Parker Sporlan Subcool Control Installation And Operation Instructions Manual Download Page 5

Bulletin 100-50-5.2 –

 Page 5

suction header to a maximum target value. By default, this 
setpoint is high in order to provide full functional subcool 
control from the factory. If the 

rGhL

 is set low, the control-

ler will override traditional subcool control in order to satisfy 
the return gas temperature. In this state, the 

LoVt

 temperature 

may fall below the setpoint. To access these parameters see 
Section 3 - Setpoint Menu Operation, 

page 4.

Manual Valve Position Feature

The Sporlan Subcool Control offers the ability to control 
the subcooler expansion valve manually. This feature can be 
used in troubleshooting to determine if the expansion valve 
responds to an open or closed position signal directly from 
the controller. In normal operation, the manual mode should 
never be used. 

WARNING : Be sure to avoid floodback while using 
this feature. Start with the valve in the low position.

Prior to entering manual mode, attach a Sporlan Kelvin II re-
mote display to the RJ-45 port on the side of the Subcool Con-
trol to monitor superheat. This will allow the user to maintain 
a minimum superheat while in manual mode by adjusting the 
valve position. If the valve is positioned too far open while in 
manual mode, superheat will drop and liquid may enter the 
suction line. It is always better to start with the valve position 
low and work up to a higher position gradually while observ-
ing the superheat value on the remote display. Superheat 
should never be allowed to drop below 2°F. If this situation 
occurs, reduce valve position and allow system to respond 
(superheat should increase). 

An alternate way to monitor superheat is to use a gauge set 
and a calibrated temperature sensor on the suction line; how-
ever the pressure and temperature will need to be converted to 
superheat. 

To enter manual mode, press and hold the Select knob, select 

111

, scroll to 

Spos

 and push the knob. See Section 3 - Set-

point Menu Operation

. The valve will start at the current 

“original” position. The controller will show percent valve 
opening. To verify if the valve is functioning, lower the valve 
position by rotating the knob counter-clockwise and note 
the change in superheat (increase). From this, increase valve 
position slowly and note the change in superheat (decrease). It 
may be necessary to allow appropriate time for system to re-
spond to changes. Ensure superheat does not drop below that 
described above. To exit manual operation mode, press encod-
er knob, scroll to 

ESC

, and press the knob again. After exiting 

manual mode, observe the system for proper operation.

 

WARNING: The controller should never be left 
unattended in manual mode. 

5. Controller Networking

The Sporlan Subcool Control can communicate with a 
MODBUS communication master via RS485 to transfer pro-
cess values and setpoints.

The Subcool Control supports only the RTU transmission 
mode. The serial settings are:

• 

9600 baud (default), 19200 baud, 38400 baud

• 

8 data bits

• 

1 stop bit

• 

Even parity (default), odd parity, no parity

The Subcool Control supports the ‘Read Input Registers’, 
‘Read Holding Register’, ‘Write Single Register’, ‘Read 
Multiple Coils’ and ‘Write Single Coil’ function codes. Other 
requests will cause an exception response. The Subcool 
Control will allow a full and partial block read of the Input 
and Holding registers and coils.

Scaling for Celsius / Bar

For better precision, scaling is used for Bar or Celsius units. 
PSI and Fahrenheit values are whole numbers and have no 
scaling. See Appendix K - MODBUS Memory Map.

Celsius values transferred via MODBUS are 10X. For exam-
ple A value of 45 will be transferred for the Superheat when 
the actual Superheat temperature is 4.5°C. Remember this 
when changing a setpoint.

Bar values transferred via MODBUS are 100X. A value of 34 
will be transferred for the Pressure Sensor Calib. Offset when 
the actual pressure is .34 bar. Remember this when changing 
a setpoint.

Setup

The Sporlan Subcool Control can be networked to com-
municate process variables back to a master controller. This 
information can be used for verifying system performance or 
updating individual setpoints via RS-485 and PC interface. 
Data can be accessed remotely through the master controller. 
For further information on remote monitoring of subcooling, 
see corresponding manuals for the master controller.

Prior to establishing the network, each controller must be 
assigned a separate address. Refer to Section 3 – Setpoint 
Menu Operation

 to enter setpoint menu. Once in the Setpoint 

menu, scroll to 

AddR

 and set each controller on the network 

with individual addresses. Note: No two controllers can have 
the same address. Default address for each controller is ‘1’.

MODBUS Communication Requirements

See Figure 4 - MODBUS Wiring

Wire Type:

 22-24 AWG Universal Twisted Pair

Maximum Number of Network Nodes:

 100

Maximum Run Length:

 4000 ft

Communication

Master

Figure 3 - Daisy Chain 
Network Configuration

Summary of Contents for Sporlan Subcool Control

Page 1: ...Bulletin 100 50 5 2 Page 1 Subcool Control Installation and Operation Instructions July 2020 Bulletin 100 50 5 2 Controller v G 1...

Page 2: ...e The user through its own analysis and testing is solely responsible for making the final selection of the system and components and assuring that all performance endurance maintenance safety and war...

Page 3: ...ressure temperature control for most common refrigerants It displays actual leaving liquid temperature superheat suction pressure valve position controller status and alarms It also allows manual cont...

Page 4: ...ivity and you will lose all changes entered 1 Enter the Parameter Menu Press and hold the SELECT knob for 5 seconds Rotate the knob to enter the pass word 111 and press the SELECT knob again 2 To chan...

