Page 8
Dimensions
Dimensions are in millimeters (
X
: Power Bracket - 890 Installation Kit,
Y
: Control Bracket
)
The units must be installed in a cubicle. Mount the drive using the keyholes and slots or on a 35mm
DIN rail using the 890 Installation Kit supplied.
IMPORTANT:
The 890CS Common Bus Supply is normally mounted to the left of the 890CD
Common Bus Drive(s). However, for 890CS Frame D, mount the 890CS between the
890CD units to share the load evenly if the total current draw on the DC busbar will
exceed 140A. Connect to the left and right busbar terminals separately. The busbar is
rated for operation at 140A. Do not exceed 140A.
Ventilation
The drives can be mounted side-by-side with no clearance. A minimum
of 150mm (6 inches) free-air space must be allowed at the top and
bottom of each drive. If mounting drives above or below other
equipment, the top and bottom distances should be added for overall
clearance between drives.
Environmental Conditions
Operating ambient temperature
0°C to 45°C (32°F to 113°F)
Enclosure rating
IP20 – UL(cUL) Open type
Atmosphere
Dust free, non flammable, non-corrosive, <85% humidity,
non-condensing
Summary of Contents for 890CS
Page 9: ...Page 9 Overview...
Page 27: ...Page 27 890CD Control Terminals...
Page 28: ...Page 28 890SD Control Terminals...
Page 29: ...Page 29 890CS Control Terminals...
Page 30: ...Page 30 Appendix D Electrical Ratings 890CS Common Bus Supply...
Page 31: ...Page 31 890CD Common Bus Drive...
Page 32: ...Page 32...
Page 33: ...Page 33...