![Parker 8903/IM Technical Manual Download Page 34](http://html1.mh-extra.com/html/parker/8903-im/8903-im_technical-manual_3789078034.webp)
30
8903/IM 8903/IP Ethernet Communications Interfaces
VALUE Type Connector
Data from PLC
Data to DSE
From SINT16 to VALUE
-32,768 to 32,767
-32,768.0 to 32,767.0
From SINT32 to VALUE
-2,147,483,648 to 2,147,483,547
-32,768.0 to 32,767.0
limits apply
From UINT16 to VALUE
0 to 65,535
0.0 to 32,767.0
limits apply
From UINT32 to VALUE
0 to 4,294,967,295
0.0 to 32,767.0
limits apply
From FLOAT to VALUE
32-bit IEEE floating-point
-32,768.0 to
32,767.9999
limits apply
Data from DSE
Data to PLC
From VALUE to SINT16
-32,768.0 to 32,767.9999
-32,768 to 32,767
limits apply/ rounding
applies
From VALUE to SINT32
-32,768.0 to 32,767.9999
-32768 to 32,767
limits apply/ rounding
applies
From VALUE to UINT16
-32,768.0 to 32,767.9999
0 to 32767
limits apply/ rounding
applies
From VALUE to UINT32
-32,768.0 to 32,767.9999
0 to 32767
limits apply/ rounding
applies
From VALUE to REAL
-32,768.0 to 32,767.9999
32-bit IEEE floating-
point