67
MSC4000 - MSC15000 USER MANUAL
Alarm (100’s) /
Warning (200’s)
Fault
Code
Rules & Causes
Possible Remedy
HIGH DEW POINT
201
Rules:
• Always actuve except for 10 minutes after
RUN is pressed
• Ignored when dryer is displaying Oil Man-
agement message
• Warn if the dew point if 15°F higher than
the dew point setting for 20 seconds
• Automatically resets 2 seconds after the
dew point falls 1°F below the trip point
• Set point is tied to the dewpoint detting
Causes:
1) Dryer is off.
2) Thermal load is too high.
3) Condener is dirty.
4) Contactor is not closing
1) Press Load/Unload or Auto button.
2) Reduce compressed air quantity and/or
inlet temperature.
3) Clean condenser
4) Check contacts and coils for opens,
shorts or sticking. Replace if necessary.
HIGH INLET TEMP
204
Rules:
• Warning if the inlet temperature rises to the
setting for 5 minutes
• The warning can be disabled from the User
Setting screen
• Setting can be accessed from the User
Setting screen
• Automatically restes if the temperature falls
below the setting for 5 minutes
• press alarm reset will reset the alarm and
alarm timer
Causes:
1) Inlet air temperature too high
1) Clean air compressor and/or
improve room ventilation
HIGH
CONDENSER
TEMP
205
Rules:
• Warning if the condenser temperature
(ambient/water) rises above the setting for
5 minutes while the compressor is running
• Setting can be accessed from the User
Setting screen
• Automatically restes if the temperature falls
below the setting for 5 minutes
• Press alarm reset will reset the alarm and
alarm timer
Causes:
1) Ambient/Water temperature too high
2) condenser fan not turning on
3) Cooling water flow insufficient
1) Improve room ventilation or cooling water
source temperature
2) Defective fan motor, blown fan motor
fuses, defective fan pressure switch or wrong
setting
3) Check cooling water delivery system for
sufficient flow and pressure
DRAIN FAULT - 1
& 2
206-207
Rules:
• Warning if the drain level switch is closed
for 10 seconds after the drain duration
setting
• Setting is tied to the drain duration setting
• Automatically resets when level switch
opens
• Pressing alarm reset will reset the alarm
and alarm timer
• In an attempt to clear any drain obstruc-
tions, the drain valve will pulse for 1 minute
Causes:
1) Valve strainer clogged
2) Drain valve clogged
3) Solenoid defective
4) Level sensor defective
1) Clean
2) Disassemble and clean
3) Replace
4) Replace
Summary of Contents for Airtek MSC4000
Page 1: ...Magnum Refrigerated Air Dryers Models MSC4000 MSC15000...
Page 9: ...9 MSC4000 MSC15000 USER MANUAL Start Up Checklist...
Page 11: ...11 MSC4000 MSC15000 USER MANUAL...
Page 28: ...28 MSC4000 MSC15000 USER MANUAL 4 4 I O Screens...
Page 35: ...35 MSC4000 MSC15000 USER MANUAL Reference Guide...
Page 36: ...36 MSC4000 MSC15000 USER MANUAL...
Page 37: ...37 MSC4000 MSC15000 USER MANUAL...
Page 38: ...38 MSC4000 MSC15000 USER MANUAL...
Page 44: ...44 MSC4000 MSC15000 USER MANUAL...
Page 45: ...45 MSC4000 MSC15000 USER MANUAL...
Page 46: ...46 MSC4000 MSC15000 USER MANUAL...
Page 47: ...47 MSC4000 MSC15000 USER MANUAL...
Page 48: ...48 MSC4000 MSC15000 USER MANUAL...
Page 49: ...49 MSC4000 MSC15000 USER MANUAL...
Page 50: ...50 MSC4000 MSC15000 USER MANUAL...
Page 51: ...51 MSC4000 MSC15000 USER MANUAL...
Page 82: ...82 MSC4000 MSC15000 USER MANUAL 10 Associated Drawings...
Page 83: ...83 MSC4000 MSC15000 USER MANUAL...
Page 84: ...84 MSC4000 MSC15000 USER MANUAL...
Page 85: ...85 MSC4000 MSC15000 USER MANUAL...
Page 86: ...86 MSC4000 MSC15000 USER MANUAL...
Page 87: ...87 MSC4000 MSC15000 USER MANUAL...
Page 88: ...88 MSC4000 MSC15000 USER MANUAL...
Page 89: ...89 MSC4000 MSC15000 USER MANUAL...
Page 90: ...90 MSC4000 MSC15000 USER MANUAL...
Page 91: ...91 MSC4000 MSC15000 USER MANUAL...
Page 92: ...92 MSC4000 MSC15000 USER MANUAL...
Page 93: ...93 MSC4000 MSC15000 USER MANUAL...
Page 94: ...94 MSC4000 MSC15000 USER MANUAL...
Page 95: ...95 MSC4000 MSC15000 USER MANUAL...
Page 96: ...96 MSC4000 MSC15000 USER MANUAL...
Page 97: ...97 MSC4000 MSC15000 USER MANUAL...
Page 108: ...108 MSC4000 MSC15000 USER MANUAL...
Page 109: ...109 MSC4000 MSC15000 USER MANUAL...