Panel C
12
13
11
(12) High Ambient Temp Display. Should not be above 100ºF. High ambient
temperature can cause head pressure tripping of refrigeration system and could
result in non-warranty damage to refrigeration compressor. This display is
used for water temperature in water cooled units.
(13) High Inlet Temp Display. Should not be above 100ºF. High inlet air temp
can cause overloading of dryer. If lit, check compressed air after cooler and/or
oil cooler on air compressor.
12
13
14
11
(14) High Coalescer PSID & Light. Pressure drop across coalescer element
should not be above 9 PSIG. Excessive pressure drop could cause mechanical
failure of element resulting in flood of oil, water and contaminants downstream
of dryer. Change element when necessary.
Summary of Contents for SC80
Page 8: ...Section 4 0 Controls REFRIGERANT DRYER CONTROLLER FEATURES AND OPERATIONS 5 1 4 8 10 2 6 3 7 9...
Page 20: ...Section 11 0 MAINTENANCE CHARTS Maintenance Log Date Service Performed Parts Replaced Initials...
Page 21: ...Section 11 0 MAINTENANCE CHARTS cont Element Replacement Log Part No Date Initials...
Page 22: ...Section 12 0 ASSOCIATED DRAWINGS...
Page 23: ......
Page 24: ......
Page 25: ......
Page 26: ......
Page 27: ......
Page 28: ......
Page 29: ......
Page 30: ......
Page 31: ......
Page 32: ......
Page 33: ......
Page 34: ......
Page 35: ......
Page 36: ......
Page 37: ......
Page 39: ......