If your RSLogic 5000 is Version 13.X:

   • Choose the equivalent Rockwell Automation module from the list 

of modules.

   

Equivalent Rockwell Automation 

  isysNet Modules 

1738 ArmorPoint Modules

  PSSTACM12A 

1738-OE2CM12

  PSSTAVM12A 

1738-OE2VM12

  • Enter a name (optional), slot number, and comm. format. Make 

sure  to  choose 

Compatible  Module  for  Electronic  Keying 

setting.

  • Choose 

Next

 to set 

RPI.

  • Choose 

Finish

.    Notice  that  the  analog  output  module  is  now 

under the I/O configuration

MOD

NET

PSSTACM12A

Analog Current Out

0

1

0

1

PSSTACM12A

I/O Status Indicators

Module Status Indicator
Network Status Indicator

isysNet 24 VDC Analog Output Modules, Series A (PSSTACM12A, PSSTAVM12A) 

E111P

7

Troubleshoot With the Indicators

Indication 

Probable Cause

Module Status

Off 

No power applied to device

Green 

Device operating normally

Flashing Green 

Device needs commissioning due to 

 

missing, incomplete, or incorrect 

 

configuration

Flashing Red 

Recoverable fault

Red 

Unrecoverable fault -  

 

may require device replacement

Flashing Red/Green 

Device is in self-test

Indication 

Probable Cause

Network Status

Off 

Device is not on line: 

 

-  Device has not completed  

 

  dup_MAC-id test. 

 

-  Device not powered - check module  

 

  status indicator.

Flashing Green 

Device is on line but has no  

 

connections in the established state.

Green 

Device is on line and has  

 

connections in the established state.

Flashing Red 

One or more I/O connections in  

 

timed-out state.

Red 

Critical link failure - failed  

 

communication device. Device  

 

detected error that prevents it from  

 

communicating on the network.

Flashing Red/Green 

Communication faulted device - the  

 

device has detected a network access  

 

error and is in communication faulted  

 

state. Device has received and accepted  

 

an Identity Communication Faulted  

 

Request - long protocol message.

Indication 

Probable Cause

I/O Status 

PSSTAVM12A 

PSSTACM12A

Off 

Module in CAL mode

Solid Green 

Device operating normally

Flashing Green 

Channel being calibrated

Flashing Red 

Low or High Clamp 

Open wire or no power

Solid Red 

No power 

Not used

Summary of Contents for PSSTACM12A

Page 1: ...nal selection of the products and systems and assuring that all performance safety and warning requirements of the application are met The products described herein including without limitation produc...

Page 2: ...onomic loss Attentions help you Identify a Hazard Avoid a Hazard Recognize the Consequence SHOCK HAZARD Labels may be located on or inside the equipment to alert people that dangerous voltage may be p...

Page 3: ...hown above in the drilling dimension drawing 2 Drill the necessary holes for 8 M4 machine or self tapping screws 3 Mount the base using 8 M4 screws 4 Ground the system using the ground lug connection...

Page 4: ...bases 3 Push the module down until it engages the latching mechanism You will hear a clicking sound when the module is properly engaged The locking mechanism will lock the module to the base Remove th...

Page 5: ...d into the processor s memory These I O analog output modules produce 2 bytes of input data scanner Rx fault status They consume 4 bytes of output data scanner Tx Default Data Map for the Analog Outpu...

Page 6: ...OK Notice that the PSSTACM12A is now under the I O configuration Add Analog Output Modules to RSLogix 5000 I O Configuration To add your analog output modules to RSLogix 5000 I O configuration follow...

Page 7: ...Flashing Red Recoverable fault Red Unrecoverable fault may require device replacement Flashing Red Green Device is in self test Indication Probable Cause Network Status Off Device is not on line Devic...

Page 8: ...ing Temperature IEC 60068 2 1 Test Ad Operating Cold IEC 60068 2 2 Test Bd Operating Dry Heat IEC 60068 2 14 Test Nb Operating Thermal Shock 20 to 60 C 4 to 140 F Storage Temperature IEC 60068 2 1 Tes...

Reviews: