Date of Issue: 19 August 2021
Page 17 of 24
QF 80: Issue 2
Parker Hannifin
– Instrumentation Products Division Europe
President Park, President Way, Sheffield,
South Yorkshire, S4 7UR, United Kingdom
Tel: +44 (0) 114 224 0000 Web: www.parker.com/ipd
Globe / Needle Valve (DN10 (⅜”) – DN50 (2”)
Reference Number:
IOM 002
Date:
20 May 2014
Issue:
B
STEP 8:
Remove the grub screw from the union nut.
Loosen and remove the union bonnet.
GO TO STEP 9
STEP 10:
Remove the stem from the cover.
NOTE:
Depending on the style of the seat, the method for replacing
the disc seal will vary.
For cone seats:
GO TO STEP 11
For flat seats:
GO TO STEP 12
STEP 9:
Remove the headwork from the body.
STEP 11:
Carefully remove the circlip from the end of the disc holder, taking
care not to damage the seal groove and store in a safe place.
Then remove the disc seal and discard.
Note - old seal (ptfe) is black and the replacement seal (pctfe) is
white on sizes 1
½”.
GO TO STEP 13