Programming Information
P31P / P32P Series
Electronic Proportional Regulators
Set Proportional Band
Proportional band is used for setting the reaction sensitivity of the regulator. The displayed value is X 10 mbar and has a range between 50
(0.5 bar) and 250 (2.5 bar).
Fine Settings
or
or
Parameter Number 12 – Set Proportional Band (P20 Must be Set to 0)
Step
1
2
3
4
5
Press
3-6 seconds
Until Display
Reads
Flashing Decimal
Flashing Decimal
(value between
50 and 250)
Flashing
Description
Accesses
changeable
parameters.
Accesses
parameter no. 12.
Displays current
parameter value.
Incremental
value is:
x 10 mbar
Edits parameter.
Accepts and
saves new
parameter
setting.
Sequences to
next parameter.
Behavior Control
The regulation speed of the pressure regulator can be modified by means of one parameter. (P 20)
The value in this parameter has a range from 0-5. A higher value indicates slower regulation speed, but will be more stable.
* When the value 0 is entered, you are able to create your own custom settings true parameters 12, 13 and 21.
or
or
Parameter Number 20 – Set Behavior Control
Step
1
2
3
4
5
Press
3-6 seconds
Until Display
Reads
Flashing Decimal
Flashing Decimal
(value between
0 and 5)
Flashing
Description
Accesses
changeable
parameters.
Accesses
parameter no. 20.
Displays current
parameter value.
Edits parameter
0 = custom set*
1 = fastest (narrow
proportional band)
2 = fast
3 = normal
4 = slow
5 = slowest
(proportional
band is broad)
Accepts and
saves new
parameter
setting.
Sequences to
next parameter.