Owner's Manual:
SMOKEETER® Electronic Air Cleaner
7.6 Ionizer Voltage
Place the probe’s tip on the ionizer (refer to Figure 6)
and measure the positive DC voltage. The voltage
should read 10 to 11 KV DC.
• If measurements are abnormal, refer to the trouble-
shooting table (page 10) for cause and correction.
7.7 Cell Voltage
Place the probe’s tip on one of the charged plates. The
voltage reading should be 4 to 6 KV DC.
• If measurements are abnormal, refer to the trouble-
shooting table (page 10) for cause and correction.
FIGURE 7
7.8 Checking the Power Supply Output
(Refer to Figure 7)
1. Remove the components from the cabinet.
2. Engage the safety interlock switch and measure the
output from the ionizer terminal of the power supply
by placing the probe’s tip on the ionizer high voltage
contact located on inside back wall of cabinet (follow
#8 wire).
3. To measure the collection cell output voltage, place
the probe’s tip on the cell high voltage contact (follow
#7 wire).
• Output without the components should read 5 to 7
KV DC positive.
FIGURE 7
(Contact point locations may vary)
7.9 Checking Lamp Terminal Output
(Refer to Figure 8)
Disconnect unit indicator lamp (neon lamp).
Connect a good neon lamp to supply terminal “light” and
to pack terminal “GND” or cabinet ground. If lamp does
not light, replace power supply. If lamp lights, check
wiring and unit indicator lamp.
FIGURE 8
Summary of Contents for SMOKEETER SE-40
Page 1: ...Owner s Manual Commercial Air Cleaner Smokeeter Models SE 40 Variable Speed SE 50 3 Speed...
Page 6: ...2 Owner s Manual SMOKEETER Electronic Air Cleaner DIMENSIONS SE 40 SE 50...
Page 15: ...11 Owner s Manual SMOKEETER Electronic Air Cleaner 10 0 llustrated Parts SE 40 Final Assembly...
Page 17: ...13 Owner s Manual SMOKEETER Electronic Air Cleaner SE 40 UNICELLULAR ASSEMBLY 02 1321...
Page 21: ...17 Owner s Manual SMOKEETER Electronic Air Cleaner SE 50 FINAL ASSEMBLY...