background image

14 - EN

3.3.2 Securing the Generator

3.3.3 Making the Connections

Refer to the “Recommended System Component Layout” on page 11 for 
the desired system configuration.

Port connections are provided on both sides of the generator. Connect the 
ball valves supplied to the ports, using PTFE tape on the threads to provide 
a leak free seal. 

Assemble the inlet pressure regulator as illustrated below taking note of the 
flow directions marked on the underside of the pilot operated regulator. 

Use PTFE tape on the threads to provide a leak free seal.

Note.

 Fittings are not supplied. 

When installing the 3-way ball valve to the Nitrogen Outlet port ensure that 
it is positioned in a vertical position and so that there is unrestricted access 
to the centre port for the connection of a flow meter.

Install the pipe-work ready for connection to the buffer vessel and 
compressed air supply. We recommend that additional ball valves are 
connected to the buffer vessel ports to allow it to be isolated during 
maintenance activities.

Setting the inlet Pressure Regulator

The inlet pressure must be set prior to running the generator.

Adjust the internal Inlet / Outlet pressure ball valve to the 

Inlet 

Pressure 

position (pointing down).

Power up the generator and navigate to menu 3.5. The inlet 
compressed air pressure will be displayed.

Check the rating plate for the required set pressure then adjust the regulator until the required set pressure is displayed on menu 3.5.

Tighten the lock nut on the regulator adjustment handle to prevent inadvertent adjustment.

Reposition the internal Inlet / Outlet pressure ball valve to the 

Outlet Pressure 

position (pointing upwards).

The generator MUST be fixed in position using suitable 
M20x40mm Rawl bolts (or equivalent). Mounting holes are 
provided in the feet of the generator.

1

Mounting holes

2

Inlet Port: Compressed Air Inlet (1” BSPP ball valve)

3

Inlet Pressure Regulator

4

Outlet Port: Nitrogen Outlet (1/2” 3-way ball valve)

5

Inlet Port: From Buffer Vessel (1/2” ball valve)

6

Outlet Port: To Buffer Vessel (1” BSPP ball valve)

7

Internal inlet / outlet pressure ball valve

1” BSPP

1/4” BSPP

Summary of Contents for NITROSource N2-25P

Page 1: ...gen Gas Generator NITROSource N2 20P N2 80P Original Language User Guide aerospace climate control electromechanical filtration fluid gas handling hydraulics pneumatics process control sealing shieldi...

Page 2: ......

Page 3: ...or 14 EN 3 3 3 Making the Connections 14 EN 3 4 Electrical Installation 15 EN 3 5 General Requirements 15 EN 3 6 Customer Connections 15 EN 3 6 1 Generator Mains Voltage Supply 15 EN 3 6 2 Dryer Suppl...

Page 4: ......

Page 5: ...for pressure temperature and compressed air requirements Do not connect liquids or gases or to the inlet port of this generator Use of the equipment in a manner not specified within this user guide m...

Page 6: ...rmed correctly may lead to damage to this product Conformit Europ enne Highlights actions or procedures which if not performed correctly could lead to electric shock When disposing of old parts always...

Page 7: ...ating plate as illustrated Model No N 2 8 0 P A L N Model 20 25 35 45 55 60 65 75 80 Technology P Pressure Swing Adsorption O2 Purity X Ultra High Purity 10 ppm A High Purity 50 1000ppm B Low Purity 0...

Page 8: ...Air Temperature 7 barg 101 5 psi g Air inlet pressure Model 5 ppm 10ppm 50ppm 100ppm 250ppm 500ppm 0 10 0 40 0 50 1 2 3 4 5 N2 20P m3 hr 3 5 4 5 6 7 8 0 9 7 11 1 12 4 16 7 17 7 21 3 25 3 29 8 30 9 33...

Page 9: ...ers Port Connections Environmental Parameters Air Quality ISO 8573 1 2010 Class 2 2 2 2 2 1 with high oil vapour content Pressure 5 13 bar g 72 5 188 5 psi g Temperature 5 50 o C 41 122 o F Purity 20...

Page 10: ...80 5 54 4 350 13 8 853 5 33 6 1007 39 6 1271 50 1739 68 5 722 1591 7 N2 65P 1894 74 6 550 21 7 1907 75 1 500 19 7 1549 5 61 0 350 13 8 853 5 33 6 1007 39 6 1271 50 1739 68 5 807 1779 1 N2 75P 1894 74...

