 

device. 

The isolated secondary of this trans-

former  is  not  polarized  and  may  be  con-
nected to either screw terminal.

5. 

Connect  the  PUMPDOWN  signal,  if

used.  The  board  will  close  the  valve 
whenever  a  closure  or  dry  contact  across 
these  terminals  is  present.  When  the  sig-
nal  is  removed  or  “opened”  the  valve  will 
resume normal operation. No voltage should 
be  supplied  to  these  terminals.  If  pump-
down is not required these terminals may not 
be used.
The  TCB  pumpdown  can  be  configured  to 
open  the  valve  fully  whenever  a  contact  is 
made  across  the  “pumpdown”  terminals. 
To  invoke  this  function,  the  supplied  pin 
jumpers on P5 (Open Valve) and P6 (Close 
Valve)  must  be  placed  across  both  pins  of 
each jumper.

6. 

Connect  the  temperature  sensor  to  the 

two  terminals.  The  leads  are  not  polarized 
but  the  sensor  must  be  Sporlan  supplied  to 
operate properly.

7. 

Two blank terminals are included for high 

voltage isolation.  These are the second and 
fourth  terminals  up  from  the  bottom  of  the 
board.  No  connections  are  to  be  made  to 
these  terminals.  No  screws  are  present  in 
the terminals.

8. 

Two  terminals  are  provided  for  24-120 

VAC  Pulse  Width  Modulated  signal 
inputs.  The  pulse  width  may  be  from  3 
to 30 seconds in width and no adjustment 
to  the  board  is  necessary.    If  the  board  is 
controlled  by  other  means  these  terminals 
will not be used.

SET THE LOGIC

Placing a jumper on either P8 or P9 will set 
the  logic  or  direction  of  “close”  in  relation 

to the temperature sensor, or the externally 
generated  signal.  The  “APPLICATION” 
section  shows  the  jumper  settings  for  hot 
gas  bypass  valve  or  evaporator  control 
valve applications.  Selection of “OPEN ON 
RISE”  or  “CLOSE  ON  RISE”  is  based  on 
sensor  location,  application,  and  controller 
logic. If the valve operates opposite from the 
intended manner, move the jumper from P8 
to P9 or from P9 to P8. Sporlan will be glad 
to provide assistance in this selection.

SET THE BOARD

When  used  as  an  interface  board,  setting 
adjustments are made through the controller 
used.  When  used  as  a  standalone  control-
ler,  setpoint  is  set  with  the  potentiometer 
dial and test points.

 

The dial label will pro-

vide  coarse  adjustments,  a  millivolt  volt-
meter  connected  across  Test  Points  1  and 
2 will provide a direct temperature setpoint      
readout. For Example:

32 mVdc=32°F Setpoint

Table 1 

VALVE

STEPS

P10 P11 P12

SEI .5 - 11

1596

XXX

SEI 50

6386

XXX

SEH ALL

6386

XXX

CDS-8*

3193

XXX

CDS-9, 16 & 17 

6386

XXX

SDR-3

3193

XXX

SDR-4

6386

XXX

OTHERS

6386

XXX

NOTE:

 

Only one jumper is used. 

*CDS-8 is Obsolete

Table 2

INPUT

STEPS

P1

P2

P7

4-20 ma

External

L,C

0-10 VDC

External

C,R

TTL LOGIC

External

L,C

120 VAC PWM

External

C,R

TEMP 

SENSOR

External

Top & 

Bottom

NOTE:

   

L = left   R = right   C = center

When board is viewed as shown in Figure 1.

Reviews: