background image

isysNet 24 VDC Input Modules, Series A (PSSN8M8A, PSSN8M12A, PSSN8M23A,PSSP8M8A, PSSP8M12A, PSSP8M23A)  E106P

8

Digital Input Modules

Inputs per Module

PSSN8M - 8 (1 group of 8) nonisolated, sinking
PSSP8M - 8 (1 group of 8) nonisolated, sourcing

Voltage, Off-State Input, Maximum

5VDC 

Voltage, On-State Input,
  Maximum
  Minimum
  Nominal

28.8VDC
10VDC
24VDC

Current, Off-State Input, Maximum

1.5 mA

Current, On-State Input,
  Maximum
  Minimum
  Nominal

5 mA
2 mA
4 mA @ 24VDC

Input Impedance,
  Maximum
  Nominal

4.7 k

3.6 k

Input Delay Time OFF to ON

0.5 ms ha (0-63 ms selectable

1

)

Input Delay Time, ON to OFF

0.5 ms ha (0-63 ms selectable

1

)

Input Point Density

2, 4, or 8

Field Power Bus Supply
  Voltage Range
  Nominal

10 to 28.8VDC
24VDC

Keyswitch Position

1

LED Indicators

2, 4, or 8 yellow input status, logic side
1 green/red network status, logic side
1 green/red module status, logic side

PointBus Current, Maximum

75 mA @ 5VDC

Power Dissipation, Maximum

PSSN8M - 1.6W @ 28.8VDC 

Thermal Dissipation, Maximum

PSSN8M - 5.5 BTU/hr. @ 28.8VDC

Isolation Voltage
(continuous-voltage withstand rating)

50V rms
Tested at 1250VAC rms for 60s

Dimensions 

Imperial (Metric) 1.25H x 2.63W x 4.25D (31.75H x 66.80W x 107.95D)

Operating Temperature

IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
-20 to 60°C (-4 to 140°F)

Storage Temperature

IEC 60068-2-1 (Test Ab, Un-packaged Non-operating Cold),
IEC 60068-2-2 (Test Bb, Un-packaged Non-operating Dry Heat),
-40 to 85°C (-40 to 185°F)

Relative Humidity

IEC 60068-2-30 (Test Db, Un-packaged Non-operating Damp Heat):  5 to 95% non-condensing

Shock

IEC60068-2-27 (Test Ea, Unpackaged Shock):
Operating 30g
Non-operating 50g

Vibration

IEC60068-2-6 (Test Fc, Operating):  5g @ 10 to 500Hz

ESD Immunity

IEC 61000-4-2:
6kV contact discharges
8kV air discharges

Radiated RF Immunity

IEC 61000-4-3:
10V/m with 1kHz sine-wave 80%AM from 30MHz to 2000MHz
10V/m with 200Hz 50% Pulse 100%AM at 900Mhz
10V/m with 200Hz 50% Pulse 100%AM at 1890Mhz

EFT/B Immunity

IEC 61000-4-4:  ±3kV at 5kHz on signal ports

Surge Transient Immunity

IEC 61000-4-5:  ±1kV line-line(DM) and ±2kV line-earth(CM) on signal ports

Conducted RF Immunity

IEC 61000-4-6:  10Vrms with 1kHz sine-wave 80%AM from 150kHz to 80MHz

Emissions

CSPR 11:  Group 1, Class A

Enclosure Type Rating

Meets IP65/66/67 (when marked)

Mounting Base Screw Torque

#8 screw, 7.5 in. lbs. in Aluminum, 16 in. lbs. in Steel

Weight 

Imperial (Metric) 0.64 lb. (0.29 kg)

Wiring Category

2

1 - on signal ports

Certifications:
(when product is marked)

c-UL-us  UL Listed Industrial Control Equipment,  

certified for US and Canada

CE

 

European Union 89/336/EEC EMC Directive, compliant with: 
EN 61000-6-4; Industrial Emissions 
EN 50082-2; Industrial Immunity 
EN 61326; Meas./Control/Lab., Industrial Requirements 
EN 61000-6-2; Industrial Immunity

C- Tick  Australian Radiocommunications Act, compliant with:  

AS/NZS CISPR 11; Industrial Emissions

  1. Input OFF to ON or ON to OFF delay is time from a valid input signal to recognition by the module.
  2. Use this Conductor Category information for planning conductor routing. Refer to Publication E115P, “Industrial Automation Wiring and Grounding Guidelines”.

Specifications

 - 

Following are specifications for the digital input modules.

Summary of Contents for PSSN8M12A

Page 1: ...8M23A PSSP8M8A PSSP8M12A PSSP8M23A ISSUED December 2006 Supersedes January 2006 Doc E106P EN 060961 Rev 3 WARNING To avoid unpredictable system behavior that can cause personal injury and property dam...

Page 2: ...y damage or economic loss Attentions help you Identify a Hazard Avoid a Hazard Recognize the Consequence SHOCK HAZARD Labels may be located on or inside the equipment to alert people that dangerous vo...

Page 3: ...0 Drill and Tap for M4 Screw 2 39 60 7 3 02 76 6 3 13 79 4 5 98 151 9 0 87 22 Drill and Tap for M6 Screw Ground Lug Connection Latching Mechanism Mounting Base Keyswitch Set to position 1 for the Isy...

Page 4: ...ge two bases 3 Push the module down until it engages the latching mechanism You will hear a clicking sound when the module is properly engaged The locking mechanism will lock the module to the base Re...

Page 5: ...eturn Com Pin 5 Input 4 Pin 11 24VDC Pin 6 Input 5 Pin 12 Chassis 8 5 4 11 3 2 10 12 6 1 9 7 PSSN8M23A PSSP8M23A Sink Input modules PSSN8 require PNP type input device Source Input modules PSSP8 requi...

Page 6: ...d received from produced the I O modules These messages are mapped into the processor s memory These I O input modules produce 1 byte of input data scanner Rx status They do not consume I O data scann...

Page 7: ...Automation module from the list of modules isysNet Modules Equivalent Rockwell Automation 1738 ArmorPoint Modules PSSN8M8A 1738 IB8M8 PSSN8M12A 1738 IB8M12 PSSN8M23A 1738 IB8M23 PSSP8M8A 1738 IV8M8 P...

Page 8: ...Humidity IEC 60068 2 30 Test Db Un packaged Non operating Damp Heat 5 to 95 non condensing Shock IEC60068 2 27 Test Ea Unpackaged Shock Operating 30g Non operating 50g Vibration IEC60068 2 6 Test Fc...

Reviews: