2 Introduction

These water coolers are monoblock units for the production of cooled 
water in a closed circuit.
The fan, pump and compressor motors are equipped with a thermal 
protector that protects them against possible overheating.

2.1 Transport

The packed unit must remain:

a)  Upright;
b)  Protected against atmospheric agents;
c)  Protected against impacts.

2.2 Handling

Use a fork-lift truck suitable for the weight to be lifted, avoiding any 
type of impact

2.3 Inspection

a)  All the units are assembled, wired, charged with refrigerant and oil 

and tested in the factory;

b)  On receiving the machine check its condition: immediately notify 

the transport company in case of any damage; 

c)  Unpack the unit as close as possible to the place of installation.

2.4 Storage

a)  Keep the unit packed in a clean place protected from damp and 

bad weather.

b)  Do not stack the units;
c)  Follow the instructions given on the package.

3 Installation

Y

For correct installation, follow the instructions given in par.7.2 and 

7.6.

!

 The product installed must be suitably protected against fi re risk 

(ref. EN378-3).

For the correct application of the warranty terms, follow the in-

structions given in the start-up report, fi ll it in and send it back to Seller

!

 

Liquids to be chilled

The liquids to be chilled must be compatible with the materials used.
Examples of liquids used are water or mixtures of 

water and ethylene 

or propylene glycols.

The liquids to be chilled must not be fl ammable. 
If the liquids to be chilled contain hazardous substances (e.g. ethylene/
propylene glycol), any liquid discharged from a leakage area must be 
collected, because it is harmful to the environment.  When draining 
the hydraulic circuit, comply with the current regulations and do not 
disperse the contents in the environment.

3.1 Operating space

Leave a space of 60 inch (1.5 m) around the unit. 
Leave a space of at least 80 inch (2 metres) above the refrigerator in 
models with vertical emission of condensation air.

3.2 Versions

Air-cooled version
Axial fans (A)

Do not create cooling air recirculation situations. 
Do not obstruct the ventilation grilles.
The ducting of extracted air is not recommended for versions with axial 
fans.

Centrifugal version (C)

Always ensure a minimum counterpressure on the delivery of
fans, ducting the individual hot air outlets.

Water- cooled version (W)

If the water to the condenser is in open circuit, install a mesh fi lter on 
the condensation water inlet.
Please note that for special cooling water types such as demineral-
ized, deionized or distilled it is necessary to contact the manufacturer 
to verify which kind of condenser should be used since the standard 
material may not be suitable.

3.3 Water circuit

3.3.1 

Checks and connection

Before connecting the chiller and fi lling the water circuit, check 

that all the pipes are clean. If not, wash them out thoroughly. 

If the plumbing circuit is of the closed type, under pressure it is 

advisable to install a safety valve set to 87 PSIg (6 bar). 

Always install mesh fi lters on the water inlet and outlet pipelines.

If the hydraulic circuit is intercepted by automatic valves, protect 

the pump with an anti-hammering system.

If the hydraulic circuit is emptied for shut-down periods we 

recommend that you add lubricating fl uid to the pump’s impeller to 
avoid the risk of blockage when it is re-started.    In case the impeller is 
blocked then you should unblock it manually.
Remove the rear cover of the pump and carefully turn the plastic fan.   
If the impeller is stuck then remove the fan and turn the impeller shaft 
directly. After un-blocking the impeller re-assemble the fan and cover.

Preliminary checks

1)  Check that any shut-off valves in the water circuit are open.
2)  In the case of a closed water circuit, check that an expansion tank 

of suitable capacity has been installed. See paragraph 3.3.3.

Connection

1)  Connect the water cooler to the inlet and outlet piping, using the 

special connections located on the back of the unit.
We recommend the use of fl exible unions to reduce system rigidity.

2)  Fill the water circuit using the fi tting provided on the rear of the 

chiller (

).

3)  The tank is equipped with a breather valve that should be operated 

manually when fi lling the tank. Also, if the hydraulic circuit has high 
points, install a vent valve at the highest points.

4)  We recommend that taps are installed on the inlet and outlet pipes, 

so that the unit can be excluded for maintenance when necessary.

5)  If the chiller works with an open tank, the pump must be installed 

on intake to the tank and on delivery to the chiller.

Subsequent checks

1)  Check that the tank and the circuit are completely full of water and 

that all the air has been expelled from the system.

2)  The water circuit must always be kept full. For this reason, carry 

out periodic checks and top the circuit up if necessary, or install an 
automatic fi lling kit.

3.3.2 

Water and ethylene glycol

If installed outdoors or in an unheated indoor area, it is possible that 
the water in the circuit may freeze if the system is not in operation dur-
ing the coldest times of the year.
To avoid this hazard:

a)  Equip the chiller with suitable antifreeze protection devices, avail-

able from the manufacturer as optional accessories;

b)  Drain the system via the drain valve if the chiller is to remain idle for 

a prolonged period;

c)  Add an appropriate quantity of antifreeze to the water in circulation 

(see table).

Sometimes the temperature of the outlet water is so low as to require 
the addition of ethylene glycol in the following percentages.

Outlet water

temperature  [°C]

Ethylene glycol

(% vol.)

Ambient

temperature

4

5

-2

2

10

-5

0

15

-7

-2

20

-10

-4

25

-12

-6

30

-15

3.3.3 Expansion 

tank

To avoid the possibility of an increase or decrease in the volume of the 
fl uid due to a signifi cant change in its temperature causing damage to 
the machine or the water circuit, we recommend installing an expansion 
tank of suitable capacity.
The expansion tank must be installed on intake to the pump on the rear 
connection of the tank.
The minimum volume of an expansion tank to be installed on a closed 
circuit can be calculated using the following formula:
V=2 x Vtot x (Pt min - P t max)
where
Vtot= vol. circuit total (in litres)
P t min/max= specifi c weight at the minimum/maximum temperature 
reached by the water [kg/dm3].

Summary of Contents for Hyperchill PCW040

Page 1: ...PCW040 PCW060 PCW080 PCW110 PCW130 PCW160 Hyperchill 60Hz DATE 14 02 2022 Rev 19 CODE 398H272295 EN User Manual ES Manual de uso FR Manuel d utilisation PT Manual do utilizador...

Page 2: ......

Page 3: ...o di modi care le informazioni contenute nel presente manuale senza alcun preav viso Ai ni di una completa ed aggiornata informazione si rac comanda all utente di consultare il manuale a bordo unit CA...

Page 4: ...let pipelines Y If the hydraulic circuit is intercepted by automatic valves protect the pump with an anti hammering system Y If the hydraulic circuit is emptied for shut down periods we recommend that...

Page 5: ...at the machine and the auxiliary equipment are earthed and protected against short circuit and or overload Once the unit has been connected and the upstream main switch closed thereby connecting the p...

Page 6: ...imit values Pmax and Pmin indicated on the pump data plate P1 pressure with pump ON P0 pressure with pump OFF Pmin P1 P0 Pmax Example n 1 Conditions closed circuit pressure P0 29 PSIg 2 bar pump data...

Page 7: ...8 Antifreeze heater operating mode see para 4 4 8 1 FUA U 0 Antifreeze heater activation mode see para 4 4 8 2 AbrA U 2 Activation set point B3 ArA U 5 0 41 0 4 4 8 1 FUA antifreeze heater operating m...

Page 8: ...maintenance make sure the power to the refrigerator is disconnected Y Always use the Manufacturer s original spare parts otherwise the Manufacturer is relieved of all liability regarding machine malf...

Page 9: ...FILTER CLOGGED RENEW THE FILTER CONDENSER FINS DIRTY CLEAN THE FINS OF THE CONDENSER CONDENSER SURFACES CLOGGED CLEAR THE FRONT SURFACE OF THE CON DENSER INSUFFICIENT WATER FLOW INCREASE THE FLOW RATE...

Page 10: ...English 8 8 PCW040 160...

Page 11: ...ricante se reserva el derecho de modi car sin previo aviso la informaci n de este manual Para que la infor maci n resulte completa se recomienda al usuario consultar el manual a pie de m quina PRECAUC...

Page 12: ...ed en los tubos de entrada y salida del agua Y Si el circuito hidr ulico posee v lvulas autom ticas de corte proteger la bomba con sistemas contra golpe de ariete Y Si se vac a el circuito por paradas...

Page 13: ...ada exterior de tipo ac s tico visual o incluida en un sistema l gico por ejemplo un PLC 3 4 3 Encendido y apagado a distancia Todos los enfriadores pueden dotarse de un mando de arranque y parada a d...

Page 14: ...r que la temperatura del agua tratada no baje de los 41 F 5 C y la temperatura ambiente en la que opera el circuito hi dr ulico no baje de los 41 F 5 C En caso contrario a adir al agua la cantidad de...

Page 15: ...pulse el bot n P5 para confirmar 4 Cambie el valor usando las flechas arriba y abajo P3 y P4 despu s pulse el bot n P5 para confirmar 6 Pulse el bot n P3 para volver al par metro dIrE 7 Pulse el bot...

Page 16: ...ia y fiabilidad del refrigerador hay que a Z ocada 6 meses climpiar las aletas del condensador y contro lar que la absorci n de corriente del compresor est dentro de los valores nominales b Z kit de m...

Page 17: ...TASCADO SUSTITUIR EL FILTRO ALETAS DEL CONDENSADOR SUCIAS LIMPIAR LAS ALETAS DEL CONDENSADOR SUPERFICIE DEL CONDENSADOR OBSTRUIDA LIBERAR LA SUPERFICIE FRONTAL DEL CONDENSADOR CAUDAL DE AGUA INSUFICIE...

Page 18: ...Espa ol 8 8 PCW040 160...

Page 19: ...et ou options sont parfaitement conformes pour une utilisation correcte de cette m me unit ou de ses composants ATTENTION Le fabricant se r serve le droit de modi er sans aucun pr avis les informatio...

Page 20: ...es d entr e et de sortie de l eau Y Si le circuit hydraulique est intercept par des soupapes auto matiques prot ger la pompe avec des syst mes contre les coups de b lier Y Si le circuit est vid pour i...

Page 21: ...iaires sont bien mis la terre et qu ils sont prot g s contre les courts circuits et ou les surcharges Apr s avoir branch l unit et ferm l interrupteur g n ral en amont mettant ainsi la machine sous te...

Page 22: ...he 4 5 b V rifier le fonctionnement de la pompe avec le manom tre lire P1 et P0 et les valeurs limites de pression Pmax et Pmin inscrites sur la plaquette signal tique de la pompe P1 pression avec pom...

Page 23: ...rmostatation B1 dIA U 1 0 1 8 Modalit fonctionnement r sistance antigel voir par 4 4 8 1 FUA U 0 Modalit activation r sistance anti gel voir par 4 4 8 2 AbrA U 2 Point de consigne activation B3 ArA U...

Page 24: ...hange d origine dans le cas contraire le constructeur est d gag de toute responsabilit pour le mauvais fonctionnement de la machine Y En cas de fuite du r frig rant appeler un professionnel qualifi et...

Page 25: ...TES DU CONDENSATEUR SALES NETTOYER LES AILETTES DU CONDENSATEUR SURFACE DU CONDENSEUR BOUCH E LIB RER LA SURFACE FRONTALE DU CONDENSATEUR D BIT D EAU INSUFFISANT AUMENTARE LA PORTATA DEL FLUI DO DA RA...

Page 26: ...Fran ais 8 8 PCW040 160...

Page 27: ...N O O fabricante reserva se o direito de modi car as infor ma es contidas no presente manual sem incorrer na obriga o de avis las previamente Para obter informa es completas e actualizadas recomenda s...

Page 28: ...om sistemas anti golpe de ariete Y Se o circuito for esvaziado para paragens prolongadas acon selh vel adicionar l quido de lubrifica o no impulsor da bomba para evitar que bloqueie no pr ximo arranqu...

Page 29: ...protegidos contra curto circuitos e ou sobrecargas Uma vez ligada a unidade e uma vez fechado o interruptor geral situado a montante conferindo assim tens o m quina a voltagem do circuito el ctrico at...

Page 30: ...uncionamento correcto da bomba utilizar um ma n metro consultar P1 e P0 e os valores limites de press o Pmax e Pmin indicados na chapa de caracter sticas da bomba P1 press o com bomba ON P0 press o co...

Page 31: ...TYPE DEFAULT Valor definido da regula o B1 SEA U 7 0 45 0 Diferencial de controlo da tempera tura por term stato B1 dIA U 1 0 1 8 Modo de funcionamento da resis t ncia anti gelo ver par 4 4 8 1 FUA U...

Page 32: ...ncias gerais Antes de efectuar qualquer manuten o verifique se o refrigera dor est desligado Y Utilizar sempre pe as de substitui o originais do fabricante caso contr rio o fabricante n o se responsa...

Page 33: ...ENTUPIDO SUBSTITUA O FILTRO ALHETAS DO CONDENSADOR SUJAS LIMPE AS ALHETAS DO CONDENSADOR SUPERF CIE DO CONDENSADOR OBSTRU DA DESOBSTRUA A SUPERF CIE FRONTAL DO CONDENSADOR D BITO DE GUA INSUFICIENTE...

Page 34: ...Portugu s 8 8 PCW040 160...

Page 35: ......

Page 36: ...fg E mail gsfsupport parker com Parker Hannifin Manufacturing S r l Sede Legale Via Sebastiano Caboto 1 Palazzina A 20094 Corsico MI Italy Sede Operativa Gas Separation and Filtration Division EMEA St...

Page 37: ...Ap ndice Appendix Appendice Anexo DATE 14 02 2022 Rev 19 CODE 398H272295...

Page 38: ......

Page 39: ...Vers o com condensador de gua LAT Opci n baja temperatura ambiente Low ambient temperature option Option basse temp rature ambiante Op o de baixa temperatura ambiente NP Opci n sin bomba No pump opti...

Page 40: ...nlet Entr e eau de condensation Entrada de gua de condensa o Salida agua de condensaci n Condensation water outlet Sortie eau de condensation Sa da de gua de condensa o Carga Descarga del agua Water d...

Page 41: ...ble homologu pour le rac cordement lectrique Sec o m nima do cabo homologado para a liga o el ctrica H20 Temperatura del agua Water temperature Temp rature eau Temperatura da gua Min Temperatura m nim...

Page 42: ...cional L mite del equipo Limit of equipmen Limite de l appareil Limite do aparelho Alarma general General alarm Alarme g n rale Alarme geral 1 MC1 Compresor Compressor Compresseur Compressor 2 Condens...

Page 43: ...de l eau V lvula de descarga da gua 15 Man metro del agua Water manometer Manom tre eau Man metro de gua 16 Man metro entrada refrigerante Refrigerant suction manometer Manom tre aspiration r frig ra...

Page 44: ...ique Controlo electr nico 22 PV1 3 Presostato Ventilator Fan pressure switch Pressostat ventilateur Press stato ventilador 23 HP1 Presostato de alta presi n High pressure switch Pressostat haute press...

Page 45: ...pet antiretour V lvula sem retorno A2 Pantalla local Local display Afficheur local Visor local A3 Variador de velocidad presost tico ventilador Fan pressure regulating speed variator Variateur de vite...

Page 46: ...ransformer Fusibles transformateur auxiliaires Fus veis auxiliares do transformador FU3 4 5 6 Fusible auxiliares Auxliary fuse Fusible auxiliaires Fus vel auxiliar F1 2 Rel t rmico bomba Pump thermal...

Page 47: ...Conector de la tarjeta Card connector Connecteur carte Conector da placa X1 6 BornerasTerminal blocks Bo tes bornes R guas de terminais UD Salidas digitales Digital Outputs Sorties num riques Sa das d...

Page 48: ...terrupteur on off Interruptor on off A101 Pantalla a distancia Remote display Afficheur distance Visor remoto A102 Tarjeta de derivaci n Derivation card Fiche d rivation Placa de deriva o B3 Sonda tem...

Page 49: ...ied with adaptors 1 1 2 NPT F 53 47 6 180 PCW110 903 9 410 52 PCW130 948 0 430 66 0 250 PCW160 1146 4 520 41 113 F 14 113 F 5 C 45 C 18 45 C 56 79 3 300 MODEL R407C F L A A 460V 10 3ph 60Hz IP lb Kg C...

Page 50: ...19 185 5 7 28 19 40 1 57 148 5 83 60 2 36 169 5 6 67 1030 40 55 30 1 18 30 1 18 No 4 HOLES 12 730 28 74 15 59 15 59 760 29 92 1248 49 13 675 26 57 1090 42 91 37 1 46 435 17 13 662 26 06 748 29 45 374...

Page 51: ...5 59 760 29 92 168 5 6 63 148 5 83 40 1 57 390 15 35 411 5 16 18 19 30 1 18 30 1 18 1650 64 96 775 30 51 172 5 6 77 19 1384 54 49 1713 5 67 46 63 5 5 2 50 19 180 5 7 09 19 212 5 8 35 19 730 28 74 927...

Page 52: ...18 30 1 18 158 5 6 24 148 5 83 40 1 57 411 5 16 18 19 172 5 6 77 19 748 29 45 677 26 65 605 23 82 375 14 76 553 21 77 1352 53 22 1657 65 24 66 5 5 2 62 19 1716 5 67 58 10 39 374 14 72 374 14 72 267 10...

Page 53: ...76 414 5 16 30 19 775 30 51 1248 49 13 No 4 HOLES 12 730 28 74 760 29 92 2140 84 25 2200 86 6 148 5 83 40 1 57 169 5 5 6 67 19 390 15 35 240 5 9 44 19 191 5 7 50 19 66 5 2 62 158 5 6 24 15 59 15 59 45...

Page 54: ...2 398H473637 398H473643 398H473644 refrigerant filter 7 398H206221 398H206224 398H206225 expansion valve kit 8 398H378803 398H378805 398H378806 398H378807 398H378808 tank evaporator 10 27 398H510980 3...

Page 55: ...17 7 5 Circuit diagram PCW040 160 A PCW040 160 A1 PCW160 PCW160 NP PCW160...

Page 56: ...18 7 6 Wiring diagram PCW040 060 A PCW040 160 Sheet 1 of 7...

Page 57: ...19 7 6 Wiring diagram PCW040 060 A PCW040 160 Sheet 2 of 7...

Page 58: ...20 7 6 Wiring diagram PCW040 060 A PCW040 160 Sheet 3 of 7...

Page 59: ...21 7 6 Wiring diagram PCW040 060 A PCW040 160 Sheet 4 of 7...

Page 60: ...22 7 6 Wiring diagram PCW040 060 A PCW040 160 Sheet 5 of 7...

Page 61: ...23 7 6 Wiring diagram PCW040 060 A PCW040 160 Sheet 6 of 7...

Page 62: ...24 7 6 Wiring diagram PCW040 060 A PCW040 160 Sheet 7 of 7...

Page 63: ...25 7 6 Wiring diagram PCW080 160 A PCW040 160 Sheet 1 of 8...

Page 64: ...26 7 6 Wiring diagram PCW080 160 A PCW040 160 Sheet 2 of 8...

Page 65: ...27 7 6 Wiring diagram PCW080 160 A PCW040 160 Sheet 3 of 8...

Page 66: ...28 7 6 Wiring diagram PCW080 160 A PCW040 160 Sheet 4 of 8...

Page 67: ...29 7 6 Wiring diagram PCW080 160 A PCW040 160 Sheet 5 of 8...

Page 68: ...30 7 6 Wiring diagram PCW080 160 A PCW040 160 Sheet 6 of 8...

Page 69: ...31 7 6 Wiring diagram PCW080 160 A PCW040 160 Sheet 7 of 8...

Page 70: ...32 7 6 Wiring diagram PCW080 160 A PCW040 160 Sheet 8 of 8...

Page 71: ......

Page 72: ...fg E mail gsfsupport parker com A division of Parker Hannifin Corporation Parker Hannifin Manufacturing S r l Sede Legale Via Sebastiano Caboto 1 Palazzina A 20094 Corsico MI Italy Sede Operativa Gas...

Reviews: