part number V150LA20A for 120 VAC input and part number 

V275LA20A for 208/240 VAC input.

NOTE:

  Sensor  and  valve  wires  may  be  extended  for  remote  appli-

cations.  Waterproof  butt  connectors  should  be  used,  and  the  cable 

should be at least 16 gauge. Care must be taken to ensure a good splice 

and  that  the  individual  wires  are  correctly  identified.  For  remote 

installation where the sensors are located more than 25 ft. from the 

controller, contact Sporlan Division of Parker for guidance.

 

OPERATION

When first powered up the numeric display will show actual superheat 

for Circuit 1.

1.

   The controller may be toggled between settings for Circuit 1 and 2 

by pressing PB1 (left button).

2.

   When Circuit 1 is being displayed, the small Green LED will be lit.

3.

   When Circuit 2 is being displayed, the small Red LED will be lit.

4.

   If Circuit 2 is not being used its display and setting will show “00”.

5.

   PB2 will toggle the readings as follows and the small Green LED 

will be steady or flash:

    • Actual Superheat, LED constant.

    • Valve percentage open, LED slow flash.

6.

   To change superheat set point for Valve 1:

    • Make sure the display shows the superheat of Valve 1.

    • Press and hold PB1 and PB2 for 8 seconds, LED will flash rapidly.

    • Use PB1 to increment set point.

    • Use PB2 to decrement set point.

    • Press and hold PB1 and PB2 for 5 seconds to lock in set point and  

  return to actual superheat.

    • To set superheat for Valve 2 toggle PB1 to Valve 2 superheat and  

  repeat above.

7.

   To manually change valve position:

    • Scroll to valve position reading with PB2.

    • Press and hold PB1 and PB2 simultaneously for 8 seconds, Green  

  LED will flash rapidly.

    • Increment “valve open” percentage by pressing PB1 for 1 second.

    • Decrement “valve open” percentage by pressing PB2 for 1 second.

      Valve will maintain manual open position for 1 hour or until PB1  

  and PB2 are pressed simultaneously and held for 5 seconds.

 

REMOTE PANEL DISPLAY

A remote panel display is available that will allow access to all the param-

eters of the controller. The Remote Panel Display can be used as a set 

point tool in production, a diagnostic tool in the field or as a permanent 

readout device for the controller. A five-foot cable is included.

Plug the remote display into the telephone jack (J9) on the controller. The 

following is a list of readings available:

SUP1

  Superheat read by controller for AC circuit 1

POS1

  Number of steps valve is open (0-6386) for AC circuit 1

PRS1

  Pressure read by the transducer (0-153 psi gauge) for AC 

circuit 1

TMP1

  Temperature read by the temperature sensor (-50 to 103°F) for 

AC circuit 1

TST1

  Saturated temperature for AC circuit 1

AC1, PDN1
 

AC1 when in normal operation

PDN1 

when in pumpdown for AC circuit 1

R22, 134A, 407C, 404A, 507
 

R22 for refrigerant R-22, 134A for refrigerant R-134a, 407C 

for refrigerant R-407C, and 404A for refrigerant R-404A and 

R507 for refrigerant R-507. 

Note: 

Not all controllers have 

both R-507 and R-407C.

LGE1, SML1, MED1, ESX1, S251

 

LGE1 if the EEV used is an SEI-50 or larger for AC circuit 1. 

 

SML1 if the EEV used is smaller than an SEI-25 for AC circuit 1. 

 

MED1 if the EEV used is a SEI-25 for AC circuit 1. 

 

ESX1 if the EEV used is a ESX for AC circuit 1.

 

S251 if the EEV is an SER 1.5 to 20.

SSP1

  Superheat set point (0 to 16°F) for AC circuit 1. Default is 10°F.

MOP1

  Maximum operating suction pressure set point (0 to 153 PSI) 

for AC circuit 1. Default is 153 PSI.

CTS1

  Cut out suction pressure set point for AC circuit 1 (0 to 153 PSI)

CLP1

  Calibrate pressure transducer for AC circuit 1.

CLT1

  Calibrate temperature sensor for AC circuit 1.

PRO1

  Proportional gain set point for AC circuit 1. Number of steps per 

degree that superheat is above or below the superheat set point 

(5 to 255 steps per degree). Default is 45 for LGE1 setting, 22 

for MED1 setting, and 11 for SML1 setting.

INT1

 

Integral set point for AC circuit 1. Number of seconds the con-

troller waits to update the reference valve position. (1 to 120 

seconds). Default is 10 seconds.

DER1

  Derivative setpoint for valve 1. Advanced algorithm parameter 

that determines the slope of the change control point. Default is 

zero.

DON1

  Time delay in seconds between end of pumpdown and compres-

sor start when Relay 2 is used to pilot the compressor contactor. 

The pre-opens the valve before compressor start to avoid nui-

sance low pressure safety trips. 2 seconds.

DOF1

   Time in seconds that the valve is shut before the compressor 

Relay 2 opens to stop the compressor. Allows refrigerant pump-

down/pumpout. Default is 2 seconds.

DST1

   Used with DON1. Number of steps to pre-open the valve before 

compressor start. Default varies with valve size.

CONTROLLER MENUS

ENTER

  will toggle display between one of the displays described above 

and the numeric value read for that particular display.

UP

   

will scroll through the menu from SUP1 to POS1, etc.

DOWN

  will scroll through the menu the opposite way.

POS1 MODE

Press and hold the 

UP

 button and 

ENTER

 button simultaneously for 5 

seconds  to  put  the  controller  in  manual  valve  position.  The  number  of 

steps open will be displayed and the 1000’s digit will blink.
Pressing the 

UP

 button will open the valve 1000 steps.

Pressing the 

DOWN

 button will close the valve 1000 steps.

Pressing the 

ENTER

 button will change the flashing digit from 1000’s 

digit to the 100’s digit.

Page 2