Bulletin 61-60

5

Adjusting the Minimum and Maximum Calibration Points

Minimum calibration:

1.  Bring the liquid level to desired minimum level.

2.  Press the calibration push button and keep it activated in 

approximately 5 seconds, until green LED stops flashing.

3.  Activate, within the next 10 seconds, the calibration push 

button once

Green LED is ON in a few seconds, and then starts flashing.

Output is now 4 mA and the HBLT is in normal operation.

Maximum calibration:

1.  Bring the refrigerant liquid level to desired maximum 

level.

2.  Press the calibration push button and keep it activated in 

approximately 5 seconds, until green LED stops flashing.

3.  Activate, within the next 10 seconds, the calibration push 

button two times, with 1 second in between

Green LED is ON in a few seconds, and then starts flashing.

Output is now 20 mA and HBLT is in normal operation.

Note: 
Maximum calibration is only required if in other refrigerants 
than ammonia best possible accuracy is required alternative if 
a non pre-calibrated electronic part is mounted!

Minimum calibration when minimum level must be 
different from 4 mA:

1.  Bring the liquid level to desired minimum level.

2.  Press the calibration push button and keep it activated in 

approximately 5 seconds, until green LED stops flashing.

3.  Activate, within the next 10 seconds, the calibration 

push button once and keep it activated. (If calibration 
push button is not activated within 10 seconds, it will 
automatically leave calibration mode and return to 
normal operation)

4.  Observe the output mA signal increasing fast starting at 4 

mA.

5.  Release the calibration push button when the output 

signal is a approximately 0.5 mA from the desired point. 6. 
All the next activations will increase the output signal by 
approximately 0.05 mA

6.  Approximately 10 seconds after the latest activation the 

LED starts flashing

7.  Output now corresponds to the value measured at the 

latest activation.

Maximum calibration when maximum level must be 
different from 20 mA:

1.  Bring the liquid level to desired maximum level.

2.  Press the calibration push button and keep it activated in 

approximately 5 seconds, until green LED stops flashing.

3.  Activate, within the next 10 seconds, the calibration push 

button two times, with 1 second in between, and keep 
it activated. (If calibration push button is not activated 

within 10 seconds, it will automatically leave calibration 
mode and return to normal operation)

4.  Observe the output mA signal decreasing fast starting at 

20 mA.

5.  Release the calibration push button when the output 

signal is approximately 0.5 mA from the desired point.

6.  All the next activations will decrease the output signal by 

approximately 0.05 mA

7.  Approximately 10 seconds after the latest activation the 

LED starts flashing

8.  Output now corresponds to the value measured at the 

latest activation.

Reset to Factory Settings

The HBLT can always be reset to factory default settings regardless 
of any revised calibration values.

1.  Press the calibration push button and keep it activated in min. 

20 seconds, until green LED starts flashing.

2.  Release the calibration push button.

3.  When LED starts flashing, reset to factory setting is completed.

All probes reset to the factory setting are pre-calibrated to 
ammonia with a sensor tube length of 1500 mm/59” and a signal  
damping of 15 seconds. See the calibrating on site section of this 
document for further instructions.

LED Indication

When voltage is applied the LED will flash rapidly as many times 
as it has been calibrated through its lifetime. The current mA 
output is activated as soon as the flashing sequence has changed 
from rapid to slowly flashing.

Normal operation:

At normal operation the Green LED will be flashing slowly.

Generally the Green LED is ON every time calibration push button 
is activated.

Calibration mode:

In calibration mode (Press the calibration push button and keep it 
activated in approximately 5 seconds) the Green LED is OFF.

Change of refrigerant:

In refrigeration mode setting (Push the calibration push button 
and keep it pressed while 24 V is connected and then release 
the push button) the green LED is OFF until the push button is 
released.

After this the green LED will flash according to the type of 
refrigerant.

When the refrigerant has been selected, the green LED is 
constantly ON.

Summary of Contents for HBLT-A1

Page 1: ...ccumulators or other similar pressure vessels Available in various lengths and factory calibrated for ammonia R717 Product Features Suitable for ammonia CO2 and halocarbon refrigerants Plug and Play no calibration required when installed on ammonia systems Service Friendly electronic head and probe can be separated without emptying the vessel Improved Calibration range signal output can be adapted...

Page 2: ...d along the height of the pipe column to determine the level of the liquid when setting the HBLT A1 probe as well as to check its performance during operation of the system These are an essential part of any well designed pressure vessel system and the use of an electronic liquid level control does not eliminate this need The pipe connection at the top of the pipe column equalizing the vapor space...

Page 3: ...5mm 1 Receiver Min 75mm 3 Min 100mm 4 Column Cap Sight Glass Pipe Column Weld Weld Liquid level Switch Notes Column caps are only available in 75mm and 100mm 3 and 4 diameters Mounting Instruction It is required to use Teflon tape paste on NPT connections or sealing ring on BSP connections Add Teflon tape paste to the threads Mount the liquid level transmitter on the vessel and tighten to a torque...

Page 4: ...g will be changed HBLT A1 HBLT A1 BSP Calibration Levels Milliamperes Vs Level Milliamperes Percent Full 4 0 0 6 12 5 8 25 0 10 37 5 12 50 0 14 62 5 16 75 0 18 87 0 20 100 0 Signal Damping Signal damping is factory set to 15 seconds This setting can be altered by activating the calibration switch The setting range is 1 to 120 seconds Settings can be made while the system is operating Procedure 1 C...

Page 5: ...he calibration push button and keep it activated in approximately 5 seconds until green LED stops flashing 3 Activate within the next 10 seconds the calibration push button two times with 1 second in between and keep it activated If calibration push button is not activated within 10 seconds it will automatically leave calibration mode and return to normal operation 4 Observe the output mA signal d...

Page 6: ...n Probe Lengths Measuring Range mm inch mm inch 280 11 02 207 8 15 500 19 69 427 16 81 800 31 50 727 28 62 1000 39 37 927 36 50 1200 47 24 1127 44 37 1500 59 06 1427 56 18 1700 66 93 1627 64 05 2200 86 61 2127 83 74 3000 118 10 2927 115 24 HBLT A1 HBLT A1 BSP Parts List Item Part Description 1 Electronic Head 2 Connection DIN 3 LED Green 4 Calibration Push Button 5 LED Level Bar Graph 6 Cover Cali...

Page 7: ...m can be solved by following these steps 1 Turn the HBLT probe upside down 1 Probe 2 3 or 4 Dia Column Tape Water 2 Tape all hole on the sleeve otherwise known as reference pipe to prevent any water from leaking out The 4 20 mA output signal is not inverted despite the upside down position 3 Fill the pipe with water according to your calibration needs With the sleeve full of water at the high leve...

Page 8: ...ties Division Defective products or parts thereof returned to the factory with transportation charges prepaid and found to be defective by factory inspection will be replaced or repaired at Refrigerating Specialties option free of charge F O B factory Warranty does not cover products which have been altered or repaired in the field damaged in transit or have suffered accidents misuse or abuse Prod...

Reviews: