![Parker AC30 series Product Manual Download Page 12](http://html.mh-extra.com/html/parker/ac30-series/ac30-series_product-manual_755681012.webp)
6
AC30 series General Purpose I/O Option
Digital Inputs and Outputs (7004-01-00 only)
The GPIO option 7004-01-00 offers four identical ports on X20 that can
be individually configured as digital input or digital output.
Terminal
Name
Range
Description
X20
01
DIN11 /
DOUT11
0 to
24VDC
Digital Input / Output 11
(default = unassigned input).
See the notes below.
02
DIN12 /
DOUT12
0 to
24VDC
Digital Input / Output 12
(default = unassigned input).
See the notes below.
03
DIN13 /
DOUT13
0 to
24VDC
Digital Input / Output 13
(default = unassigned input).
See the notes below.
04
DIN14 /
DOUT14
0 to
24VDC
Digital Input / Output 14
(default = unassigned input).
See the notes below.
05
+24V DC
IN
24V ± 10%
24V DC Input. Required to
power digital outputs
DOUT11 to DOUT14. See
the notes below.
06
DIG 0V
0V
0V reference for 7004-01-
XXX Digital Inputs and
Outputs. See the notes
below.
Note 1:
If any of X20/01 to X20/04 is to be configured as digital output, then
X20/05 must be connected to the positive output from a 24V supply,
and X20/06 must be connected to the negative output from the same
supply. See the example applications on page 11.
Note 2:
Digital input and output ports on the 7004-01-00 are fully isolated
from the drive electronics. Therefore it is essential that X20/06 is
connected to the user’s 0V signal reference which should be
grounded at an appropriate point in the system.