Introduction
PSUP Mains module
10
192-120147N9 PSUP Manual 2019-06
1.6
Conditions of utilization for CE-conform operation
- Industry and trade -
The EC guidelines for electromagnetic compatibility
2014/30/EU
and for electrical
operating devices for utilization within certain voltage limits
2014/35/EU
are fulfilled
when the following boundary conditions are observed:
Operation of devices only in the state in which they are delivered.
A mains filter is required in the mains input line if the motor cable exceeds a certain
length. Filtering can be provided centrally at the system mains input or separately
for each axis system.
The following mains filters are available for independent utilization:
Use of the devices in the industrial area (limit values class C3 in accordance
with EN 61800-3)
Device: PSU
Limit value
class
Reference: Axis system
with motor cable
Mains filter
Order No.:
P10
C3
< 6 x 10 m
NFI03/01
P10
C3
< 6 x 50 m
NFI03/02
P20
C3
< 6 x 50 m
NFI03/03
P30
C3
< 6 x 50 m
NFI03/03
unshielded:
Connection length: Connection between mains filter and device:
< 0.5 m
shielded
< 5 (fully shielded on ground - e.g. ground of control cabinet)
Connect the filter housing and the device to the cabinet frame, making sure that the
contact area is adequate and that the connection has low resistance and low
inductance.
Never mount the filter housing and the device on paint-coated surfaces!
Signal lines and power lines should be installed as far apart as possible.
Signal lines should never pass close to excessive sources of interference
(motors, transformers, contactors etc.).
Do not place mains filter output cable parallel to the load cable.
Make sure to use only the accessories recommended by Parker
Connect all cable shields at both ends, ensuring large contact areas!
This is a product in the restricted sales distribution class according to EN 61800-3.
In a domestic area this product can cause radio frequency disturbance, in which
case the user may be required to implement appropriate remedial measures.
Mains filter:
Grounding:
Cable installation:
Accessories:
Warning: