Parker PSSSE24A Installation & Service Instructions Manual Download Page 3

Isysnet 24VDC Expansion Power Supply, Series A (PSSSE24A) 

E105P

3

Inches

(mm)

Adapter

2.0

(50)

2.0

(50)

1.9

(47.2)

4.02

(102)

1.81

(46)

4.32

(109.8)

5.39

(137.0)

Drill and Tap

for M4 Screw

2.39

(60.7)

3.02

(76.6)

3.13

(79.4)

5.98*

(151.9)

0.87

(22)

Drill and Tap

for M6 Screw

Mount the I/O Base

To  mount  the  I/O  base  on  a  wall  or  panel,  use  the  screw  holes 
provided in the base.

  IMPORTANT

The I/O module must be mounted on a grounded metal mounting 
plate or other conductive surface.

A mounting illustration for the base with an adapter is shown below.

Ground Lug
Connection

Latching Mechanism

Mounting Base
  Keyswitch-
  Set to position 1
  for the PSSSE24A
  dc expansion
  power supply

Install the Mounting Base as Follows:
  1. Lay  out  the  required  points  as  shown  above  in  the  drilling 

dimension drawing.

  2. Drill  the  necessary  holes  for  #8  (M4)  machine  or  self-tapping 

screws.

  3. Mount the base using #8 (M4) screws.
  4. Ground the system using the ground lug connection.  (The ground 

lug connection is also a mounting hole.)

* Depending on the type and number of manifolds, this dimension 

may vary.  Refer to Catalog 0600P-# for additional information.