TWP/TWB200 – TWP/TWB9000
49
MODBUS REGISTER MAP (CONT’D)
30125
R
Control Outputs Register #1
Mirrors bit registers 10033 thru 10048
30126
R
Control Outputs Register #2
Mirrors bit registers 10049 thru 10064
30127
R
Switch Input Data Register #1
Mirrors bit registers 10065 thru 10080
30128
R
Switch Input Data Register #2
Mirrors bit registers 10081 thru 10096
40001
R/W
Alarm Set - Over Temperature
see separate alarm chart for details
40002
R/W
Alarm Set - High Inlet Temperature
see separate alarm chart for details
40003
R/W
Alarm Set - Low Inlet Pressure
see separate alarm chart for details
40004
R/W
Alarm Set - High Dewpoint
see separate alarm chart for details
40005
R/W
Alarm Set - High After-Filter Pressure
see separate alarm chart for details
40006
R/W
Alarm Set - High Pre-Filter Pressure
see separate alarm chart for details
40008
R/W
Alarm Set - Low Purge Temperature
see separate alarm chart for details
40009
R/W
Alarm Set - User Sensor #1 Low Setpoint
see separate alarm chart for details
40010
R/W
Alarm Set - User Sensor #1 High Setpoint
see separate alarm chart for details
40011
R/W
Alarm Set - User Sensor #2 Low Setpoint
see separate alarm chart for details
40012
R/W
Alarm Set - User Sensor #2 High Setpoint
see separate alarm chart for details
40013
R/W
Calibration - Sensor Min Set - Left Tower Pressure
Minimum sensor pressure. Default is 0 psi
40014
R/W
Calibration - Sensor Min Set - Right Tower Pressure
Minimum sensor pressure, Default is 0 psi
40015
R/W
Calibration - Sensor Min Set - Inlet Pressure
Minimum sensor pressure, Default is 0 psi
40016
R/W
Calibration - Sensor Min Set - Output Pressure
Minimum sensor pressure, Default is 0 psi
40017
R/W
Calibration - Sensor Min Set - Purge Pressure
Minimum sensor pressure, Default is 0 psi
40018
R/W
Calibration - Sensor Low Set - Dewpoint Probe
Minimum sensor dewpoint, Default is -148°F
40019
R/W
Calibration - Sensor Min Set - User Sensor #1
User adjustable input #1 minimum range.
Default is 0. Refer to register 40039.
40020
R/W
Calibration - Sensor Min Set - User Sensor #2
User adjustable input #2 minimum range.
Default is 0. Refer to register 40040.
40021
R/W
Calibration - Sensor Max Set -
Left Tower Pressure
Maximum sensor pressure, Default is 200 psi
40022
R/W
Calibration - Sensor Max Set -
Right Tower Pressure
Maximum sensor pressure, Default is 200 psi
40023
R/W
Calibration - Sensor Max Set - Inlet Pressure
Maximum sensor pressure, Default is 200 psi
40024
R/W
Calibration - Sensor Max Set - Outlet Pressure
Maximum sensor pressure, Default is 200 psi
40025
R/W
Calibration - Sensor Max Set - Purge Pressure
Maximum sensor pressure, Default is 200 psi
40026
R/W
Calibration - Sensor Max Set - Dewpoint Probe
Maximum dewpoint. Default is 68°F
40027
R/W
Calibration - Sensor Max Set - User Sensor #1
User adjustable input #1 maximum range, Default is 100
40028
R/W
Calibration - Sensor Max Set - User Sensor #2
User adjustable input #2 maximum range, Default is 100
40029
R/W
Calibration - Sensor Offset Set - Left Tower Pres-
sure
Sensor offset, Default is 0 psi
40030
R/W
Calibration - Sensor Offset Set - Right Tower
Pressure
Sensor offset, Default is 0 psi
40031
R/W
Calibration - Sensor Offset Set - Inlet Pressure
Sensor offset, Default is 0 psi
40032
R/W
Calibration - Sensor Offset Set - Outlet Pressure
Sensor offset, Default is 0 psi
40033
R/W
Calibration - Sensor Offset Set - Purge Pressure
Sensor offset, Default is 0 psi
40034
R/W
Calibration - Sensor Offset Set - Dewpoint Probe
Sensor offset, Default is 0°F
40035
R/W
Calibration - Sensor Offset Set - User Sensor #1
User adjustable input #1 offset
40036
R/W
Calibration - Sensor Offset Set - User Sensor #2
User adjustable input #2 offset
40037
R/W
Calibration - System Display Temperature Units
0 = F, 1 = C., Does not affect Modbus register units.
Summary of Contents for Airtek TWP200
Page 1: ...1 Externally Heated Blower Purge Desiccant Dryers User Manual Models TWP TWB200 TWP TWB9000...
Page 9: ...TWP TWB200 TWP TWB9000 9 TWP Desiccant Dryer Operation TWB Desiccant Dryer Operation...
Page 10: ...TWP TWB200 TWP TWB9000 10 FLOW SCHEMATIC MODELS TWP200 300 DWG FS11682 Rev...
Page 11: ...TWP TWB200 TWP TWB9000 11 FLOW SCHEMATIC MODELS TWP400 800 DWG FS11683 Rev...
Page 12: ...TWP TWB200 TWP TWB9000 12 FLOW SCHEMATIC MODELS TWP1000 1500 DWG FS11684 Rev...
Page 13: ...TWP TWB200 TWP TWB9000 13 FLOW SCHEMATIC MODELS TWP2000 9000 DWG FS11685 Rev...
Page 14: ...TWP TWB200 TWP TWB9000 14 FLOW SCHEMATIC MODELS TWB200 800 DWG FS11686 Rev...
Page 15: ...TWP TWB200 TWP TWB9000 15 FLOW SCHEMATIC MODELS TWB1000 1500 DWG FS11687 Rev...
Page 16: ...TWP TWB200 TWP TWB9000 16 FLOW SCHEMATIC MODELS TWB2000 9000 DWG FS11688 Rev...
Page 17: ...TWP TWB200 TWP TWB9000 17 WIRING DIAGRAM STANDARD CONTROLLER...
Page 18: ...TWP TWB200 TWP TWB9000 18 WIRING DIAGRAM STANDARD CONTROLLER...
Page 19: ...TWP TWB200 TWP TWB9000 19 WIRING DIAGRAM STANDARD CONTROLLER...
Page 20: ...TWP TWB200 TWP TWB9000 20 WIRING DIAGRAM STANDARD CONTROLLER...
Page 21: ...TWP TWB200 TWP TWB9000 21 PANEL LAYOUT STANDARD CONTROLLER...
Page 38: ...TWP TWB200 TWP TWB9000 38 Service Screen...
Page 71: ...TWP TWB200 TWP TWB9000 71...