![Parker 8903/IM Technical Manual Download Page 28](http://html1.mh-extra.com/html/parker/8903-im/8903-im_technical-manual_3789078028.webp)
24
8903/IM 8903/IP Ethernet Communications Interfaces
Routing Failures
Error Status Register: 4xxxx + 1 (HEX)
Error Coding: Mmss where M = major code, m = minor code, ss = sub code
Routing failure error code: 6mjj
n
6m01: No response.
n
6m02: Program access denied.
n
6m03: Node is offline and unable to communicate.
n
6m04: Exception response received.
n
6m05: Route node data paths busy.
n
6m06: Slave device down.
n
6m07: Bad destination address.
n
6m08: Invalid node type in routing.
n
6m10: Slave rejected the Modbus command.
n
6m20: Slave forgot initiated translation.
n
6m40: Unexpected master output path received.
n
6m80: Unexpected response received.
Note: m = index to location in the routing information where routing problem was discovered.
0 = local network station
1 = first device in route
2 = second device in route, etc.