background image

isysNet EtherNet/IP Adapter, Series A (PSSCENA) 

E104P

8

General Specifications (continued)

Operating Temperature 

IEC 60068-2-1 (Test Ad, Operating Cold), 

 

IEC 60068-2-2 (Test Bd, Operating Dry Heat), 

 

IEC 60068-2-14 (Test Nb, Operating Thermal Shock): 

 

-20 to 60°C (-4 to 140°F)

Storage Temperature 

IEC 60068-2-1 (Test Ab, Un-packaged Non-operating Cold), 

 

IEC 60068-2-2 (Test Bb, Un-packaged Non-operating Dry Heat), 

 

-40 to 85°C (-40 to 185°F)

Relative Humidity 

IEC 60068-2-30 (Test Db, Un-packaged Non-operating Damp Heat): 

 

5-95% non-condensing

Shock 

IEC60068-2-27 (Test Ea, Unpackaged Shock): 

 

Operating 30g 

 

Non-operating 50g

Vibration 

IEC60068-2-6 (Test Fc, Operating): 

 

5g @ 10-500Hz

ESD Immunity 

IEC 61000-4-2: 

 

6kV contact discharges 

 

8kV air discharges

Radiated RF Immunity 

IEC 61000-4-3: 

 

10V/m with 1kHz sine-wave 80%AM from 30MHz to 2000MHz 

 

10V/m with 200Hz 50% Pulse 100%AM at 900Mhz 

 

10V/m with 200Hz 50% Pulse 100%AM at 1890Mhz

EFT/B Immunity 

IEC 61000-4-4: 

 

±4kV at 5kHz on power ports 

 

±2kV at 5kHz on communications ports

Surge Transient Immunity 

IEC 61000-4-5: 

 

±1kV line-line(DM) and ±2kV line-earth(CM) on power ports 

 

±2kV line-earth(CM) on unshielded communications port (tested as balanced circuits)

Conducted RF Immunity 

IEC 61000-4-6: 

 

10Vrms with 1kHz sine-wave 80%AM from 150kHz to 80MHz

Emissions 

CSPR 11: 

 

Group 1, Class A

Enclosure Type Rating 

Meets IP65/66/67 (when marked)

Mounting Base Screw Torque 

#8 screw, 7.5 in. lbs. in Aluminum, 16 in. lbs. in Steel

Wiring Category

1

 

1 - on power ports 

 

1 - on communications ports

Weight 

Imperial (Metric)  0.80 lb. (0.36 kg)

Certifications: (when product is marked) 

c-UL-us 

UL Listed Industrial Control Equipment, certified for US and Canada

 

CE 

European Union 89/336/EEC EMC Directive, compliant with: 

 

 

EN 61000-6-4; Industrial Emissions 

 

 

EN 50082-2; Industrial Immunity 

 

 

EN 61326; Meas./Control/Lab., Industrial Requirements 

 

 

EN 61000-6-2; Industrial Immunity

 

C-Tick 

Australian Radiocommunications Act, compliant with: 

 

 

AS/NZS CISPR 11; Industrial Emissions

 

EtherNet/IP  ODVA conformance tested to EtherNet/IP specifications

  1. Use this Conductor Category information for planning conductor routing.  Refer to Publication E115P, “Industrial Automation Wiring and 

Grounding Guidelines”.

Summary of Contents for isysNet E104P A Series

Page 1: ...cations for these products or systems the user through its own analysis and testing is solely responsible for making the final selection of the products and systems and assuring that all performance s...

Page 2: ...Attentions help you Identify a Hazard Avoid a Hazard Recognize the Consequence SHOCK HAZARD Labels may be located on or inside the equipment to alert people that dangerous voltage may be present BURN...

Page 3: ...ddresses to the adapter use version 2 3 2 or greater Understanding Messaging Class 3 Explicit Message requests through the adapter to a specific I O module may not always receive a response from the I...

Page 4: ...or a value greater than 254 the adapter checks to see if DHCP is enabled If DHCP is enabled the adapter asks for an address from a DHCP server The DHCP server will also assign other Transport Control...

Page 5: ...ed to properly seal the connections against leaks and maintain IP67 requirements ATTENTION Female In Connector PSSCENA Network Connector D Coded M12 view into connector Pin 1 Tx Pin 2 Rx Pin 3 Tx Pin...

Page 6: ...Device has an IP address but no CIP connections are established Green CIP connections Device on line has an IP address and CIP connections are established Flashing Red One or more Ethernet connections...

Page 7: ...afety Extra Low Voltage SELV or a Protected Extra Low Voltage PELV power supply to power this adapter A SELV supply cannot exceed 30V rms 42 4V peak or 60VDC under normal conditions and under single f...

Page 8: ...s ports Surge Transient Immunity IEC 61000 4 5 1kV line line DM and 2kV line earth CM on power ports 2kV line earth CM on unshielded communications port tested as balanced circuits Conducted RF Immuni...

Reviews: