Option Modules

General Purpose IO Option (GPIO)

HA501836U001 Issue 3

Technical Manual

aerospace

aerospace

climate control

climate control

electromechanical

fi ltration

fi ltration

fl uid & gas handling

fl uid & gas handling

hydraulics

hydraulics

pneumatics

pneumatics

process control

process control

sealing & shielding

sealing & shielding

ENGINEERING 

YOUR 

SUCCESS

Summary of Contents for AC30 series

Page 1: ...al Manual aerospace aerospace climate control climate control electromechanical filtration filtration fluid gas handling fluid gas handling hydraulics hydraulics pneumatics pneumatics process control process control sealing shielding sealing shielding ENGINEERING YOUR SUCCESS ...

Page 2: ...l performance endurance maintenance safety and warning requirements of the application are met The user must analyze all aspects of the application follow applicable industry standards and follow the information concerning the product in the current product catalog and in any other materials provided from Parker or its subsidiaries or authorized distributors To the extent that Parker or its subsid...

Page 3: ...very effort has been taken to ensure the accuracy of this document it may be necessary without notice to make amendments or correct omissions Parker cannot accept responsibility for damage injury or expenses resulting therefrom Parker Hannifin Manufacturing Limited is referred to throughout this document as Parker WARRANTY The general terms and conditions of sale of goods and or services of Parker...

Page 4: ...tablished safety practices with the installation process operation and maintenance of this equipment and with all the hazards involved Product Warnings DANGER Risk of electric shock WARNING Hot surfaces Caution Refer to documentation Earth Ground Protective Conductor Terminal CAUTION APPLICATION RISK The specifications processes and circuitry described herein are for guidance only and may need to ...

Page 5: ...ere is conflict between EMC and Safety requirements personnel safety shall always take precedence Never perform high voltage resistance checks on the wiring without first disconnecting the drive from the circuit being tested Whilst ensuring ventilation is sufficient provide guarding and or additional safety systems to prevent injury or damage to equipment When replacing a drive in an application a...

Page 6: ...gramming 13 Specification 13 Example Application 14 Motor Thermistor 7004 01 00 7004 02 00 and 7004 03 00 15 Programming 15 Specification 16 Example Application 16 Volt free Relays 7004 01 00 only 17 Programming 17 Specification 18 Example application 18 Real Time Clock 7004 01 00 and 7004 03 00 19 Programming 19 Specification 19 Environmental 21 Restriction Evaluation Authorisation and Restrictio...

Page 7: ...pansion according to the full product code Understanding the Product Code The GPIO product codes are 7004 XX 00 and are available with different features Product Code Features available 7004 01 00 4 x Digital Inputs or Outputs 3 x Analogue Inputs 1 x Motor Thermistor Input 2 x Volt free Relay Outputs Real Time Clock 7004 02 00 1 x Motor Thermistor Input 7004 03 00 1 x Motor Thermistor Input Real T...

Page 8: ...he AC30 product manual Chapter 1 Safety before installing or removing a GPIO option 2 Ensure all power is removed from the drive 3 Remove the GKP by pulling from the top down and remove 4 After removing the screw slide the VCM lower cover down slightly and then remove ...

Page 9: ... AC30 series General Purpose I O Option 5 Click the Option into place and tighten the retaining screw as shown 6 Slide and click back the VCM lower cover tighten the retaining screw and slot back the GKP ...

Page 10: ...4 AC30 series General Purpose I O Option User Terminals The GPIO range contains blocks of user terminals as shown below Digital Inputs and Outputs Analogue Inputs Thermistor Input Relay Outputs ...

Page 11: ...nternal Sourced from drive s internal supplies Its purpose is to power the option module except digital outputs Maximum consumption 7004 01 00 1W Power consumption external Sourced from user supply Its purpose is to power digital outputs Maximum consumption 7004 01 00 only 500mA 24V ...

Page 12: ... Digital Input Output 14 default unassigned input See the notes below 05 24V DC IN 24V 10 24V DC Input Required to power digital outputs DOUT11 to DOUT14 See the notes below 06 DIG 0V 0V 0V reference for 7004 01 XXX Digital Inputs and Outputs See the notes below Note 1 If any of X20 01 to X20 04 is to be configured as digital output then X20 05 must be connected to the positive output from a 24V s...

Page 13: ...ithin the 7004 01 00 that can be configured by the user and INPUT is a signal within the 7004 01 00 that can be monitored by the user If OUTPUT CONTROL is ON switch SW is closed and X20 01 outputs a high level 24V If OUTPUT CONTROL is OFF switch SW is open and the resistor pulls X20 01 low 0V INPUT always reports the logic level at the user terminal Configure a port as input To select a port as an...

Page 14: ...08 0 DOUT11 low level output or port is configured as input 1 DOUT11 high level output 09 0 DOUT12 low level output or port is configured as input 1 DOUT12 high level output 10 0 DOUT13 low level output or port is configured as input 1 DOUT13 high level output 11 0 DOUT14 low level output or port is configured as input 1 DOUT14 high level output 12 to 13 x Unused Value don t care 14 15 x These con...

Page 15: ...parameter 0005 Parameter Access Bit Value Description 0005 Read only 00 to 07 x Used by functions on the base I O 08 0 DIN11 is low 1 DIN11 is high 09 0 DIN12 is low 1 DIN12 is high 10 0 DIN13 is low 1 DIN13 is high 11 0 DIN14 is low 1 DIN14 is high 12 to 15 0 Not used Value is always 0 ...

Page 16: ... functional only intended to eliminate ground loops It is not a safety isolation barrier Conformance to standard EN61131 2 2007 Digital Outputs DOUT11 to DOUT14 Feature Value Output high voltage X20 05 2V Maximum output current high level 160mA per output Output leakage current Low output level 0 1mA Overload short circuit protection Indefinite Each output is protected by a self resetting fuse Upd...

Page 17: ...11 AC30 series General Purpose I O Option Example Applications Digital Input to DIN11 Digital Output from DOUT11 X20 06 X20 01 24V PSU CLASS II 24V PSU CLASS II X20 06 X20 05 X20 01 LOAD ...

Page 18: ...put ports are differential That means that the signal reference on terminal X21 01 is not directly connected internally to the drive s 0V terminal It is allowed to float relative to the drive s 0V within the limits of the common mode voltage range see specification on page 13 This effectively eliminates ground loops Therefore X21 01 must be connected to the user s 0V signal reference which should ...

Page 19: ...ue of ANIN13 Specification Analogue Inputs ANIN11 to ANIN13 Common mode voltage range 10V X21 01 relative to drive 0V Input voltage range 10V to 10V each analogue input relative to terminal X21 01 Overrange 2 Accuracy Better than 1 Absolute maximum input voltage 20V to 20V relative to terminal X21 01 Input impedance 50kΩ Resolution 12 bits sign Sample rate 1ms Conformance to standard EN61131 2 200...

Page 20: ...14 AC30 series General Purpose I O Option Example Application 10V Analogue Input to ANIN11 10V PSU CLASS II 10V PSU CLASS II X21 01 X21 02 ...

Page 21: ...cription X22 01 TH1 0 to 4 5kΩ Connect motor thermistor between these two terminals If thermistor is not required connect these two terminals together and ensure PTC thermistor is selected 02 TH2 Programming Parameter Access Value Description 1184 Write or Read NTC PTC KTY Thermistor type Default PTC 1004 Write or Read 0 to 4500Ω Thermistor trip level Default 1000Ω PTC Drive trips if thermistor re...

Page 22: ... by user Default 1kΩ Motor temperature reset threshold Resistance based on temperature threshold Default 50 of trip threshold Update rate 1 second Insulation Reinforced insulation between thermistor terminals and drive electronics Important safety information Insulation and routing of wiring to the GPIO thermistor terminals must be appropriately rated to ensure the correct degree of insulation to ...

Page 23: ...12B Terminal B of relay 12 default unassigned Important safety information Insulation and routing of wiring to the relay terminals must be appropriately rated to ensure the correct degree of insulation to other user wiring including the motor thermistor both inside and outside the drive Programming Parameter Access Bit Value Description 00022 Write or Read 0 to 13 x These bits control other I O on...

Page 24: ...ching capacity 100µA 100mVDC Recommended load Resistive Contact suppression None External components must be added to protect the relay contacts against inductive or capacitive loads Expected life 300 x 103 operations Electrical 20 x 106 operations Mechanical Example application Relay Output RLY11 to 230VAC Load 230V AC Note the load must be earthed if necessary for safety LOAD X23 02 X23 01 ...

Page 25: ... a long period of time Adjustment is achieved through an RTC trim parameter A positive value causes the RTC to run faster A negative value causes the RTC to run slower Each increment or decrement in RTC trim value causes the RTC to run faster or slower respectively by 1 part in 1048576 or approximately 1 part per million ppm 1ppm is equivalent to approximately 2 5 seconds per month or 31 seconds p...

Page 26: ...y Unspecified User can set time on first power up Accuracy drive powered RTC trim 0 1 minute month Accuracy drive unpowered RTC trim 0 5 minutes month Battery backup duration This is the minimum length of time the RTC will continue to run while the drive is unpowered 6 months Automatic adjustment for daylight saving Not supported ...

Page 27: ...article manufacturers or importers into Europe are obligated under Article 33 of REACH to inform recipients of any articles that contain chemicals on the Substances of Very High Concern SVHC candidate list above a 0 1 concentration by weight per article As of 19th December 2011 VSD products manufactured and marketed by Parker do not contain substances on the REACH SVHC candidate list in concentrat...

Page 28: ... Hydride Ni MH battery Parker Hannifin Company together with local distributors and in accordance with EU directive 2002 96 EC undertakes to withdraw and dispose of its products fully respecting environmental considerations For more information about how to recycle your Parker supplied waste equipment please contact your local Parker Service Centre Packaging During transport our products are prote...

Page 29: ... com IE Ireland Dublin Tel 353 0 1 466 6370 parker ireland parker com IN India Mumbai Tel 91 22 6513 7081 85 IT Italy Corsico MI Tel 39 02 45 19 21 parker italy parker com JP Japan Tokyo Tel 81 0 3 6408 3901 KR South Korea Seoul Tel 82 2 559 0400 KZ Kazakhstan Almaty Tel 7 7272 505 800 parker easteurope parker com MX Mexico Apodaca Tel 52 81 8156 6000 MY Malaysia Shah Alam Tel 60 3 7849 0800 NL Th...