Page 5: ...ges Ensure superheat does not drop below that described above To exit manual operation mode press encod er knob scroll to ESC and press the knob again After exiting manual mode observe the system for...

Page 6: ...ammed with de fault Proportional Integral Derivative PID settings that will provide efficient control It may be necessary however to fine tune the PID settings in applications where systems experi enc...

Page 7: ...nsor will read 60 on the controller Temperature sensor output can be checked by measuring the DC voltage across the sensor wire using the tables in Appen dix L page 19 and Appendix M page 20 Since the...

Page 8: ...ontrol power Pump down signal ensure Subcool Control expansion valve is not closed Proper system refrigerant charge Liquid line filter clogging or excessive pressure drop Proper Subcooler OffTemperatu...

Page 9: ...adout Description R 22 R 134a R 402A R 404A R 407A R 407C 410A R 410A 417A R 417A R 422A R 422D R 507A R 744 R 245FA R E5 R 438A R 401B 408A R 408A 508A R 508A 508B R 508B 407F R 407F 434A R 434A 444B...

Page 10: ...ional S 4 Status of the Auxiliary Temperature Input Stat Controller Status ALS Controller Alarms APPENDIX C Controller Status DISPLAY DESCRIPTION CooL Subcool On Valve modulating pdn Pumpdown Valve cl...

Page 11: ...448A R 448A 450A R 450A 449A R 449A 452A R 452A 513A R 513A Maximum Valve Capacity 0 to 100 Default is 100 Liquid Proportional Coefficient 0 to 25 5 Default is 1 0 Increase value to increase valve res...

Page 12: ...Units Readout Description Pounds Force Per Square Inch Bars Temperature Units Readout Description Fahrenheit Celsius t4p Temperature SensorType Readout Description typ3 3k typ2 typ2 2k tP10 10k 4 Cho...

Page 13: ...Coefficient LSHi Low Superheat Integral Gain Coefficient The integral gain coefficient to use for the superheat PID loop if the superheat is below 3 degrees F CyCt CycleTime The PID update time StEP...

Page 14: ...ENDIX G Alarms and Failsafes APPENDIX H Technical Specifications ELECTRICAL Supply Voltage 20 26VAC 50 60Hz or 22 26 6VDC Class II input 40VA is recommended for each controller Digital Inputs 0 5VDC M...

Page 15: ...ls Counter Flow Brazed Plate Heat Exchanger Dry Contacts T4 Evap Outlet Temp T1 Liquid Outlet Temp T2 White Signal Green Ground Black 5VDC Black 24V AC DC RS485 White Green Red B Ground A Suction Temp...

Page 16: ...ensors 10 14 inches from the heat exchanger on a free draining hori zontal line 2 Remove all insulation and adhesives at the marked loca tion Using Scotch BriteTM clean the copper line to remove oxide...

Page 17: ...422D 10 R 507A 11 R 744 12 R 245FA 13 R E5 14 R 438A 15 R 401B 16 R 408A 17 R 508A 18 R 508B 19 R 407F 20 R 434A 21 R 444B 22 R 448A 23 R 450A 24 R 449A 25 R 452A 26 R 513A 5 Valve Maximum 0 to 100 6...

Page 18: ...sor Range and Type 15 to 500 PSI 1 01 to 34 47 Bar Maximum Range 4 Saturation Temperature 60 to 150 F 51 1 to 65 6 C 5 Suction Temperature 60 to 125 F 51 1 to 65 6 C 6 Valve Position of Max Stroke 0 t...

Page 19: ...5 0 41 1 837 1 915 5 6 42 1 812 1 889 6 1 43 1 788 1 863 6 7 44 1 763 1 837 7 2 45 1 739 1 812 7 8 46 1 715 1 787 8 3 47 1 691 1 763 8 9 48 1 668 1 738 9 4 49 1 644 1 714 10 0 50 1 621 1 690 10 6 51 1...

Page 20: ...698 5 0 41 2 556 2 663 5 6 42 2 522 2 628 6 1 43 2 489 2 593 6 7 44 2 455 2 558 7 2 45 2 422 2 524 7 8 46 2 389 2 489 8 3 47 2 356 2 455 8 9 48 2 323 2 421 9 4 49 2 290 2 386 10 0 50 2 258 2 353 10 6...

Page 21: ...438 3 540 15 0 59 3 412 3 511 15 6 60 3 383 3 486 16 1 61 3 357 3 456 C F RANGE VDC 16 7 62 3 327 3 427 17 2 63 3 301 3 401 17 8 64 3 271 3 372 18 3 65 3 244 3 346 18 9 66 3 214 3 316 19 4 67 3 183 3...

Page 22: ...een 98 6k Surface Sensor white 952662 230545 230546 230072 230076 230078 230073 952565 Used with or without well 20 ft Surface only 20 ft Air Only 20 ft Surface only 20 ft Surface only 20 ft Surface o...

Page 23: ...ion Author Approved 000 122011 Added Revision History 001 062012 Updated Appendices E I K N Updated Table 2 JH ER 002 112012 Revised as Bulletin JH ER APPENDIX P System Flow Chart Start NO PROCESS Con...

Page 24: ...Parker Hannifin Corporation Sporlan Division 206 Lange Drive Washington MO 63090 USA phone 636 239 1111 fax 636 239 9130 www sporlan com Bulletin 100 50 5 2 72020 2020 Parker Hannifin Corporation...

Reviews: