background image

6

NITROGEN GENERATORS

INSTALLATION, OPERATION, AND MAINTENANCE MANUAL 

4.1 Prefiltration

Two Balston

®

 high efficiency coalescing filters, an activated carbon filter, and a particulate filter are 

incorporated into the Parker Nitrogen Generators to protect the membrane module from contamina-
tion. The coalescing filters are located behind the filtration access panel. They remove liquids and 
particulate matter from the incoming air supply to 0.01 micron. These filters are equipped with float 
drains which automatically open to empty any liquids which accumulate inside the filter housing. The 
drains are connected to 1/4" O.D. plastic tubing which discharges to atmosphere on the left side of 
the generator (see Figure 1).
The activated carbon filter removes hydrocarbons from the compressed air before it enters the  
separation module. A Balston high efficiency particulate filter is installed between the activated  
carbon filter and the separation module to protect the membrane from carbon dust.

4.2 Air Separation

Air separation takes place in the membrane modules. The modules consist of bundles of hollow 
fiber membranes. As the air passes through these hollow fibers, oxygen and water molecules pass 
through the membrane wall at a higher rate than nitrogen molecules. This differential permeation 
results in a high purity, dry nitrogen gas stream exiting the membrane module. The oxygen enriched 
permeate stream is exhausted through ports on the membrane module at a very low pressure.

4.3 Final Filtration

The final filter on the generators is a Balston Grade GS membrane filter. The final membrane  
filter removes particulate contamination to 0.01 micron (absolute), and assures the user a clean, 
commercially sterile supply of high purity nitrogen.

4.4 Controls

The flow controls integral to the Parker Nitrogen Generators comprise: an operating pressure  
gauge, a flowmeter, a flow control valve, an outlet pressure gauge, and an outlet pressure regulator 
(see Figures 1 and 2). Proper use of these controls will assure the user of a 95% to 99.5% purity  
nitrogen outlet stream. The pressure gauges, mounted on the front panel, measure operating pres-
sure and outlet pressure. The outlet pressure regulator allows the user to set the pressure of the outlet 
nitrogen process stream. The flow control valve sets the flow rate of nitrogen exiting the membrane 
module. The scale on the flowmeter is dimensionless because the operating pressure can range from 
60 psig (4.1 barg) to 145 psig (10 barg). The flowmeter adjustment label on the control panel is used  
to convert the dimensionless flowmeter reading into standard liters per minute of outlet nitrogen 
based on operating air pressure.

Summary of Contents for N2-120

Page 1: ...Nitrogen Generator Installation Operation Maintenance Manual Models N2 120 N2 160 N2 240...

Page 2: ...NITROGEN GENERATORS INSTALLATION OPERATION AND MAINTENANCE MANUAL 1...

Page 3: ...ty 11 8 NITROGEN FLOW AT GIVEN OPERATING PRESSURE AND PURITY 12 9 OPERATION ADJUSTMENT PROCEDURES 14 9 1 Atmospheric Pressure Applications 10 psig 0 7 barg 14 9 2 Elevated Pressure Applications 10 psi...

Page 4: ...of purchase when this product is operated and maintained according to the instructions provided with the product then Parker guarantees at Parker s option to replace the product repair the product or...

Page 5: ...manual and by other safety governing bodies will void the safety certification of this product Any modification of the product will void the warranty If you have any questions or concerns please call...

Page 6: ...100 psig 6 9 barg outlet pressure To achieve this outlet pressure the inlet pressure needs to be approximately 110 115 psig 7 6 7 9 barg 4 ENGINEERED SYSTEM The Parker N2 120 N2 160 and N2 240 Nitrog...

Page 7: ...er rate than nitrogen molecules This differential permeation results in a high purity dry nitrogen gas stream exiting the membrane module The oxygen enriched permeate stream is exhausted through ports...

Page 8: ...tration in a process stream It can be easily installed on top of the nitrogen generator and connected to the outlet nitrogen line using appropriate fittings 6 INSTALLATION All installation operation a...

Page 9: ...tor to up to 2 instruments and to the compressed air supply See Figure 4 for the recommended installation schematic Shutoff Valve A shutoff valve should be installed directly upstream from the nitroge...

Page 10: ...air at room temperature and relatively free of water compressor oil hydrocarbons and particulate matter An oil content 0 01 mg m3 is recommended The dewpoint of the incoming air is recommended to be l...

Page 11: ...rker Nitrogen Generator and the receiver tank see Figure 5 The Balston 72 460 V883 Back Pressure Controller contains both components and may be ordered as an accessory for the Nitrogen Generator The a...

Page 12: ...ust be constant for the system to supply nitrogen of consistent purity to the application The inlet pressure to the Parker Nitrogen Generator should be maximized within process and generator parameter...

Page 13: ...0 PSIG 100 PSIG 125 PSIG 145 PSIG Meter SLPM Meter SLPM Meter SLPM Meter SLPM Meter SLPM Meter SLPM Meter SLPM 99 50 0 7 32 0 9 43 1 1 54 1 3 66 1 5 78 1 9 110 2 1 133 99 00 1 0 43 1 2 55 1 5 71 1 7 8...

Page 14: ...r SLPM Meter SLPM Meter SLPM Meter SLPM 99 50 0 9 23 1 3 34 1 6 47 2 0 60 2 2 75 2 5 88 2 7 100 99 00 1 2 30 1 6 44 2 2 63 2 7 81 2 9 100 3 4 119 3 7 138 98 00 1 7 43 2 3 63 3 0 88 3 7 113 4 2 144 4 8...

Page 15: ...en at or near atmospheric pressure e g purging or blanketing applications use the following procedure for start up and adjustment of the system 1 Open the customer installed inlet air gate valve 2 Adj...

Page 16: ...djust the customer installed inlet air pressure regulator until the Operating Pressure gauge see Figure 1 shows the pressure required to deliver nitrogen at the desired flow rate per flowmeter adjustm...

Page 17: ...nerator to the proper reading as specified by the Flowmeter Adjustment Label 6 Purge the entire system venting the initial nitrogen stream through the vent valve to atmosphere Purge time is dependent...

Page 18: ...9 7 Shutting Down Proper shutdown of the Parker Nitrogen Generator can be accomplished by simply closing the customer supplied inlet air gate valve see Figure 4 or 5 If this valve is left open the sy...

Page 19: ...1B1 BX filter assemblies Replace these filter cartridges with Balston 100 18 DXE and 100 18 BXE filter cartridges When replacing the prefilter cartridges be sure to install the proper grade filter in...

Page 20: ...o the generator and allow the system to depressurize 2 Disconnect the upper hose from the filter using the 7 8 open end wrench 3 Remove the two lockdown knobs to release the filter 4 Disconnect the lo...

Page 21: ...essure Drop 15 psig 0 7 barg Min Max Ambient Operating Temp 34 F 140 F 1 C 60 C Recommended Ambient Operating Temp 68 F 20 C Max Relative Humidity 80 Altitude 2000 m Max Min Max Inlet Air Temp 40 F 13...

Page 22: ...is nontoxic and largely inert It can act as a simple asphyxiant by displacing oxygen in air Inhalation of nitrogen in excessive concentrations can result in uncon sciousness without any warning sympto...

Page 23: ...fied Check setting of flow rate Check the operating pressure to assure that it has not varied from the original reading Check the system for leaks Calibrate oxygen analyzer if needed Air Leak Through...

Page 24: ...410 5121 Engine Mobile Filtration Division EMEA Dewsbury United Kingdom 44 0 1924 487 037 Gas Separation Filtration Division EMEA Team Valley United Kingdom 44 0 191 402 9000 Gas Turbine Filtration Di...

Reviews: