Parker PSSTACM12A Installation & Service Instructions Manual Download Page 8

isysNet 24 VDC Analog Output Modules, Series A (PSSTACM12A, PSSTAVM12A) 

E111P

8

Analog Output Modules

Outputs per Module 

2 single ended, nonisolated

Output Voltage 

PSSTAVM12A 

 

0V output until communication established 

 

0-10V (user configurable) (0.0V under, +5V over) 

 

±10V (user configurable) (-0.5V under, +5V over)

Output Current 

0 mA output until communication established 

 

4-20 mA user configurable 

 

0-20 mA user configurable

Resolution 

PSSTACM12A 

 

13 bits - over 0-21 mA 

 

2.5µA/cnt (average value - typical range: 2.3-2.7µA/cnt) 

 

PSSTAVM12A 

 

14 bits (13 plus sign) 

 

1.28µV/cnt in unipolar or bipolar mode

Absolute Accuracy

1

 

0.1% Full Scale @ 25°C

Accuracy Drift w/Temp. 

PSSTACM12A - 30ppm/°C 

 

PSSTAVM12A - 5ppm/°C

Resistive Load on mA Output 

PSSTACM12A - 0-750k

Current Load on Output, Maximum 

PSSTAVM12A - 3 mA

Conversion Type 

Digital to analog converter

Conversion Rate 

PSSTACM12A - 16µs 

 

PSSTAVM12A - 20µs

Data Format 

Signed integer

General Specifications

Calibration 

Factory calibrated

Step Response to 63% of FS 

24µs

Indicators 

1 green/red module status indicator, logic side 

 

1 green/red network status indicator, logic side 

 

2 green/red output status indicators, logic side

Keyswitch Position 

4

PointBus Current 

75 mA @ 5VDC

Power Dissipation - Maximum at 28.8VDC 

PSSTACM12A 

 

750

 load on each output - 1.23W 

 

0

 load on each output - 1.83W 

 

PSSTAVM12A 

 

1.0W

Thermal Dissipation - Maximum at 28.8VDC 

PSSTACM12A 

 

750

 load on each output - 4.19 BTU/hr. 

 

0

 load on each output - 6.24 BTU/hr. 

 

PSSTAVM12A 

 

3.4 BTU/hr.

Isolation Voltage 

50V rms 

(continuous voltage withstand rating) 

Tested at 1250VAC rms for 60s

External DC Power 

  Supply Voltage 

24VDC nominal 

  Voltage Range 

10-28.8VDC 

  Supply Current 

PSSTACM12A:  70 mA @ 24VDC (including outputs @ 20 mA) 

   

PSSTAVM12A:  35 mA @ 24VDC (including outputs @ 3 mA)

Dimensions 

Imperial (Metric)  1.25H x 2.63W x 4.25D (31.75H x 66.80W x 107.95D)

Operating Temperature 

IEC 60068-2-1 (Test Ad, Operating Cold), 

 

IEC 60068-2-2 (Test Bd, Operating Dry Heat), 

 

IEC 60068-2-14 (Test Nb, Operating Thermal Shock): 

 

-20 to 60°C (-4 to 140°F)

Storage Temperature 

IEC 60068-2-1 (Test Ab, Un-packaged Non-operating Cold), 

 

IEC 60068-2-2 (Test Bb, Un-packaged Non-operating Dry Heat), 

 

-40 to 85°C (-40 to 185°F)

Relative Humidity 

IEC 60068-2-30 (Test Db, Un-packaged Non-operating Damp Heat): 

 

5 to 95% non-condensing

Shock 

IEC60068-2-27 (Test Ea, Unpackaged Shock):  Operating 30g, Non-operating 50g

Vibration 

IEC60068-2-6 (Test Fc, Operating):  5g @ 10 to 500Hz

ESD Immunity 

IEC 61000-4-2: 

 

6kV contact discharges 

 

8kV air discharges

Radiated RF Immunity 

IEC 61000-4-3: 

 

10V/m with 1kHz sine-wave 80%AM from 30MHz to 2000MHz 

 

10V/m with 200Hz 50% Pulse 100%AM at 900Mhz 

 

10V/m with 200Hz 50% Pulse 100%AM at 1890Mhz

EFT/B Immunity 

IEC 61000-4-4:  ±3kV at 5kHz on signal ports

Surge Transient Immunity 

IEC 61000-4-5:  ±2kV line-earth(CM) on shielded ports

Conducted RF Immunity 

IEC 61000-4-6:  10Vrms with 1kHz sine-wave 80%AM from 150kHz to 80MHz

Emissions 

CSPR 11:  Group 1, Class A

Enclosure Type Rating 

Meets IP65/66/67 (when marked)

Mounting Base Screw Torque 

#8 screw, 7.5 in. lbs. in Aluminum, 16 in. lbs. in Steel

Wiring Category

2

 

1 - on signal ports

Weight 

Imperial (Metric)  0.637 lb. (0.289 kg)

Certifications: (when product is marked) 

c-UL-us 

UL Listed Industrial Control Equipment, certified for US and Canada

 

CE

 

European Union 89/336/EEC EMC Directive, compliant with: 

 

 

EN 61000-6-4; Industrial Emissions 

 

 

EN 50082-2; Industrial Immunity 

 

 

EN 61326; Meas./Control/Lab., Industrial Requirements 

 

 

EN 61000-6-2; Industrial Immunity

 

C- Tick 

Australian Radiocommunications Act, compliant with: 

 

 

AS/NZS CISPR 11; Industrial Emissions

  1. Includes offset, gain, non-linearity and repeatability error terms.
  2. Use this Conductor Category information for planning conductor routing. Refer to Publication E115P, “Industrial Automation Wiring and Grounding Guidelines”.

Specifications

 - 

Following are specifications for the PSSTACM12A and PSSTAVM12A analog output modules.

Summary of Contents for PSSTACM12A

Page 1: ...nal selection of the products and systems and assuring that all performance safety and warning requirements of the application are met The products described herein including without limitation produc...

Page 2: ...onomic loss Attentions help you Identify a Hazard Avoid a Hazard Recognize the Consequence SHOCK HAZARD Labels may be located on or inside the equipment to alert people that dangerous voltage may be p...

Page 3: ...hown above in the drilling dimension drawing 2 Drill the necessary holes for 8 M4 machine or self tapping screws 3 Mount the base using 8 M4 screws 4 Ground the system using the ground lug connection...

Page 4: ...bases 3 Push the module down until it engages the latching mechanism You will hear a clicking sound when the module is properly engaged The locking mechanism will lock the module to the base Remove th...

Page 5: ...d into the processor s memory These I O analog output modules produce 2 bytes of input data scanner Rx fault status They consume 4 bytes of output data scanner Tx Default Data Map for the Analog Outpu...

Page 6: ...OK Notice that the PSSTACM12A is now under the I O configuration Add Analog Output Modules to RSLogix 5000 I O Configuration To add your analog output modules to RSLogix 5000 I O configuration follow...

Page 7: ...Flashing Red Recoverable fault Red Unrecoverable fault may require device replacement Flashing Red Green Device is in self test Indication Probable Cause Network Status Off Device is not on line Devic...

Page 8: ...ing Temperature IEC 60068 2 1 Test Ad Operating Cold IEC 60068 2 2 Test Bd Operating Dry Heat IEC 60068 2 14 Test Nb Operating Thermal Shock 20 to 60 C 4 to 140 F Storage Temperature IEC 60068 2 1 Tes...

Reviews: