user’s manual PSU

 

 

10

 

3.2. 

Mains supply 

 
The PSU series is designed for fixed connection to TN networks (TN-C, TN-C-S or TN-S). 
Please note that the line-earth voltage may not exceed 300VAC.  
 

 

When grounding the neutral conductor, mains voltages 
of up to 480VAC are permitted. 

 

 

When  grounding  an  external  conductor  (delta  mains, 
two-phase  mains),  mains  voltages  (external  conductor 
voltages) of up to 300VAC are permitted. 

 

 

 
Servo controllers which are to be connected to an IT network must be provided with a 
separating transformer. Then the PSU device is operated locally like in a TN network. The 
secondary sided center of the separating transformer must be grounded and connected to the 
PE connector of the PSU. 
 
 

4.Parameters set-up 

 

N.B.:

  

This operation must be executed only by the first axis connected to the PSU. 

 

4.1.1.

 

Voltage supply 

 
The default status of the drive is configured to 400VAC (=560V DC). For all other cases, it’s 
necessary to set the correct value of the voltage [3-phase VAC

supply  

2 = VDC

bus

]: 

 
 

230V AC 3-phase  

Æ

  Pr206 = 325 

 

400V AC 3-phase  

Æ

  Pr206 = 565 

 

480V AC 3-phase  

Æ

  Pr206 = 680 

 
To activate the new configuration, it’s necessary to save the parameter and restart the PSU 
unit. 
 
 

Summary of Contents for P10

Page 1: ...1 User s manual Rev 0 January 2011 PSU...

Page 2: ...Parker Hannifin Divisione S B C EME Division and of its licensees and they shall not be copied or used without express authorization Parker Hannifin S p A Divisione S B C is committed to a continuous...

Page 3: ...s 5 1 2 2 Cable 5 1 2 3 Grounding 5 1 2 4 PSU protections 5 1 2 5 Hardware PSU 6 2 MOUNTING 7 2 1 Connectors layout 8 2 1 1 LED Status 8 2 1 2 Signal connectors 8 3 MODULE CONNECTIONS 9 3 1 1 Rail sys...

Page 4: ...PSUPx0 Mains module 3AC 230 480V nominal power in 1kW 10 10kW 20 20kW 30 30kW D6 Designation nominal supply 3 Configuration and parameterization interface USB USB connection 4 Options Mxx I O extensi...

Page 5: ...1 2 Nm M5 Braking resistor X40 Section 0 25 4mm2 AWG23 11 0 25 4mm2 AWG23 11 Tightening torque 0 5 Nm M4 0 5 Nm M4 Mains X41 Section 0 5 6mm2 AWG20 10 0 5 16mm2 AWG20 6 Tightening torque 1 2 Nm M5 1 7...

Page 6: ...41 41 36 Peak output current 5 sec Arms 36 36 30 72 72 60 82 82 72 Power kW 6 10 10 12 20 20 17 30 30 Internal capacitance F 550 1175 1175 Total capacity applicable F 2400 5000 5000 External braking...

Page 7: ...on user s manual PSU 7 2 Mounting 100mm 360mm 263mm 96mm 400mm 90 50 5mm 101mm PSU Weight Size 1 P10 3 95 kg Size 2 P20 P30 6 5 kg P20 Dimensions Size Lenght mm Height mm Depht mm 1 50 360 410 270 2 1...

Page 8: ...U completed Flashes slowly Serial communication error Flashes quickly Flashes quickly Ready On Off 2 1 2 Signal connectors X41 Mains X40 Braking resistor 1 L1 R Braking resistor No short circuit prote...

Page 9: ...safety measures in order to prevent damages to persons and electric accidents Address setting Switch Value upon ON 1 16 2 32 3 64 Range 0 16 32 48 64 80 96 112 Settings left OFF right ON 1st Module a...

Page 10: ...etwork must be provided with a separating transformer Then the PSU device is operated locally like in a TN network The secondary sided center of the separating transformer must be grounded and connect...

Page 11: ...User Manual Rev 0 January 2011 First edition For other informations log into website www sbcelettronica com Arranges to the manual data can be made by the manufacturer without advance notice The data...

Page 12: ......

Reviews: