Fan Control Application Manual
5
AC30V series Variable Speed Drive
Outputs
Terminal
Function
Comment
ANOUT 01 (X11/03)
FAN SPEED DEMAND
Speed demand as % of maximum Fan speed
ANOUT 02 (X11/04)
FAN LOAD
Calculated fan load as % of maximum fan load
RELAY 01
(X14/01 & X14/02)
RUNNING
When closed the Fan is being driven
RELAY 02
(X14/03 & X14/04)
NOT TRIPPED
When closed the Drive is not tripped
DIGOUT 01 (X12/01)
Terminal used as DIGIN 04
DIGOUT 02 (X12/02)
Terminal used as DIGIN 05
DIGOUT 03 (X12/03)
Terminal used as DIGIN 06
DIGOUT 04 (X12/04)
Terminal used as DIGIN 07
RELAY 11
(X23/01 & X23/02)
FIRE MODE ACTIVATED
When closed Fire Mode is currently Activated
RELAY 12
(X23/03 & X23/04)
FIRE MODE READY
When closed Fire Mode is Ready for Activation
DIGOUT 11 (X20/01)
LOAD WARNING
Abnormal load detection low warning (belt slipping)
DIGOUT 12 (X20/02)
LOAD FAULT
Abnormal load detection low fault (belt broken)
DIGOUT 13 (X20/03)
Not used
DIGOUT 14 (X20/03)
Not used