7
CONFIGURATION
7.1
Unit of measurements
Units of measurement used in the internal algorithm are Celsius (ºC) and Kelvin (K) degrees in tenths for
temperatures, and barG in hundreds for pressure.
For the convenience of the user, it is possible to set temperature and pressure parameters in the preferred unit to be
measured, specify the unit value in the parameter Pressure unit of measurement (Ph60) and Temperature unit of
measurement (Ph61) sets the value.
These parameters are acquired only during Initialization (0) phase at the reset , which means that any changes to
these parameters will take effect after a reset.
Setting of the Ph60 and Ph61 parameters affects:
-
the limits of certain parameters
-
the measurement read from state variables
-
the temperature and pressure parameters
The modification of any of the measurement units will trigger the automatic conversion of existing temperature and
pressure parameters: the automatic conversion of all the pressure and temperature parameters is performed in the
Initialization (0) at start-up, and then a board reset is needed, after unit of measure has been changed.
The correct procedure should be performed in this order:
-
disable the valve
-
change parameters Ph60 and/or Ph61
- reset
the
board
-
check Parameters alarm bit in the Alarm status (AlSt)
-
if parameters alarm is active, check and correct all the parameters of temperature and pressure,
cancel the alarm leading to 1 bit 0 of the variable Command (Cmd), and then reset the
PSD04
-
if parameter alarm is cleared check ParS variable and if necessary, reset the board again.
It is recommended not to abuse the automatic conversion of the parameters: is a sensitive function as its disruption
can lead to the invalidation of all the memory parameters.
In addition, repetitive conversions lead to a subsequent loss of precision in the values.
The Internal unit of measure (UdM) indicates which units of measurements are actually used, since the parameters
Ph60 and Ph61 may have been changed. After the reset and the automatic conversion the Internal unit of measure
(UdM) mirrors the parameters.
Given that, as stated earlier, the internal algorithm work in Kelvin, Celsius and BarA, if the units of measurement
chosen match these, no conversions are performed. If the user's units of measurements are in Fahrenheit and / or Psi,
the following conversions are applied:
Param. in °F/R/Psi
→
val. in °C/K/Bar
→
algorithm
→
val. out °C/K/Bar
→
var. out °F/R/Psi.
7.2
Configuring a built-in display version
To gain access to the user menu:
1.
Make sure the power supply is switched on.
2.
Move through the pages using the buttons as shown in the example here below:
to the installer menu
page
1
or
or
to select “
Alarm status
” and