Installation
A simplified installation is shown below. This installation is
not
EMC compliant. For European
installations and countries with EMC legislation refer to the 890 Engineering Reference Manual,
Appendix C.
KEY
B
Back-plate
C
Cubicle
G
Supply
Protective
Earth/Ground
K
Motor
(M1, M2, M3)
L
3
∅
Power
Supply Cable
(L1, L2, L3)
P
Fuse or circuit
breaker
R
AC Line
Reactor
T
Control Wiring
Terminals
890 Installation Kit
The 890 Installation Kit is shown in the diagram attached to the bottom of
the 890CD units. It can also be fixed to the top of the unit.
The kit provides several options for earth/ground connections. It also
includes the brackets for DIN rail mounting the unit. Refer to the instructions
in the kit and use the appropriate parts.
* Permanent Earthing
The unit must be
permanently earthed
according to EN 50178: A cross-
section conductor of at least 10mm² is required. This can be achieved either
by using a single conductor (PE) or by laying a second conductor though
separate terminals (PE2 where provided) and electrically in parallel.
Summary of Contents for 890CS
Page 9: ...Page 9 Overview...
Page 27: ...Page 27 890CD Control Terminals...
Page 28: ...Page 28 890SD Control Terminals...
Page 29: ...Page 29 890CS Control Terminals...
Page 30: ...Page 30 Appendix D Electrical Ratings 890CS Common Bus Supply...
Page 31: ...Page 31 890CD Common Bus Drive...
Page 32: ...Page 32...
Page 33: ...Page 33...