Parker S8VS Product Bulletin Download Page 12

ISO 9001 CERTIFIED

Safe Operation  (See Bulletin RSBCV)

People doing any work on a refrigeration system must be 
qualified and completely familiar with the system and the 
Refrigerating Specialties Division valves involved, or all other 
precautions will be meaningless. This includes reading and 
understanding pertinent Refrigerating Specialties Division 
Product Bulletins and Safety Bulletin RSB prior to installation 
or servicing work.

Where cold refrigerant liquid lines are used, it is necessary 
that certain precautions be taken to avoid damage which 
could result from liquid expansion. Temperature increase in a 
piping section full of solid liquid will cause high pressure due 
to the expanding liquid which can possibly rupture a gasket, 
pipe or valve. All hand valves isolating such sections should 
be marked, warning against accidental closing, and must not 
be closed until the liquid is removed. Check valves must never 
be installed upstream of solenoid valves, or regulators with 
electric shut-off, nor should hand valves upstream of solenoid 
valves or downstream of check valves be closed until the  
liquid has been removed. 

It is advisable to properly install relief devices in any section 
where liquid expansion could take place.  Avoid all piping 
or control arrangements which might produce thermal or 
pressure shock.

For the protection of people and products, all refrigerant 
must be removed from the section to be worked on before a 
valve, strainer, or other device is opened or removed.  Flanges 
with ODS connections are not suitable for ammonia service.

Warranty

All Refrigerating Specialties products are under warranty 
against defects in workmanship and materials for a period of 
one year from date of shipment from factory. This warranty 
is in force only when products are properly installed, 
field assembled, maintained, and operated in use and 
service as specifically stated in Refrigerating Specialties 
Catalogs or Bulletins for normal refrigeration applications, 
unless otherwise  approved in writing by the Refrigerating  
Specialties Division. Defective products, or parts thereof 
returned to the factory with transportation charges prepaid 

and found to be  defective by factory inspection, will be 
replaced or repaired at Refrigerating Specialties option, free 
of charge, F.O.B. factory. Warranty does not cover products 
which have been altered, or repaired in the field, damaged in 
transit, or have suffered accidents, misuse, or abuse. Products 
disabled by dirt or other foreign substances will not be 
considered defective.

The express warranty set forth above constitutes the only 
warranty applicable to Refrigerating Specialties products, and 
is in lieu of all other  warranties, expressed or implied, written 
including any warranty of merchantability, or fitness for a 
particular purpose. In no event is Refrigerating Specialties 
responsible for any consequential damages of any nature 
whatsoever. No employee, agent, dealer or other person is 
authorized to give any warranties on behalf of Refrigerating 
Specialties, nor to assume, for Refrigerating Specialties, any 
other liability in  connection with any of its products.

© 2018 Parker Hannifin Corporation

314449RSD ECO: 0265766 10/26/2018

Summary of Contents for S8VS

Page 1: ...nates the need to order and install additional components The S8VS valve station is based on the proven S8F solenoid valves RSF strainers and R S hand valves The S8ST solenoid strainer combination val...

Page 2: ...ceeded Conversely low fluid tem peratures permit higher ambient temperatures A solenoid coil should never be energized except when mounted on its corresponding solenoid tube The molded Class F coil is...

Page 3: ...t and valve outlet allows the main valve to be lifted A minimum pressure difference of approximately 1 psi is required for operation Stop Check Expansion Module Position 4 features a isolation valve w...

Page 4: ...3 Nut Packing 303 Stainless Steel 4 Packing Gland PTFE Carbon Filled 5 Packing Style 235A Crane Foil 6 Bonnet Hand Valve Steel Zinc Plated A350 LF2 Class 1 7 Disc Carrier Hand Valve 1117 Stainless St...

Page 5: ...Aluminum 2011 T3 per ASTM B211 2 Stem Hand Valve 303 Stainless Steel 3 Nut Packing 303 Stainless Steel 4 Packing Gland PTFE Carbon Filled 5 Packing Style 235A Crane Foil 6 Bonnet Hand Valve Steel Zin...

Page 6: ...arefully Check the carton to make sure all items are unpacked Save the enclosed instruction for the installer and eventual user Do not remove the protective coverings from the inlet and outlet of the...

Page 7: ...be remedied by replacing the valve seat or by cleaning the seat Valve is installed backwards This can be remedied by removing the valve from the system and reinstalling in the correct orientation Stra...

Page 8: ...tion mm inch Figure 5 S8VS Dimensional Diagram Figure 6 S8ST Dimensional Diagram Bulletin 10 02 8 146 18 5 76 56 41 2 22 164 12 6 46 117 30 4 62 234 95 9 25 Clearance Zone 152 40 6 00 164 12 6 46 112...

Page 9: ...T Butt Weld BW ANSI Port Size Connection T OD mm inch mm inch mm inch 15 1 2 1 2 3 9 0 152 21 6 0 850 3 4 4 0 0 159 26 9 1 060 BW Butt Weld ANSI OD T Butt Weld BW Metric Port Size Connection T OD mm...

Page 10: ...embly Gasket Solenoid Plunger Kit AC Coil DC Coil 201019 201021 6 7 8 Gasket Solenoid Piston Seat Piston Seat Kit 210562 6 10 Gasket Solenoid Tube Assembly Gasket Kit 209322 9 10 Seal Cap Gasket Seal...

Page 11: ...ube Kit Standard DN 209320 209321 5 6 Plunger Needle Assembly Gasket Solenoid Plunger Kit AC Coil DC Coil 201019 201021 6 7 8 Gasket Solenoid Piston Seat Piston Seat Kit 210562 6 10 Gasket Solenoid Tu...

Page 12: ...langes with ODS connections are not suitable for ammonia service Warranty All Refrigerating Specialties products are under warranty against defects in workmanship and materials for a period of one yea...