English
3/10
Hyperchiller 150-230
operation during the coldest times of the year.
To avoid this hazard:
a) Equip the chiller with suitable antifreeze protection devices,
available from the manufacturer as optional accessories;
b) Drain the system via the drain valve if the chiller is to remain
idle for a prolonged period;
c) Add an appropriate quantity of antifreeze to the water in
circulation (see table).
Sometimes the temperature of the outlet water is so low as to
require the addition of ethylene glycol in the following percent-
ages.
Outlet water
temperature [°C]
Ethylene glycol
(% vol.)
Ambient
temperature [°C]
4
5
-2
2
10
-5
0
15
-7
-2
20
-10
-4
25
-12
-6
30
-15
-10
40
-20
3.4.3 Expansion tank
To avoid the possibility of an increase or decrease in the vol-
ume of the fl uid due to a signifi cant change in its temperature
causing damage to the machine or the water circuit, we recom-
mend installing an expansion tank of suitable capacity.
The expansion tank must be installed on intake to the pump on
the rear connection of the tank.
The minimum volume of an expansion tank to be installed on a
closed circuit can be calculated using the following formula:
V=2 x Vtot x (Pt min - P t max)
where
Vtot= vol. circuit total (in litres)
P t min/max= specifi c weight at the minimum/maximum tem-
perature reached by the water [kg/dm3].
The specifi c weight values at different temperatures for glycol
percentage values are given in the table.
%
glicol
Temperature [°C]
-10
0
10
20
30
40
50
0%
1.0024 1.0008 0.9988 0.9964 0.9936 0.9905 0.9869
10%
1.0177 1.0155 1.0130 1.0101 1.0067 1.0030 0.9989
20%
1.0330 1.0303 1.0272 1.0237 1.0199 1.0156 1.0110
30%
1.0483 1.0450 1.0414 1.0374 1.0330 1.0282 1.0230
!
Caution: When fi lling the system, take into account
the capacity of the expansion vessel as well.
If the ambient air temperature at the chiller is less than
-10°C then you must move the expansion tank to a pro-
tected ambient close on the water return side of the chiller.
The safety valve and bleed valve must remain at the chiller.
3.5 Electrical circuit
3.5.1
Checks and connections
!
Before carrying out any operation on the electrical system,
make sure that the appliance is disconnected from the electri-
cal power supply.
All electrical connections must comply with the applicable
regulations in force in the country of installation.
Initial checks
1) The power supply voltage and frequency must correspond
to the values stamped on the chiller nameplate. The power
supply characteristics must not deviate, even for brief
periods, from the tolerance limits indicated on the electrical
diagram , which are +/- 10% for the voltage; +/- 1% for the
frequency.
2) The power supply must be symmetrical (the effective volt-
ages and the phase angles of consecutive phases must be
equal). The maximum permissible voltage imbalance is 2%.
Connection
1) The electrical power supply must be connected to the chiller
using a 4-wire cable, comprising 3 phase conductors and an
earth conductor, with no neutral. For minimum cable section,
see par. 7.5.
2) Pass the cable through the cable entry on the rear panel of
the machine and connect the phase and neutral to the termi-
nals of the main isolator switch (QS); connect the earth wire
to the earth terminal (PE).
3) Ensure that supply cable has at its source protection against
direct contact of at least IP2X or IPXXB.
4) On the supply line to the chiller, install a residual-current cir-
cuit breaker with a trip rating of 0.3A, with the current rating
indicated in the reference electrical diagram, and with a short
circuit current rating appropriate to the short circuit fault cur-
rent existing in the machine installation area.
The nominal current In of the magnetic circuit breaker must
be equal to the FLA with an intervention curve type D.
5) Max. grid impedance value = 0.274 ohm.
Subsequent checks
Check that the machine and the auxiliary equipment are
earthed and protected against short circuit and/or overload.
!
Once the unit has been connected and the upstream main
switch closed (thereby connecting the power supply to the ma-
chine), the voltage in the electrical circuit will reach dangerous
levels. Maximum caution is required!
3.5.2 General
alarm
All the chillers are equipped with an alarm signalling system
(see electrical diagram), comprised of a switching free contact
in a terminal block: this may be used for the connection of an
external audible or visual alarm, or used to provide an input
signal for a logic control system such as a PLC.
3.5.3 ON/OFF
remoto
All the chillers can be connected to a remote ON/OFF control.
See the electrical diagram for the connection of the remote ON-
OFF contact.
3.6 Water-cooled version (W)
In the water-cooled version, the chillers require a water circuit
that takes the cold water to condenser.
The water version chiller is equipped with a pressure regulating
valve at the condenser inlet, whose function is to regulate the
water fl ow in order to always obtain optimum condensation.
Preliminary checks
If the water supply to the condenser is by means of a closed
circuit,
perform all the preliminary checks listed for the main water
circuit (para. 3.3.1).
Connection
1) It is advisable to equip the cooling water circuit with shutoff
valves, enabling the machine to be cut out in case of mainte-
nance.
2) Connect the water delivery/return pipes to the special con-
nections located on the back of the unit.
3) If the cooling water is “expendable” it is advisable to equip
the circuit with a fi lter at the condenser inlet, in order to re-
duce the risk of the surfaces becoming dirtied.
4) If the circuit is of the closed type, make sure it is fi lled with
water and the air properly vented.
Summary of Contents for Hyperchill ICE150
Page 2: ......
Page 63: ...Appendice Anhang Ap ndice Appendix Appendice Anexo...
Page 84: ...7 8 Circuit diagram ICE150 230 A 20 ICE150 230 DP NP LAT ICE230 A1...
Page 85: ...7 8 Circuit diagram ICE150 183 W 21 ICE150 230 DP NP A1...
Page 86: ...7 9 Wiring diagram Standard 22 ICE150 230 Sheet 1 of 12...
Page 87: ...7 9 Wiring diagram Standard 23 ICE150 230 Sheet 2 of 12...
Page 88: ...7 9 Wiring diagram Standard 24 ICE150 230 Sheet 3 of 12...
Page 89: ...7 9 Wiring diagram Standard 25 ICE150 230 Sheet 4 of 12...
Page 90: ...7 9 Wiring diagram Standard 26 ICE150 230 Sheet 5 of 12...
Page 91: ...7 9 Wiring diagram Standard 27 ICE150 230 Sheet 6 of 12...
Page 92: ...7 9 Wiring diagram Standard 28 ICE150 230 Sheet 7 of 12...
Page 93: ...7 9 Wiring diagram Standard 29 ICE150 230 Sheet 8 of 12...
Page 94: ...7 9 Wiring diagram Standard 30 ICE150 230 Sheet 9 of 12...
Page 95: ...7 9 Wiring diagram Standard 31 ICE150 230 Sheet 10 of 12...
Page 96: ...7 9 Wiring diagram Standard 32 ICE150 230 Sheet 11 of 12...
Page 97: ...7 9 Wiring diagram Standard 33 ICE150 230 Sheet 12 of 12...
Page 98: ...7 9 Wiring diagram L2 option 34 ICE150 230 Sheet 1 of 14...
Page 99: ...7 9 Wiring diagram L2 option 35 ICE150 230 Sheet 2 of 14...
Page 100: ...7 9 Wiring diagram L2 option 36 ICE150 230 Sheet 3 of 14...
Page 101: ...7 9 Wiring diagram L2 option 37 ICE150 230 Sheet 4 of 14...
Page 102: ...7 9 Wiring diagram L2 option 38 ICE150 230 Sheet 5 of 14...
Page 103: ...7 9 Wiring diagram L2 option 39 ICE150 230 Sheet 6 of 14...
Page 104: ...7 9 Wiring diagram L2 option 40 ICE150 230 Sheet 7 of 14...
Page 105: ...7 9 Wiring diagram L2 option 41 ICE150 230 Sheet 8 of 14...
Page 106: ...7 9 Wiring diagram L2 option 42 ICE150 230 Sheet 9 of 14...
Page 107: ...7 9 Wiring diagram ICE150 183 A C W 43 ICE150 230 Sheet 10 of 14...
Page 108: ...7 9 Wiring diagram ICE150 183 A C W 44 ICE150 230 Sheet 11 of 14...
Page 109: ...7 9 Wiring diagram ICE150 183 A C W 45 ICE150 230 Sheet 12 of 14...
Page 110: ...NE150 183 46 ICE150 230 Sheet 13 of 14...
Page 111: ...7 9 Wiring diagram ICE150 183 A C W 47 ICE150 230 Sheet 14 of 14...
Page 112: ......
Page 113: ......