4. Parameters
The following tables describes the parameters that are available for this controller. The parameters can be
accessed by connecting to the controller by using a mobile device such as a smart phone. See the Setup
Section for more details on how to connect to the controller.
Parameter
Description
Range
Date/Time
Current date and time
Dates/Times
Superheat Target
The desired superheat
5°F to 45°F
2.78°C to 25°C
Refrigerant
Specifies what refrigerant is being used
See list of available refrigerants
Identification - Rack
Identifies the compressor rack
the coil is connected to
4 characters, alphanumeric
Identification - Lineup
Identifies the lineup the coil is connected to
4 characters, alphanumeric
Identification - Case ID
Identifies the specific case/coil being
controlled by the controller
4 characters, alphanumeric
Pressure Transducer - Range
Specifies the range of the pressure
transducer being used
0 to 1000 PSI
0 to 68.95 bar
Pressure Transducer - Type
Specifies the pressure transducer type
Absolute or Gauge
Pressure Transducer - Offset
Offset from zero applied to the pressure sensor
-20 to 20 PSI
-1.38 to 1.38 bar
Coil Outlet Thermistor - Type
Specifies the type of thermistor used
The controller comes with a 10K thermistor
2K
3K
10K (default)
Coil Outlet Thermistor - Offset
Offset from zero applied to the thermistor
-10°F to 10°F
-5.56°C to 5.56°C
Stepper Type - Number of Steps
Specifies the number of steps the stepper
valve has – only applies to SCS-SB
100 to 10,000 steps
Stepper Custom Polarity
Specifies the valve polarity –
only applies if “Custom” is chosen as
the stepper type on the SCS-SB
Unipolar or Bipolar
Stepper Custom Step Rate
Specifies the valve movement rate in steps/
second – only applies if “Custom” is chosen
as the stepper type on the SCS-SB
30 to 400
Refrigerants available to use with the SCS controller:
R-22
R-134a
R-402A
R-404A
R-407A
R-407C
R-410A
R-417A
R-422A
R422D
R-507A
R-744
R-245fa
R-438A
R-401B
R-408A
R-508A
R-508B
R-407F
R-434A
R-444B
R-448A
R-450A
R-449A
R-452A
R-513A
R1336mzz
R-427A
R-422C
Note:
Additional refrigerants may be added over time. If your refrigerant is not listed, a new firmware package with additional refrigerants may be
available. Please contact Sporlan Application Support or your local Sporlan Sales Representative for information.