Parker EME
PSUP Connections
192-120147N9 PSUP Manual 2019-06
21
Mains connection PSUP10D6
Device type PSUP10
230V
400V
480V
Supply voltage
230VAC ±10%
50-60Hz
400VAC ±10%
50-60Hz
480VAC ±10%
50-60Hz
Rated voltage
3AC 230V
3AC 400V
3AC 480V
Input current
22Arms
22Arms
18Arms
Output Voltage
325VDC ±10%
565VDC ±10%
680VDC ±10%
Output power
6kW
10 kW
10 kW
Pulse power (<5s)
12kW
20kW
20kW
Heat dissipation
60W
60W
60W
Maximum fuse rating per
device
Measure for line and device protection:
MCB miniature circuit breaker (K characteristic) 25A in
accordance with UL category DIVQ
Recommendation: (ABB) S203UP-K25 (480VAC)
Mains connection PSUP20D6
Device type PSUP20
230V
400V
480V
Supply voltage
230VAC ±10%
50-60Hz
400VAC ±10%
50-60Hz
480VAC ±10%
50-60Hz
Rated voltage
3AC 230V
3AC 400V
3AC 480V
Input current
44Arms
44Arms
35Arms
Output Voltage
325VDC ±10%
565VDC ±10%
680VDC ±10%
Output power
12kW
20kW
20kW
Pulse power (<5s)
24kW
40kW
40kW
Heat dissipation
120W
120W
120W
Maximum fuse rating per
device
2 special purpose fuses in
line are required
Cable protection measure:
MCB (K characteristic) with a rating of 50A / 4xxVAC
(depending on the input voltage)
Recommendation: (ABB) S203U-K50 (440VAC)
Device protection measure:
Circuit breakers 80A / 700VAC per supply leg in
accordance with UL category JFHR2
Requirement: Bussmann 170M1366 or 170M1566D
PSUP30D6 Mains connection
Device type PSUP30
230V
400V
480V
Supply voltage
230VAC ±10%
50-60Hz
400VAC ±10%
50-60Hz
480VAC ±10%
50-60Hz
Rated voltage
3AC 230V
3AC 400V
3AC 480V
Input current
50Arms
50Arms
42Arms
Output Voltage
325VDC ±10%
565VDC ±10%
680VDC ±10%
Output power
17kW
30kW
30kW
Pulse power (<5s)
34kW
60kW
60kW
Heat dissipation
140W
140W
140W
Maximum fuse rating per
device
2 special purpose fuses in
line are required
Cable protection measure:
MCB (K characteristic) with a rating of 63A / 4xxVAC
(depending on the input voltage)
Recommendation: (ABB) S203U-K63 (440VAC)
Device protection measure:
Circuit breakers 125A / 700VAC per supply leg in
accordance with UL category JFHR2
Requirement: Bussmann 170M1368 or 170M1568D
Only three-phase operation of the PSUP devices is permitted!
The PSUP30 mains module may only be operated with mains filter
Required mains filter for the PSUP30:
0.45 mH / 55 A
We offer the following mains filters:
LCG-0055-0.45 mH (WxDxH: 180 mm x 140 mm x 157 mm; 10 kg)
LCG-0055-0.45 mH-UL (with UL approval) (WxDxH: 180 mm x 170 mm x 157 mm; 15 kg)
Caution!