Page 11: ...re the environmental conditions fall outside of those specified in the technical specification it should be moved to its final location installation site and left to stabilise prior to unpacking Failu...

Page 12: ...ion 1 Outlet Port To Buffer Vessel 7 User control interface with 20 x 2 line menu display 2 Cable glands 8 Exhaust silencer 3 Pressure gauges 9 Oxygen Dependant Switching EST Sensor if fitted 4 Inlet...

Page 13: ...constant pdp of 3 C however this is the least preferred option as this type of dryer provides a inimal barrier to oil carry over and should be strongly discouraged It must be used in conjunction with...

Page 14: ...n international standard that specifies the purity classes of compressed air with respect to solid particulates water and oil The air inlet quality specified for this generator is ISO 8573 1 2010 clas...

Page 15: ...The most commonly used material for installing nitrogen pipe work is table X de greased copper This should be silver soldered with a nitrogen purge where ever possible and for threaded interfaces gene...

Page 16: ...s to allow it to be isolated during maintenance activities Setting the inlet Pressure Regulator The inlet pressure must be set prior to running the generator 1 Adjust the internal Inlet Outlet pressur...

Page 17: ...t breaker rated at 250VAC 6A with a minimum short circuit rating of 10KA All of the current carrying conductors should be disconnected by this device This protection should be selected in accordance w...

Page 18: ...tching The generator may be controlled remotely by connecting a remote start stop circuit to digital input 4 on the control board When the circuit is open the generator should remain in standby mode c...

Page 19: ...exceed 30m in length Suitable ferrites are available from Wurth Electronics P N 74271633S 3 6 7 MODBUS The generator s controller is capable of supporting direct Modbus communication via its integral...

Page 20: ...will automatically run through a start up cycle if enabled and then commence normal operation Wait until this cycle is complete and the menu displays Running This may take several minutes for ppm gen...

Page 21: ...ault 10 2 1 Fault 1 Active 2 1 Fault 1 Active C1 at 5234h C1 at 5234h 3 Customer 3 Customer settings settings 3 16 EST enable 3 16 EST enable 0 0 3 15 Modbus parity 3 15 Modbus parity Even Even 3 14 R...

Page 22: ...ating in EST mode Each fault is represented by a fault code and is displayed along with the run hours at which the fault occurred If a fault is active the fault code displayed will flash Any faults th...

Page 23: ...f standby mode and economy mode 0 Disabled 1 Enabled Enables the economy mode 0 Disabled 1 Enabled When enabled the actuation of the Stop control will generate an alarm 0 Disabled 1 Enabled Sets the a...

Page 24: ...nerator is in economy mode If the over ride is enabled a clean up cycle will be performed once every 20 minutes default This allows the generator to go straight on line when the outlet pressure falls...

Page 25: ...he purity of the calibration gas Press to send the calibration level to the O2 Analyser On successful completion of the calibration the new O2 reading will be shown on the bottom line of the display I...

Page 26: ...Months 24000 Hrs 60 Months 40000 Hrs Generator Check the status indicators located on the front panel System Check the inlet air quality Generator Check for air leaks Generator Check the pressure gaug...

Page 27: ...72 84 96 108 120 A M12 EST 0001 12 Month EST Service Kit Every 12 Months D D D D D D D D D D B M24 PPM 0001 24 Month PPM Service Kit Every 24 Months x2 x2 x2 x2 x2 C M36 STD 0001 36 Month Standard Se...

Page 28: ...ontents M24 PPM 0001 24 Month PPM Service Kit Every 24 Months PPM Cell c w wiring M24 PCT 0001 24 Month Percentage Service Kit Every 24 Months Cell c w wiring Catalogue No Description Contents M36 STD...

Page 29: ...r ring main pressure low Check and Rectify Inlet valve not open Check and Rectify Defect on pre treatment package Refer to pre treatment manual Excessive noise or vibration Silencer loose or defective...

Page 30: ...enda PED Assessment Route CAT III N2 20P N2 35P CAT IV N2 45P N2 80P EC Type examination Certificate TBA Notified body for PED Lloyds Register Verification 71 Fenchurch St London EC3M 4BS Authorised R...

Page 31: ......

Page 32: ...e parker com NL The Netherlands Oldenzaal Tel 31 0 541 585 000 parker nl parker com NO Norway Asker Tel 47 66 75 34 00 parker norway parker com PL Poland Warsaw Tel 48 0 22 573 24 00 parker poland par...

Reviews: