Plug and connector assignment Compax3 Fluid
3.2.5.
Analog Output (plug X2)
Plug X2
Pin
Description
Combicon 3.81mm; female connector
1
I/U Aout0
±10V/10mA or 4..20mA
2
GND 0
3
I/U Aout1
±10V/10mA or 4..20mA
4
GND 1
5
I/U Aout2
±10V/10mA or 4..20mA
6
GND 2
7
I/U Aout3
±10V/10mA or 4..20mA
8
GND 3
9
Iout 0
+/-100mA current output 0
10
GND
11
lout 1
+/-100mA current output 1
12
GND
Terminating resistor:
V/-
10V: ≥ 1000
Ω
Current 4..20mA: ≤ 600
Ω
Current 100mA: ≤ 100
Ω
All outputs are short circuit proof.
Requirement: Connection cable
Use shielded cables.
Shield connection of the cables
The cable must be fully-screened and connected to the Compax3 housing. Use the
cable clamps/shield connecting terminals furnished with the device.
3.2.5.1
Wiring of analog outputs
Output I/U Aout0
Output Iout0
* 20mA to max. 450
Ω
* if RL<=180
Ω
Aout0 to Aout3 do have the same wiring!
Pin assignment
(see on page 15) X2
Iout0 and Iout1 (X2/11 and X2/12) have the same wiring!
3.2.6.
Voltage supply (plug X3)
X2/2
0...20mA*
+/-10V
(10mA)
X2/1 I/Uout0
GND0
Com
pax
3
Fluid
X2/10
+/-100mA*
X2/9 Iout0
GND
Com
pax
3
Fluid