background image

isysNet 24 VDC Output Modules, Series A 

E107P

7

Troubleshoot With the Indicators

MOD

NET 

PSST8M12A
24V  dc   Out

0

1

2

3

4

5

6

7

0

1

2

3

4

5

6

7

PSST8M12A

I/O Status Indicators

Module Status Indicator
Network Status Indicator

Indication  

Probable Cause 

Network Status 
Off  

Device is not on line: 

 

-  Device has not completed  

 

  dup_MAC-id test. 

 

-  Device not powered - check module  

 

  status indicator. 

Flashing Green  

Device is on line but has no  

 

connections in the established state. 

Green  

Device is on line and has  

 

connections in the established state. 

Flashing Red  

One or more I/O connections in  

 

timed-out state. 

Red  

Critical link failure - failed  

 

communication device. Device  

 

detected error that prevents it from  

 

communicating on the network. 

Flashing Red/Green   Communication faulted device - the  

 

device has detected a network access  

 

error and is in communication faulted  

 

state. Device has received and accepted  

 

an Identity Communication Faulted  

 

Request - long protocol message.

Indication  

Probable Cause 

I/O Status 
Off  

Output is inactive 

Yellow  

Output is active and under control 

Flashing Red  

Open circuit detection. No load.  

 

(Off-State only) 

Red  

Short circuit detected. (On-State only)

Indication  

Probable Cause 

Module Status 
Off  

No power applied to device 

Green  

Device operating normally 

Flashing Green  

Device needs commissioning due to 

 

missing, incomplete, or incorrect 

 

configuration 

Flashing Red  

Recoverable fault 

Red  

Unrecoverable fault -  

 

may require device replacement 

Flashing Red/Green   Device is in self-test

If your RSLogic 5000 is Version 13.X:

  • Choose the equivalent Rockwell Automation module from the list 

of modules.

isysNet Modules

Equivalent Rockwell Automation

1738 ArmorPoint Modules

PSST8M8A

1738-OB8EM8

PSST8M12A

1738-OB8EM12

PSST8M23A

1738-OB8EM23*

* 1738-OB8EM23 profile will be available in RSLogix 5000 v15.
   To use 1738-OB8EM23 in RSLogix 5000 v13, choose 

1738-OB8EM12 profile and disable keying.

  • Enter a name (optional), slot number, and communication format. 

Make sure to choose 

Compatible Module for Electronic Keying

 

setting.

  • Choose 

Next

 to set 

RPI.

  • Choose 

Finish

.  Notice that the output module is now under the  

I/O configuration

isysNet Modules

Equivalent Rockwell Automation

1738 ArmorPoint Modules

PSST16M23A

1738-OB16E19M23

PSST16D25A

1738-OB16E25DS

PSST16M12A

1738-OB16EM12

Summary of Contents for PSST16M12A

Page 1: ...ct or systems in the current product catalog Due to the variety of operating conditions and applications for these products or systems the user through its own analysis and testing is solely responsib...

Page 2: ...n not in use store the equipment in appropriate static safe packaging ATTENTION Environment and Enclosure This equipment is intended for use in overvoltage Category II applications as defined in IEC p...

Page 3: ...60 7 3 02 76 6 3 13 79 4 5 98 151 9 0 87 22 Drill and Tap for M6 Screw Ground Lug Connection Latching Mechanism Mounting Base Keyswitch Set to position 1 for the PSST8M digital output modules Install...

Page 4: ...PSST8M12A 24V dc Out 0 1 2 3 4 5 6 7 Module Will Bridge Two Bases Wire the Output Modules Following are wiring instructions for the digital output modules view into connector Pin 1 Output 0 Pin 7 Out...

Page 5: ...2 Output Output 24VDC 500mA 3 Channel 4 Output Output 24VDC 500mA 4 Channel 6 Output Output 24VDC 500mA 5 Channel 8 Output Output 24VDC 500mA 6 Channel 10 Output Output 24VDC 500mA 7 Channel 12 Output...

Page 6: ...hat the PSST8M12A is now under the I O configuration Add 24 VDC Output Modules to RSLogix 5000 I O Configuration To add your output modules to RSLogix 5000 I O configuration follow these steps In RSLo...

Page 7: ...active and under control Flashing Red Open circuit detection No load Off State only Red Short circuit detected On State only Indication Probable Cause Module Status Off No power applied to device Gree...

Page 8: ...IEC 60068 2 2 Test Bb Un packaged Non operating Dry Heat 40 to 85 C 40 to 185 F Relative Humidity IEC 60068 2 30 Test Db Un packaged Non operating Damp Heat 5 to 95 Non condensing Shock IEC60068 2 27...